Standard objects (0x1000-0x1FFF)

The standard objects have the same meaning for all EtherCAT slaves.

Index 1000 Device type

Index (hex)

Name

Meaning

Data type

Flags

Default

1000:0

Device type

Device type of the EtherCAT slave: the Lo-Word contains the used CoE profile (5001). The Hi-Word contains the module profile according to the modular device profile.

UINT32

RO

0x00FA1389 (16389001dec)

Index 1008 Device name

Index (hex)

Name

Meaning

Data type

Flags

Default

1008:0

Device name

Device name of the EtherCAT slave

STRING

RO

EJ2564

Index 1009 Hardware version

Index (hex)

Name

Meaning

Data type

Flags

Default

1009:0

Hardware version

Hardware version of the EtherCAT slave

STRING

RO

00

Index 100A Software version

Index (hex)

Name

Meaning

Data type

Flags

Default

100A:0

Software version

Firmware version of the EtherCAT slave

STRING

RO

01

Index 100B Bootloader version

Index (hex)

Name

Meaning

Data type

Flags

Default

100B:0

Bootloader version

Bootloader version

STRING

RO

 

Index 1018 Identity

Index (hex)

Name

Meaning

Data type

Flags

Default

1018:0

Identity

Information for identifying the slave

UINT8

RO

0x04 (4dec)

1018:01

Vendor ID

Vendor ID of the EtherCAT slave

UINT32

RO

0x00000002 (2dec)

1018:02

Product code

Product code of the EtherCAT slave

UINT32

RO

0x0E6C3052 (241971282dec)

1018:03

Revision

Revision number of the EtherCAT slave; the Low Word (bit 0-15) indicates the special terminal number, the High Word (bit 16-31) refers to the device description

UINT32

RO

0x00000000 (0dec)

1018:04

Serial number

Serial number of the EtherCAT slave; the Low Byte (bit 0-7) of the Low Word contains the year of production, the High Byte (bit 8-15) of the Low Word contains the week of production, the High Word (bit 16-31) is 0

UINT32

RO

0x00000000 (0dec)

Index 10F0 Backup parameter handling

Index (hex)

Name

Meaning

Data type

Flags

Default

10F0:0

Backup parameter handling

Information for standardized loading and saving of backup entries

UINT8

RO

0x01 (1dec)

10F0:01

Checksum

Checksum across all backup entries of the EtherCAT slave

UINT32

RO

0x00000000 (0dec)

Index 10F3 Diagnosis History

Index (hex)

Name

Meaning

Data type

Flags

Default

10F3:0

Diagnosis History

Max. Subindex

UINT8

RO

0x15 (21dec)

10F3:01

Maximum Messages

Maximum number of stored messages.
A maximum of 16 messages can be stored

UINT32

RO

0x00000000 0dec)

10F3:02

Newest Message

Subindex of the latest message

UINT8

RO

0x00 0dec)

10F3:03

Newest Acknowledged Message

Subindex of the last confirmed message

UINT8

RO

0x00 (0dec)

10F3:04

New Message available

Indicates that a new message is available

BOOLEAN

RO

0x00 (0dec)

10F3:05

Flags

not used

UINT16

RO

0x0000 (0dec)

10F3:06

Diagnosis Message 001

Message 1

OCTET-STRING[20]

RO

{0}

…

…

…

…

…

…

10F3:015

Diagnosis Message 016

Message 16

OCTET-STRING[20]

RO

{0}

Index 1600 PWM RxPDO-Map Outputs Ch. 1

Index (hex)

Name

Meaning

Data type

Flags

Default

1600:0

PWM RxPDO-Map Outputs Ch. 1

PDO Mapping RxPDO 1

UINT8

RO

0x02 (2dec)

1600:01

SubIndex 001

1. PDO Mapping entry (16 bits align)

UINT32

RO

0x0000:00, 16

1600:02

SubIndex 002

2. PDO Mapping entry (object 0x7000 (PWM Outputs Ch.1), entry 0x11 (PWM output))

UINT32

RO

0x7000:11, 16

Index 1601 PWM RxPDO-Map Outputs Ch. 2

Index (hex)

Name

Meaning

Data type

Flags

Default

1601:0

PWM RxPDO-Map Outputs Ch. 2

PDO Mapping RxPDO 2

UINT8

RO

0x02 (2dec)

1601:01

SubIndex 001

1. PDO Mapping entry (16 bits align)

UINT32

RO

0x0000:00, 16

1601:02

SubIndex 002

2. PDO Mapping entry (object 0x7010 (PWM Outputs Ch.2), entry 0x11 (PWM output))

UINT32

RO

0x7010:11, 16

Index 1602 PWM RxPDO-Map Outputs Ch. 3

Index (hex)

Name

Meaning

Data type

Flags

Default

1602:0

PWM RxPDO-Map Outputs Ch. 3

PDO Mapping RxPDO 3

UINT8

RO

0x02 (2dec)

