Time synchronization

The “Sample Time Adjustment” configuration parameter can be used to set time synchronization with an SNTP server.

To ensure compatibility with older firmware versions, the factory setting is “Disabled”.

For synchronization, the value must be set to “Enabled”.

Time synchronization 1:
Setting the time synchronization

Time synchronization is set using the SNTP server configuration, which can be selected via the “Software -> System” web configuration page.

Time synchronization 2:
SNTP server setting

With this configuration, for example, the time server “time.windows.com” is queried every hour and written to the clocks of the EK9160.

The next MQTT timestamp sent will then be based on this new time.

To apply the new settings, a reboot must be performed.