EP9224 commissioning

This chapter describes the commissioning or the implementation of the EP9224-0037 into TwinCAT and TIA. Because the EP9224-0037 contains two EtherCAT slave controllers (ESC), two EP9224 must also be implemented during configuration. In the automation software these are represented once with the ending -0037 and once with -1037. For more information on the process image, refer to the documentation of EP9224-0037.

EP9224 commissioning 1:Fig.37: Representation EP9224-0037 in TwinCAT
EP9224 commissioning 2:Fig.38: Representation EP9224-0037 in TIA

Each IO module has four ports. Some of these ports are used internally as interfaces to each other, which are not accessible to the user. The others are available as interfaces to the connectors on the EP box. The following illustration shows the assignment of the connectors to the ports of the I/O modules.

EP9224 commissioning 3:Fig.39: Connector designations

Type

EP9224-0037

Automation software

Connector

IO module

Port

EtherCAT P output

X52

EP9224-1037

D

EtherCAT P output

X53

B

EtherCAT P output

X54

C

EtherCAT P output

X55

EP9224-0037

B

EtherCAT input

X70

A

EtherCAT output

X71

C

If the configuration is created offline, the user must know at which port or at which connector the EtherCAT devices are present at the EP9224 in which number and in which order.

The sequence of the EtherCAT devices to be configured on the EP9224 in the automation software starts with all EtherCAT devices on connector 52, then with all on connector 53, then with all on connector 54 and ends with the last EtherCAT device on connector 55. If there are no EtherCAT device(s) at a port, this port is omitted or skipped.

Sample configuration 1

Type

EP9224-0037

Automation software

EtherCAT devices

Connector

IO module

Port

1.

2.

n.

EtherCAT P output

X52

EP9224-1037

D

EPP3204

-

-

EtherCAT P output

X53

B

EPP3314

EPP2308

-

EtherCAT P output

X54

C

EPP1018

-

-

EtherCAT P output

X55

EP9224-0037

B

EPP3184

EPP1008

-

EtherCAT input

X70

A

 

EtherCAT output

X71

C

 

EP9224 commissioning 4:Fig.40: Sample configuration 1 TwinCAT
EP9224 commissioning 5:Fig.41: Sample configuration 1 TIA

Sample configuration 2

Type

EP9224-0037

Automation software

EtherCAT devices

Connector

IO module

Port

1.

2.

3.

4.

n.

EtherCAT P output

X52

EP9224-1037

D

EPP3204

EPP3314

EPP2308

EPP1018

-

EtherCAT P output

X53

B

-

-

-

-

-

EtherCAT P output

X54

C

-

-

-

-

-

EtherCAT P output

X55

EP9224-0037

B

EPP3184

EPP1008

 

 

 

EtherCAT input

X70

A

 

EtherCAT output

X71

C

 

EP9224 commissioning 6:Fig.42: Sample configuration 2 TwinCAT
EP9224 commissioning 7:Fig.43: Sample configuration 2 TIA