Diagnostic LED

Diagnostic LED 1:
EK1310 LEDs

LEDs for fieldbus diagnostics

LED

Display

State

Description

L/A E-Bus

green

off

-

No connection internal E-bus

on

linked

Connection internal E-bus (Preceding terminal pass through E‑bus)

flashing

active

Connection/ Communication internal E-bus (Preceding terminal pass through E‑bus)

X1 L/A (out)

green

off

-

no connection on the subsequent EtherCAT P strand

on

linked

Subsequent EtherCAT P device connected

flashing

active

Communication with subsequent EtherCAT P device

LED for power supply diagnosis

LED

Display

State

Description

US 24V

green

off

 

System- and Sensor supply US not present

on

 

System- and Sensor supply US present

UP 24V

green

off

 

Peripheral voltage for Actors UP not present

on

 

Peripheral voltage for Actors UP present

Diag UP

red

off

 

Peripheral voltage for Actors UP >= 19.4 V, no overload/ no case of shortcut

on

 

Peripheral voltage for Actors UP < 19.4 V or overload/ case of shortcut (output current > 3 A)

Diag US

red

off

 

System- and Sensor supply US >= 19.4 V, no overload/ no case of shortcut

on

 

System- and Sensor supply US < 19.4 V or overload/ case of shortcut (output current > 3 A)

LED diagnostics EtherCAT State Machine

LED

Color

Meaning

RUN

green

This LED indicates the terminal's operating state:

off

State of the EtherCAT State Machine: INIT = initialization of the terminal

flashing uniformly

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set

flashing slowly

State of the EtherCAT State Machine: SAFEOP = verification of the sync manager channels and the distributed clocks.
Outputs remain in safe state

on

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible

flashing rapidly

State of the EtherCAT State Machine: BOOTSTRAP = function for terminal firmware updates