Information and diagnostic data

Index 80nE TC Internal data for 0 ≤ n ≤ 7 (Ch. 1 - 8)

Index (hex)

Name

Meaning

Data type

Flags

Default

80nE:0

TC Internal data Ch.n

Maximum subindex

UINT8

RO

0x05 (5dec)

80nE:01

ADC raw value TC

ADC raw value thermocouple

INT32

RO

0x00000000 (0dec)

80nE:03

CJ temperature

Cold junction temperature (resolution [1/10]°C)

INT16

RO

0x0000 (0dec)

80nE:04

CJ voltage

Cold junction voltage (resolution 1 μV)

INT32

RO

0x00000000 (0dec)

80nE:05

CJ resistor

reserved

UINT16

RO

0x0000 (0dec)

Index 808E RTD Internal data Ch. 1

Index (hex)

Name

Meaning

Data type

Flags

Default

808E:0

RTD Internal data Ch.1

Maximum subindex

UINT8

RO

0x04 (4dec)

808E:01

ADC raw value

ADC raw value

INT32

RO

0x00000000 (0dec)

808E:02

Resistor

Resistance (measured value of resistance sensor, resolution 1/256 Ohm)

UINT32

RO

0x00000000 (0dec)

Index 809E RTD Internal data Ch. 2

Index (hex)

Name

Meaning

Data type

Flags

Default

809E:0

RTD Internal data Ch.2

Maximum subindex

UINT8

RO

0x04 (4dec)

809E:01

ADC raw value

ADC raw value

INT32

RO

0x00000000 (0dec)

809E:02

Resistor

Resistance (measured value of resistance sensor, resolution 1/256 Ohm)

UINT32

RO

0x00000000 (0dec)

Index F000 Modular device profile

Index (hex)

Name

Meaning

Data type

Flags

Default

F000:0

Modular device profile

General information for the modular device profile

UINT8

RO

0x02 (2dec)

F000:01

Module index distance

Index spacing of the objects of the individual channels

UINT16

RO

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RO

0x000A (10dec)

Index F008 Code word

Index (hex)

Name

Meaning

Data type

Flags

Default

F008:0

Code word

currently reserved

UINT32

RW

0x00000000 (0dec)

Index F010 Module list

Index (hex)

Name

Meaning

Data type

Flags

Default

F010:0

Module list

Maximum subindex

UINT8

RO

0x0A (10dec)

F010:01

Subindex 001

Profile 330

INT32

RO

0x0000014A (330dec)

F010:02

Subindex 002

Profile 330

INT32

RO

0x0000014A (330dec)

F010:03

Subindex 003

Profile 330

INT32

RO

0x0000014A (330dec)

F010:04

Subindex 004

Profile 330

INT32

RO

0x0000014A (330dec)

F010:05

Subindex 005

Profile 330

INT32

RO

0x0000014A (330dec)

F010:06

Subindex 006

Profile 330

INT32

RO

0x0000014A (330dec)

F010:07

Subindex 007

Profile 330

INT32

RO

0x0000014A (330dec)

F010:08

Subindex 008

Profile 330

INT32

RO

0x0000014A (330dec)

F010:09

Subindex 009

Profile 320

INT32

RO

0x00000140 (320dec)

F010:0A

Subindex 010

Profile 320

INT32

RO

0x00000140 (320dec)