Latch and Gate/Latch inputs
The module provides two digital 24 VDC inputs. The function of these inputs is described in the respective chapter.
- Latch input (Latch extern)
- Gate/latch input (Latch extern 2)
Both inputs are type 3 inputs according to EN61131-2, with a minimum pulse duration of tON > 1µs.
Digital input type 3, according to EN61131-2 | Voltage [V] | Input current [mA] |
|---|---|---|
Signal voltage "0 - LOW" | -3 V ... +5 V typ. | 0 mA ... 2.6 mA typ. |
Signal voltage "1 - HIGH" | 11 V ... 30 V typ. | typ. 2.5 mA |

Notice | |
Be aware of bouncing when using electromechanical switches and push buttons When using electromechanical switches and push buttons, repeated closing and opening of the switch or push button can occur when the switch or push button is actuated, which is referred to as bouncing.
|