Technical data - Signal distribution board
Technical data | Signal distribution board |
|---|---|
PCB layer stack | Multilayer PCB, min. 4 layers |
PCB thickness | 1.6 mm ± 10 % |
Board connector | Samtec: SSQ-120-01-L-D |
Starting from the left: | |
EJ1100 (2.2 A) | |
EJ9400 (2.5 A) | |
Air gap and leakage distances between E-bus- and field signals | typ. 1.2 mm |
Differential impedance of the LVDS traces | 100 Ω |
SGND connection | via mounting bolts |
max. 100 mm | |
92 mm | |
Module depth above PCB | min. 55 mm |
Distance between PCB and mounting surface | min. 4 mm |
Standard |
Description of potential groups | |
|---|---|
UEBUS: Power supply E-bus | The power supply UEBUS is provided by the coupler and supplied from the supply voltage Us of the EtherCAT coupler. UEBUS: E-bus power supply 3.3 V GND: E-bus GND signal; |
Us: Power supply bus side | The power supply Us is used to supply the bus coupler electronics and to generate voltage for the E-bus (UEBUS). 0 V Us: Bus side GND signal 24 V Us: Bus side power supply 24 V |
Up: Power supply field side | The peripheral voltage Up supplies the electronics on the field side. 0 V Up: GND signal field side 24 V Up: Power supply field side 24 V |
SGND: Shield Ground | Ground signal with shielding function in relation to the rest of the board |
Notice | |
Damage to devices possible Note the specifications and notes for the components used! |