Diagnostic LED
LEDs for fieldbus diagnostics
LED | Display | State | Description | |
|---|---|---|---|---|
L/A E‑Bus | green | off | - | No connection internal E-bus |
on | linked | Connection internal E-bus (Preceding terminal pass through E‑bus) | ||
flashing | active | Connection/ Communication internal E-bus (Preceding terminal pass through E‑bus) | ||
X1 L/A (out) | green | off | - | no connection on the subsequent EtherCAT P strand |
on | linked | Subsequent EtherCAT P device connected | ||
flashing | active | Communication with subsequent EtherCAT P device | ||
LED for power supply diagnosis
LED | Display | Description | |
|---|---|---|---|
US 24V | green | off | System- and Sensor supply US not present |
on | System- and Sensor supply US present | ||
UP 24V | green | off | Peripheral voltage for Actors UP not present |
on | Peripheral voltage for Actors UP present | ||
Diag UP | red | off | Peripheral voltage for Actors UP >= 19.4 V, no overload/ no case of short circuit |
on | Peripheral voltage for Actors UP < 19.4 V or overload/ case of short circuit (output current > 3 A) | ||
Diag US | red | off | System- and Sensor supply US >= 19.4 V, no overload/ no case of short circuit |
on | System- and Sensor supply US < 19.4 V or overload/ case of short circuit (output current > 3 A) | ||
LED diagnostics EtherCAT State Machine
LED | Color | Meaning | |
|---|---|---|---|
RUN | green | This LED indicates the terminal's operating state: | |
off | State of the EtherCAT State Machine: INIT = initialization of the terminal | ||
flashing uniformly | State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set | ||
flashing slowly | State of the EtherCAT State Machine: SAFEOP = verification of the sync manager channels and the distributed clocks. | ||
on | State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible | ||
flashing rapidly | State of the EtherCAT State Machine: BOOTSTRAP = function for terminal firmware updates | ||