Application with EK1541
![]() | Recommended plug connectors and POF cables For the connection of the EK1541 it is recommended to use the connector set ZS1090-0008 (Versatile Link Duplex connectors) in conjunction with a duplex polymer fiber with an outside diameter of 2 x 2.2 mm (Z1190), which are available from Beckhoff. |
![]() | Installation notes
|
Connecting and releasing the POF cable at the coupler
To connect the cable, insert the plug (available as an accessory in the plug set ZS1090-0008) into the connection opening until it audibly latches.

To release the connector activate the release device with the latching lug. This can be found on the right-hand side of the connector (see figure).
Notice | |
Risk of damage to the cable! To release the cable, press the release catch on the plug and pull the plug at the same time – never pull by the POF cable alone! |
Notice | |
TX / Rx channel assignment During cable assembly note the assignment of the optical channels in the connection sockets. In the EK1541 the light-emitting transmitter channel (Tx) is the lower outlet in the connection sockets. |
Notice | |
Use of blind plugs In order to avoid accidents due to glare (Class 1 laser, please observe the safety instructions) and to protect the transceiver against environmental influences, unused sockets should be sealed using the blind plugs provided! |