EK1814

EK1814 1:
TwinCAT tree EK1814

Extent of process data EK1814

EK1814 2:
Extent of process data EK1814 TwinCAT
EK1814 3:
Extent of process data EK1814 TwinCAT

PDO Assignment EK1814

SM1, PDO Assignment 0x1C11

Index

Size (byte.bit)

Name

PDO content

0x1A00

0.1

Channel 1

Index 0x6000:01 - Input

0x1A01

0.1

Channel 2

Index 0x6010:01 - Input

0x1A02

0.1

Channel 3

Index 0x6020:01 - Input

0x1A03

0.1

Channel 4

Index 0x6030:01 - Input

SM0, PDO Assignment 0x1C10

Index

Size (byte.bit)

Name

PDO content

0x1608

0.1

Channel 5

Index 0x7080:01 - Output

0x1609

0.1

Channel 6

Index 0x7090:01 - Output

0x160A

0.1

Channel 7

Index 0x70A0:01 - Output

0x160B

0.1

Channel 8

Index 0x70B0:01 - Output

Table 1 + 2: PDO assignment of the SyncManagers EK1814