Technical data

Technical data

EK1101-0010

Task in the EtherCAT system

Coupling of EtherCAT Terminals (ELxxxx) to 100BASE-TX or BroadR EtherCAT P networks

Extended distance connection

Number of EtherCAT Terminals

up to 65535 in the overall system

Number of peripheral signals

max. 4.2 GB addressable I/O points

Data transfer medium

Ethernet 100BASE - TX (at least Ethernet CAT5 cable)

Cable length between 2 bus couplers

max. 100 m (100BASE-TX)

max. 300 m (copper, Cat. 5, 4-wire) for connection between two couplers with extended distance connection

max. 200 m (copper, Cat. 5, 4-wire) for connection between two couplers with extended distance connection,
at ambient temperature < 0°C or > +55°C

Protocol / Baud rate

EtherCAT Device Protocol / 100 MBaud

HotConnect

max. number of configurable IDs: 4096

Propagation delay

1 µs typ.

Bus connection

2 x RJ45

Power supply

24 VDC (-15 %/+20 %)

Current consumption

90 mA + (∑ E-bus current)/4

E-bus power supply (5 V)
dependent on the ambient temperature

(at higher current consumption the EL9410 power supply terminal can be used in addition)

max. 2 A (-25°C ... +55°C)

max. 1 A (> +55°C)

Power contacts

max. 24 VDC, max. 10 A

Electrical isolation

500 V (power contact/supply voltage/EtherCAT)

Dimensions (W x H x D)

approx. 44 mm x 100 mm x 68 mm

Weight

approx. 105 g

Permissible ambient temperature range during operation

-25 °C ... +60 °C

Permissible ambient temperature range during storage

-40 °C... + 85 °C

Permissible relative air humidity

95 %, no condensation

Installation

on 35 mm mounting rail, conforms to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Installation position

variable

Approvals / markings*)

CE, EAC, UKCA,
cULus

*) Real applicable approvals/markings see type plate on the side (product marking).