1602:01

SubIndex 001

1. PDO Mapping entry (16 bits align)

UINT32

RO

0x0000:00, 16

1602:02

SubIndex 002

2. PDO Mapping entry (object 0x7020 (PWM Outputs Ch.3), entry 0x11 (PWM output))

UINT32

RO

0x7020:11, 16

Index 1603 PWM RxPDO-Map Outputs Ch. 4

Index (hex)

Name

Meaning

Data type

Flags

Default

1603:0

PWM RxPDO-Map Outputs Ch. 4

PDO Mapping RxPDO 4

UINT8

RO

0x02 (2dec)

1603:01

SubIndex 001

1. PDO Mapping entry (16 bits align)

UINT32

RO

0x0000:00, 16

1603:02

SubIndex 002

2. PDO Mapping entry (object 0x7030 (PWM Outputs Ch.4), entry 0x11 (PWM output))

UINT32

RO

0x7030:11, 16

Index 1604 PWM RxPDO-Map Outputs Device

Index (hex)

Name

Meaning

Data type

Flags

Default

1604:0

PWM RxPDO-Map Outputs Device

PDO Mapping RxPDO 5

UINT8

RO

0x02 (2dec)

1604:01

SubIndex 001

1. PDO Mapping entry (16 bits align)

UINT32

RO

0x0000:00, 16

1604:02

SubIndex 002

2. PDO Mapping entry (object 0xF719 (PWM Outputs), entry 0x11 (Master gain))

UINT32

RO

0xF719:11, 16

Index 1800 PWM TxPDO-Par Inputs Ch. 1

Index (hex)

Name

Meaning

Data type

Flags

Default

1800:0

PWM TxPDO-Par Inputs Ch. 1

PWM TxPDO-Par Inputs Ch. 1

UINT8

RO

0x06 (6dec)

1800:06

Exclude TxPDOs

Exclude TxPDOs

UINT16

RO

0x1A01 (6657dec)

Index 1801 PWM TxPDO-Par Ext. Inputs Ch. 1

Index (hex)

Name

Meaning

Data type

Flags

Default

1801:0

PWM TxPDO-Par Ext. Inputs Ch. 1

PWM TxPDO-Par Ext. Inputs Ch. 1

UINT8

RO

0x06 (6dec)

1801:06

Exclude TxPDOs

Exclude TxPDOs

UINT16

RO

0x1A00 (6656dec)

Index 1802 PWM TxPDO-Par Inputs Ch. 2

Index (hex)

Name

Meaning

Data type

Flags

Default

1802:0

PWM TxPDO-Par Inputs Ch. 2

PWM TxPDO-Par Inputs Ch. 2

UINT8

RO

0x06 (6dec)

1802:06

Exclude TxPDOs

Exclude TxPDOs

UINT16

RO

0x1A03 (6659dec)

Index 1803 PWM TxPDO-Par Ext. Inputs Ch. 2

Index (hex)

Name

Meaning

Data type

Flags

Default

1803:0

PWM TxPDO-Par Ext. Inputs Ch. 2

PWM TxPDO-Par Ext. Inputs Ch. 2

UINT8

RO

0x06 (6dec)

1803:06

Exclude TxPDOs

Exclude TxPDOs

UINT16

RO

0x1A02 (6658dec)

Index 1804 PWM TxPDO-Par Inputs Ch. 3

Index (hex)

Name

Meaning

Data type

Flags

Default

1804:0

PWM TxPDO-Par Inputs Ch. 3

PWM TxPDO-Par Inputs Ch. 3

UINT8

RO

0x06 (6dec)

1804:06

Exclude TxPDOs

Exclude TxPDOs

UINT16

RO

0x1A05 (6661dec)

Index 1805 PWM TxPDO-Par Ext. Inputs Ch. 3

Index (hex)

Name

Meaning

Data type

Flags

Default

1805:0

PWM TxPDO-Par Ext. Inputs Ch. 3

PWM TxPDO-Par Ext. Inputs Ch. 3

UINT8

RO

0x06 (6dec)

1805:06

Exclude TxPDOs

Exclude TxPDOs

UINT16

RO

0x1A04 (6660dec)

Index 1806 PWM TxPDO-Par Inputs Ch. 4

Index (hex)

Name

Meaning

Data type

Flags

Default

1806:0

PWM TxPDO-Par Inputs Ch. 4

PWM TxPDO-Par Inputs Ch. 4

UINT8

RO

0x06 (6dec)

1806:06

Exclude TxPDOs

Exclude TxPDOs

UINT16

RO

0x1A07 (6663dec)

Index 1807 PWM TxPDO-Par Ext. Inputs Ch. 4

Index (hex)

Name

Meaning

Data type

Flags

Default

1807:0

PWM TxPDO-Par Ext. Inputs Ch. 4

PWM TxPDO-Par Ext. Inputs Ch. 4

UINT8

RO

0x06 (6dec)

1807:06

Exclude TxPDOs

Exclude TxPDOs

UINT16

RO

0x1A06 (6662dec)

