Configuration data
Index 80n0 TC Settings (for Ch. 1 - 4 (0 ≤ n ≤ 3))
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
80n0:0 | TC Settings Ch (n+1) | Maximum subindex | UINT8 | RO | 0x19 (25dec) |
80n0:01 | Enable user scale | User scaling is enabled. | BOOLEAN | RW | 0x00 (0dec) |
80n0:02 | Presentation | 0: Signed presentation, 0.1°C/digit 1: Absolute value with MSB as sign (signed amount representation), 0.1°C/digit 2: High resolution (0.01°C/digit) | BIT3 | RW | 0x00 (0dec) |
80n0:05 | Siemens bits | The S5 bits are displayed in the three low-order bits | BOOLEAN | RW | 0x00 (0dec) |
80n0:06 | Enable filter | This setting generally activates the basic filters in object 0x80n0:15. These are technically implemented in the ADC and therefore cannot be switched off, even if this object is set to “disabled”. | BOOLEAN | RW | 0x01 (1dec) |
80n0:0A | Enable user calibration | Enable user calibration | BOOLEAN | RW | 0x00 (0dec) |
80n0:0B | Enable vendor calibration | Enable vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
80n0:0C | Coldjunction compensation | 0: intern RTD Ch1 1: no 2: Extern process data 3: intern RTD Ch2 | BIT2 | RW | 0x00 (0dec) |
80n0:11 | User scale offset | User scale offset | INT16 | RW | 0x0000 (0dec) |
8000:12 | User scale gain | Gain of the user scaling. | INT32 | RW | 0x00010000 (65536dec) |
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
80n0:15 | Filter settings | This object determines the digital basic filter settings. | UINT16 | RW | 0x0000 (0dec) | |
0: 50 Hz (default) | 6: 3.75 kHz | |||||
80n0:17 | User calibration offset | User calibration offset | INT16 | RW | 0x0000 (0dec) | |
80n0:18 | User calibration gain | User calibration gain | UINT16 | RW | 0xFFFF (65535dec) | |
80n0:19 | TC element | Thermocouple Implemented temperature range | UINT16 | RW | 0x0000 (0dec) | |
0: Type: K -200°C to 1370°C | ||||||
Index 8040 RTD Settings Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8040:0 | RTD Settings Ch.1 | Max. subindex | UINT8 | RO | 0x1B (27dec) |
8040:19 | RTD Element | Permitted values 2: PT1000 (-200 … 850°C) | UINT16 | RW | 0x0002 (2dec) |
8040:1A | Connection technology | Permitted values 0: Two-wire connection | UINT16 | RW | 0x0000 (0dec) |
8040:1B | Wire calibration 1/32 Ohm | Offset-value for calibration of supply lines [1/32] Ohm | UINT16 | RW | 0x0000 (0dec) |
Index 8050 RTD Settings Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8050:0 | RTD Settings Ch.1 | Max. subindex | UINT8 | RO | 0x1B (27dec) |
8050:19 | RTD Element | Permitted values 2: PT1000 (-200 … 850°C) | UINT16 | RW | 0x0002 (2dec) |
8050:1A | Connection technology | Permitted values 0: Two-wire connection | UINT16 | RW | 0x0000 (0dec) |
8050:1B | Wire calibration 1/32 Ohm | Calibration of supply lines | UINT16 | RW | 0x0000 (0dec) |
Index 8060 TSC Settings
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8060:0 | TSC Settings | Max. subindex | UINT8 | RO | 0x02 (2dec) | |
8060:19 | Address | TwinSAFE SC address | UINT16 | RW | 0x0001 (1dec) | |
8060:1A | Connection Mode | Selection of TwinSAFE SC CRC Permitted values | UINT32 | RW | 0x00017B0F (97039dec) | |
97039 | TwinSAFE SC CRC1 master | |||||
153375 | TwinSAFE SC CRC2 master | |||||
204693 | TwinSAFE SC CRC3 master | |||||
283633 | TwinSAFE SC CRC4 master | |||||
389589 | TwinSAFE SC CRC5 master | |||||
419387 | TwinSAFE SC CRC6 master | |||||
506061 | TwinSAFE SC CRC7 master | |||||
582077 | TwinSAFE SC CRC8 master | |||||