Standard objects (0x1000-0x1FFF)
The standard objects have the same meaning for all EtherCAT slaves.
Index 1000 Device type
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1000:0  | Device type  | Device type of the EtherCAT slave: 
  | UINT32  | RO  | 0x01F51389 (32838537dec)  | 
Index 1008 Device name
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1008:0  | Device name  | Device name of the EtherCAT slave  | STRING  | RO  | EJ5002  | 
Index 1009 Hardware version
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1009:0  | Hardware version  | Hardware version of the EtherCAT slave  | STRING  | RO  | 00  | 
Index 100A Software version
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
100A:0  | Software version  | Firmware version of the EtherCAT slave  | STRING  | RO  | 01  | 
Index 1018 Identity
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1018:0  | Identity  | Information for identifying the slave  | UINT8  | RO  | 0x04 (4dec)  | 
1018:01  | Vendor ID  | Vendor ID of the EtherCAT slave  | UINT32  | RO  | 0x00000002 (2dec)  | 
1018:02  | Product code  | Product code of the EtherCAT slave  | UINT32  | RO  | 0x138A2852 (327821394dec)  | 
1018:03  | Revision  | Revision number of the EtherCAT slave 
  | UINT32  | RO  | 0x00000000 (0dec)  | 
1018:04  | Serial number  | Serial number of the EtherCAT slave: 
  | UINT32  | RO  | 0x00000000 (0dec)  | 
Index 10F0 Backup parameter handling
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
10F0:0  | Backup parameter handling  | Information for standardized loading and saving of backup entries  | UINT8  | RO  | 0x01 (1dec)  | 
10F0:01  | Checksum  | Checksum across all backup entries of the EtherCAT slave  | UINT32  | RO  | 0x00000000 (0dec)  | 
Index 1A00 SSI TxPDO-Map Inputs
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A00:0  | SSI TxPDO Map Inputs  | PDO Mapping TxPDO 1  | UINT8  | RO  | 0x09 (9dec)  | 
1A00:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6000 (SSI Inputs), entry 0x01 (Data error))  | UINT32  | RO  | 0x6000:01, 1  | 
1A00:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x6000 (SSI Inputs), entry 0x02 (Frame error))  | UINT32  | RO  | 0x6000:02, 1  | 
1A00:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x6000 (SSI Inputs), entry 0x03 (Power failure))  | UINT32  | RO  | 0x6000:03, 1  | 
1A00:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x6000 (SSI Inputs), entry 0x04 (Data mismatch))  | UINT32  | RO  | 0x6000:04, 1  | 
1A00:05  | SubIndex 005  | 5. PDO Mapping entry (9 bits align)  | UINT32  | RO  | 0x0000:00, 9  | 
1A00:06  | SubIndex 006  | 6. PDO Mapping entry (object 0x6000 (SSI Inputs) entry 0x0E) (Sync error))  | UINT32  | RO  | 0x6000:0E, 1  | 
1A00:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x6000 (SSI Inputs) entry 0x0F) (TxPDO State))  | UINT32  | RO  | 0x6000:0F, 1  | 
1A00:08  | SubIndex 008  | 8. PDO Mapping entry (object 0x6000 (SSI Inputs) entry 0x10) (TxPDO Toggle))  | UINT32  | RO  | 0x6000:10, 1  | 
1A00:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x6000 (SSI Inputs), entry 0x11 (Counter value))  | UINT32  | RO  | 0x6000:11, 32  | 
Index 1A01 SSI TxPDO-Map Inputs
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A01:0  | SSI TxPDO Map Inputs  | PDO Mapping TxPDO 2  | UINT8  | RO  | 0x09 (9dec)  | 
1A01:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6010 (SSI Inputs), entry 0x01 (Data error))  | UINT32  | RO  | 0x6010:01, 1  | 
1A01:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x6010 (SSI Inputs), entry 0x02 (Frame error))  | UINT32  | RO  | 0x6010:02, 1  | 
1A01:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x6010 (SSI Inputs), entry 0x03 (Power failure))  | UINT32  | RO  | 0x6010:03, 1  | 
1A01:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x6010 (SSI Inputs), entry 0x04 (Data mismatch))  | UINT32  | RO  | 0x6010:04, 1  | 
