Configuration data
Index 80n0 TC settings for 0 ≤ n ≤ 7 (Ch. 1 - 8)
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
80n0:0  | TC Settings  | Maximum subindex  | UINT8  | RO  | 0x1B (27dec)  | 
80n0:01  | Enable user scale  | User scale is active.  | BOOLEAN  | RW  | 0x00 (0dec)  | 
80n0:02  | Presentation  | 0: Signed presentation 1: Absolute value with MSB as sign 2: High resolution (1/100°C)  | BIT3  | RW  | 0x00 (0dec)  | 
80n0:05  | Siemens bits  | The S5 bits are superimposed on the three low-order bits (value 0x60n0:11) Bit 0 = 1 (“overrange” or “underrange”)  | BOOLEAN  | RW  | 0x00 (0dec)  | 
80n0:06  | Enable filter  | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary  | BOOLEAN  | RW  | 0x00 (0dec)  | 
80n0:0A  | Enable user calibration  | Enabling of the user calibration  | BOOLEAN  | RW  | 0x00 (0dec)  | 
80n0:0B  | Enable vendor calibration  | Enabling of the vendor calibration  | BOOLEAN  | RW  | 0x01 (1dec)  | 
80n0:0C  | Coldjunction compensation  | 0: internal 1: no 2: Extern process data  | BIT2  | RW  | 0x00 (0dec)  | 
80n0:11  | User scale offset  | User scaling offset  | INT16  | RW  | 0x0000 (0dec)  | 
80n0:12  | User scale gain  | This is the user scaling gain.  | INT32  | RW  | 0x00010000 (65536dec)  | 
80n0:15  | Filter settings  | This object determines the digital filter settings, if it is active via Enable filter (index 80n0:06). 0: 50 Hz  | UINT16  | RW  | 0x0000 (0dec)  | 
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
80n0:17  | User calibration offset  | User offset calibration  | UINT16  | RW  | 0x0000 (0dec)  | 
80n0:18  | User calibration gain  | User gain compensation  | UINT16  | RW  | 0xFFFF (65535dec)  | 
80n0:19  | TC element  | Thermocouple 0: K, -200°C to 1370°C  | UINT16  | RW  | 0x0000 (0dec)  | 
![]()  | The filter characteristics are set via index 0x8000:15 The filter frequencies are set for all channels of the module centrally via index 0x8000:15 (channel 1). All other corresponding indices 0x80n0:15 have no parameterization function! The latest firmware version (see status table) returns an EtherCAT-compliant error message, if the filter characteristics of other channels (index 0x80n0:06, 0x80n0:15) are set.  | 
Index 8080 RTD Settings Ch. 1
Index (hex)  | Name  | Bedeutung  | Datentyp  | Flags  | Default  | 
|---|---|---|---|---|---|
8080:0  | RTD Settings Ch1.  | Maximum subindex  | UINT8  | RO  | 0x1B (27dec)  | 
8080:19  | RTD element  | RTD element 2: PT1000 (-200…850°C)  | BOOLEAN  | RW  | 0x02 (2dec)  | 
8080:1A  | Connection technology  | Permitted values 0: Two-wire connection  | BIT3  | RW  | 0x00 (0dec)  | 
8080:1B  | Wire calibration 1/32 Ohm  | Offset-value for calibration of supply lines [1/32] Ohm  | INT16  | RW  | 0x0000 (0dec)  | 
Index 8090 RTD Settings Ch. 2
Index (hex)  | Name  | Bedeutung  | Datentyp  | Flags  | Default  | 
|---|---|---|---|---|---|
8090:0  | RTD Settings Ch2.  | Maximum subindex  | UINT8  | RO  | 0x1B (27dec)  | 
8090:19  | RTD element  | RTD element 2: PT1000 (-200…850°C)  | BOOLEAN  | RW  | 0x02 (2dec)  | 
8090:1A  | Connection technology  | Permitted values 0: Two-wire connection  | BIT3  | RW  | 0x00 (0dec)  | 
8090:1B  | Wire calibration 1/32 Ohm  | Offset-value for calibration of supply lines [1/32] Ohm  | INT16  | RW  | 0x0000 (0dec)  | 