LEDs

Single-Channel mode 1 x ABC
No. | Name | Color | Description | ||
|---|---|---|---|---|---|
A | Run | green | This LED indicates the module´s operating state: | ||
off | State of the EtherCAT State Machine: INIT = initialization of the module or BOOTSTRAP = function for firmware updates of the module | ||||
flashing | State of the EtherCAT State Machine: PREOP = function for mailbox communication and different default settings set | ||||
Single flash | State of the EtherCAT State Machine: SAFEOP = verification of the Sync-Manager channels and the distributed clocks. Outputs remain in safe state | ||||
on | State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication are possible | ||||
B | Diag | red | Initialization process active or state of the EtherCAT State Machine: BOOT | ||
C | ENC | green | Operating voltage display for incremental encoder power supply | ||
1 | - | - | - | ||
2 | A1 | green, red | green: indicates TRUE level red: There is a broken wire at the respective input. Diagnosis is only possible if the following three conditions are met.
| ||
3 | B1 | ||||
4 | C1 | ||||
5 | DI neg | green | Fault signal input from encoder. Input is internally connected to 5 V via a pull-up resistor. The encoder output must actively pull the signal against GND. | ||
ON | Output active at the encoder, a fault message is present at the encoder | ||||
OFF | Output not active at the encoder; no fault message is present | ||||
6 | Latch | green | is on, if a signal (+24 V) is presented to the latch input | ||
7 | Gate | green | is on if a signal (+24 V) is presented at the gate/latch input | ||

Two-Channel mode 2 x AB
No. | Name | Color | Description | |
|---|---|---|---|---|
A | Run | green | This LED indicates the module´s operating state: | |
off | State of the EtherCAT State Machine: INIT = initialization of the module or BOOTSTRAP = function for firmware updates of the module | |||
flashing | State of the EtherCAT State Machine: PREOP = function for mailbox communication and different default settings set | |||