1A01:05  | SubIndex 005  | 5. PDO Mapping entry (9 bits align)  | UINT32  | RO  | 0x0000:00, 9  | 
1A01:06  | SubIndex 006  | 6. PDO Mapping entry (object 0x6010 (SSI Inputs), entry 0x0E (Sync error))  | UINT32  | RO  | 0x6010:0E, 1  | 
1A01:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x6010 (SSI Inputs), entry 0x0F (TxPDO State))  | UINT32  | RO  | 0x6010:0F, 1  | 
1A01:08  | SubIndex 008  | 8. PDO Mapping entry (object 0x6010 (SSI Inputs), entry 0x10 (TxPDO Toggle))  | UINT32  | RO  | 0x6010:10, 1  | 
1A01:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x6010 (SSI Inputs), entry 0x11 (Counter value))  | UINT32  | RO  | 0x6010:11, 32  | 
Index 1C00 Sync manager type
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C00:0  | Sync manager type  | Using the Sync Managers  | UINT8  | RO  | 0x04 (4dec)  | 
1C00:01  | SubIndex 001  | Sync-Manager Type Channel 1: Mailbox Write  | UINT8  | RO  | 0x01 (1dec)  | 
1C00:02  | SubIndex 002  | Sync-Manager Type Channel 2: Mailbox Read  | UINT8  | RO  | 0x02 (2dec)  | 
1C00:03  | SubIndex 003  | Sync-Manager Type Channel 3: Process Data Write (Outputs)  | UINT8  | RO  | 0x03 (3dec)  | 
1C00:04  | SubIndex 004  | Sync-Manager Type Channel 4: Process Data Read (Inputs)  | UINT8  | RO  | 0x04 (4dec)  | 
Index 1C12 RxPDO assign
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C12:0  | RxPDO assign  | PDO Assign Outputs  | UINT8  | RW  | 0x00 (0dec)  | 
Index 1C13 TxPDO assign
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C13:0  | TxPDO assign  | PDO Assign Inputs  | UINT8  | RO  | 0x02 (2dec)  | 
1C13:01  | SubIndex 001  | 1. allocated TxPDO (contains the index of the associated TxPDO mapping object)  | UINT16  | RO  | 0x1A00 (6656dec)  | 
1C13:02  | SubIndex 002  | 2. allocated TxPDO (contains the index of the associated TxPDO mapping object)  | UINT16  | RO  | 0x1A01 (6657dec)  | 
Index 1C33 SM input parameter
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C33:0  | SM input parameter  | Synchronization parameters for the inputs  | UINT8  | RO  | 0x20 (32dec)  | 
1C33:01  | Sync mode  | Current synchronization mode: 
  | UINT16  | RW  | 0x0022 (34dec)  | 
1C33:02  | Cycle time  | Cycle time (in ns): 
  | UINT32  | RW  | 0x000F4240 (1000000dec)  | 
1C33:03  | Shift time  | Time between SYNC0 event and reading of the inputs (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:04  | Sync modes supported  | Supported synchronization modes: 
  | UINT16  | RO  | 0xC00B (49163dec)  | 
1C33:05  | Minimum cycle time  | Minimum cycle time (in ns)  | UINT32  | RO  | 0x0001D4C0 (120000dec)  | 
1C33:06  | Calc and copy time  | Time between reading of the inputs and availability of the inputs for the master (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:07  | Minimum delay time  | Minimum time between Sync 1 Event and reading of the inputs (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:08  | Command  | With this entry the real required process data provision time can be measured. 
 The entries 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values.  | UINT16  | RW  | 0x0000 (0dec)  | 
1C33:09  | Maximum Delay time  | Time between SYNC1 event and reading of the inputs (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:0B  | SM event missed counter  | Number of missed SM events in OPERATIONAL (DC mode only)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C33:0C  | Cycle exceeded counter  | Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C33:0D  | Shift too short counter  | Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C33:20  | Sync error  | The synchronization was not correct in the last cycle (outputs were output too late; DC mode only)  | BOOLEAN  | RO  | 0x00 (0dec)  |