Diagnostic LED

Diagnostic LED 1:Fig.39: EK1322 LEDs

LEDs for fieldbus diagnostics

LED

Display

State

Description

Run

green

off

INIT

EtherCAT P module is in state Init

flashing uniformly

PREOP

EtherCAT P module is in state Pre-Operational

flashing slowly

SAFEOP

EtherCAT P module is in state Safe-Operational

on

OP

EtherCAT P module is in state Operational

LEDs for fieldbus diagnostics

LED

Display

State

Description

X1 L/A

green

off

-

No connection on the previous EtherCAT P strand

on

link

Previous EtherCAT P device connected

flashing

active

Communication with previous EtherCAT P device

X2 L/A

green

off

-

No connection on the subsequent EtherCAT P strand

on

link

Subsequent EtherCAT P device connected

flashing

active

Communication with subsequent EtherCAT P device

LEDs power supply diagnostics

LED

Display

Description

US

green

off

System- and Sensor supply US not present

on

System- and Sensor supply US present

red

off

System- and Sensor supply US >= 19.4 V, no overload/ no case of short circuit

on

System- and Sensor supply US < 19.4 V or overload/ case of short circuit (output current > 3 A)

UP

green

off

Peripheral voltage for Actors UP not present

on

Peripheral voltage for Actors UP present

red

off

Peripheral voltage for Actors UP >= 19.4 V, no overload/ no case of short circuit

on

Peripheral voltage for Actors UP < 19.4 V or overload/ case of short circuit (output current > 3 A)