Configuration data

Index 80n0 TC Settings  (for Ch. 1 - 4 (0 ≤ n ≤  3))

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

TC Settings Ch (n+1)

Maximum subindex

UINT8

RO

0x19 (25dec)

80n0:01

Enable user scale

User scaling is enabled.

BOOLEAN

RW

0x00 (0dec)

80n0:02

Presentation

0: Signed presentation, 0.1°C/digit

1: Absolute value with MSB as sign (signed amount representation), 0.1°C/digit

2: High resolution (0.01°C/digit)

BIT3

RW

0x00 (0dec)

80n0:05

Siemens bits

The S5 bits are displayed in the three low-order bits

BOOLEAN

RW

0x00 (0dec)

80n0:06

Enable filter

This setting generally activates the basic filters in object 0x80n0:15. These are technically implemented in the ADC and therefore cannot be switched off, even if this object is set to “disabled”.

BOOLEAN

RW

0x01 (1dec)

80n0:0A

Enable user calibration

Enable user calibration

BOOLEAN

RW

0x00 (0dec)

80n0:0B

Enable vendor calibration

Enable vendor calibration

BOOLEAN

RW

0x01 (1dec)

80n0:0C

Coldjunction compensation

0: intern RTD Ch1

1: no
Cold junction compensation is not active

2: Extern process data
Cold junction compensation takes place via the process data (resolution [1/10]°C)

3: intern RTD Ch2

BIT2

RW

0x00 (0dec)

80n0:11

User scale offset

User scale offset

INT16

RW

0x0000 (0dec)

8000:12

User scale gain

Gain of the user scaling.
The gain has a fixed-point representation with a factor of 2-16.
The value 1 corresponds to 65536 (0x00010000)

INT32

RW

0x00010000 (65536dec)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:15

Filter settings

This object determines the digital basic filter settings.
The possible settings are numbered consecutively.

UINT16

RW

0x0000 (0dec)

0: 50 Hz (default)
1: 60 Hz
2: 100 Hz
3: 500 Hz
4: 1 kHz
5: 2 kHz

6: 3.75 kHz
7: 7.5 kHz
8: 15 kHz
9: 30 kHz
10: 5 Hz
11:10 Hz

80n0:17

User calibration offset

User calibration offset

INT16

RW

0x0000 (0dec)

80n0:18

User calibration gain

User calibration gain

UINT16

RW

0xFFFF (65535dec)

80n0:19

TC element

Thermocouple

Implemented temperature range

UINT16

RW

0x0000 (0dec)

0: Type: K -200°C to 1370°C
1: Type: J -100°C to 1200°C
2: Type: L  0°C to 900°C
3: Type: E -100°C to 1000°C
4: Type: T -200°C to 400°C
5: Type: N -100°C to 1300°C
6: Type: U 0°C to 600°C
7: Type: B 200…1820
8: Type: R -50…1767
9: Type: S -50…1760
10: Type: C 0°C to 2320°C

100:  ±30 mV (1 µV resolution)
101:  ±60 mV (2 µV resolution)
102:  ±75 mV (4 µV resolution)

Index 8040 RTD Settings Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8040:0

RTD Settings Ch.1

Max. subindex

UINT8

RO

0x1B (27dec)

8040:19

RTD Element

Permitted values

2: PT1000 (-200 … 850°C)
8: Resistor 1/16 Ohm resolution (0…4095 Ohm)

UINT16

RW

0x0002 (2dec)

8040:1A

Connection technology

Permitted values

0: Two-wire connection
3: not connected

UINT16

RW

0x0000 (0dec)

8040:1B

Wire calibration 1/32 Ohm

Offset-value for calibration of supply lines [1/32] Ohm

UINT16

RW

0x0000 (0dec)

Index 8050 RTD Settings Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

8050:0

RTD Settings Ch.1

Max. subindex

UINT8

RO

0x1B (27dec)

8050:19

RTD Element

Permitted values

2: PT1000 (-200 … 850°C)
8: Resistor 1/16 Ohm resolution (0…4095 Ohm)

UINT16

RW

0x0002 (2dec)

8050:1A

Connection technology

Permitted values

0: Two-wire connection
3: not connected

UINT16

RW

0x0000 (0dec)

8050:1B

Wire calibration 1/32 Ohm

Calibration of supply lines

UINT16

RW

0x0000 (0dec)

Index 8060 TSC Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8060:0

TSC Settings

Max. subindex

UINT8

RO

0x02 (2dec)

8060:19

Address

TwinSAFE SC address

UINT16

RW

0x0001 (1dec)

8060:1A

Connection Mode

Selection of TwinSAFE SC CRC

Permitted values

UINT32

RW

0x00017B0F (97039dec)

97039

TwinSAFE SC CRC1 master

153375

TwinSAFE SC CRC2 master

204693

TwinSAFE SC CRC3 master

283633

TwinSAFE SC CRC4 master

389589

TwinSAFE SC CRC5 master

419387

TwinSAFE SC CRC6 master

506061

TwinSAFE SC CRC7 master

582077

TwinSAFE SC CRC8 master