Index 1A00 PWM TxPDO-Map Inputs Ch. 1

Index (hex)

Name

Meaning

Data type

Flags

Default

1A00:0

PWM TxPDO-Map Inputs Ch. 1

PDO Mapping TxPDO 1

UINT8

RO

0x05 (5dec)

1A00:01

SubIndex 001

1. PDO Mapping entry (5 bits align)

UINT32

RO

0x0000:00, 5

1A00:02

SubIndex 002

2. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.1), entry 0x06 (Warning))

UINT32

RO

0x6000:06, 1

1A00:03

SubIndex 003

3. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.1), entry 0x07 (Error))

UINT32

RO

0x6000:07, 1

1A00:04

SubIndex 004

4. PDO Mapping entry (8 bits align)

UINT32

RO

0x0000:00, 8

1A00:05

SubIndex 005

5. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.1), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x6000:10, 1

Index 1A01 PWM TxPDO-Map Ext. Inputs Ch. 1

Index (hex)

Name

Meaning

Data type

Flags

Default

1A01:0

PWM TxPDO-Map Ext. Inputs Ch. 1

PDO Mapping TxPDO 1

UINT8

RO

0x07 (7dec)

1A01:01

SubIndex 001

1. PDO Mapping entry (5 bits align)

UINT32

RO

0x0000:00, 5

1A01:02

SubIndex 002

2. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.1), entry 0x06 (Warning))

UINT32

RO

0x6000:06, 1

1A01:03

SubIndex 003

3. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.1), entry 0x07 (Error))

UINT32

RO

0x6000:07, 1

1A01:04

SubIndex 004

4. PDO Mapping entry (8 bits align)

UINT32

RO

0x0000:00, 8

1A01:05

SubIndex 005

5. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.1), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x6000:10, 1

1A01:06

SubIndex 006

6. PDO Mapping entry (32 bits align)

UINT32

RO

0x0000:00, 32

1A01:07

SubIndex 007

7. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.1), entry 0x13 (Output duty cycle))

UINT32

RO

0x6000:13, 16

Index 1A02 PWM TxPDO-Map Inputs Ch. 2

Index (hex)

Name

Meaning

Data type

Flags

Default

1A02:0

PWM TxPDO-Map Inputs Ch. 2

PDO Mapping TxPDO 2

UINT8

RO

0x05 (5dec)

1A02:01

SubIndex 001

1. PDO Mapping entry (5 bits align)

UINT32

RO

0x0000:00, 5

1A02:02

SubIndex 002

2. PDO Mapping entry (object 0x6010 (PWM Inputs Ch.2), entry 0x06 (Warning))

UINT32

RO

0x6010:06, 1

1A02:03

SubIndex 003

3. PDO Mapping entry (object 0x6010 (PWM Inputs Ch.2), entry 0x07 (Error))

UINT32

RO

0x6010:07, 1

1A02:04

SubIndex 004

4. PDO Mapping entry (8 bits align)

UINT32

RO

0x0000:00, 8

1A02:05

SubIndex 005

5. PDO Mapping entry (object 0x6010 (PWM Inputs Ch.2), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x6010:10, 1

Index 1A03 PWM TxPDO-Map Ext. Inputs Ch. 2

Index (hex)

Name

Meaning

Data type

Flags

Default

1A03:0

PWM TxPDO-Map Ext. Inputs Ch. 2

PDO Mapping TxPDO 1

UINT8

RO

0x07 (7dec)

1A03:01

SubIndex 001

1. PDO Mapping entry (5 bits align)

UINT32

RO

0x0000:00, 5

1A03:02

SubIndex 002

2. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.2), entry 0x06 (Warning))

UINT32

RO

0x6010:06, 1

1A03:03

SubIndex 003

3. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.2), entry 0x07 (Error))

UINT32

RO

0x6010:07, 1

1A03:04

SubIndex 004

4. PDO Mapping entry (8 bits align)

UINT32

RO

0x0000:00, 8

1A03:05

SubIndex 005

5. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.2), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x6010:10, 1

1A03:06

SubIndex 006

6. PDO Mapping entry (32 bits align)

UINT32

RO

0x0000:00, 32

1A03:07

SubIndex 007

7. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.2), entry 0x13 (Output duty cycle))

UINT32

RO

0x6010:13, 16

Index 1A04 PWM TxPDO-Map Inputs Ch. 3

Index (hex)

Name

Meaning

Data type

Flags

Default

1A04:0

PWM TxPDO-Map Inputs Ch. 3

PDO Mapping TxPDO 3

UINT8

RO

0x05 (5dec)

1A04:01

SubIndex 001

1. PDO Mapping entry (5 bits align)

UINT32

RO

0x0000:00, 5

1A04:02

SubIndex 002

2. PDO Mapping entry (object 0x6020 (PWM Inputs Ch.3), entry 0x06 (Warning))

UINT32

RO

0x6020:06, 1

1A04:03

SubIndex 003

3. PDO Mapping entry (object 0x6020 (PWM Inputs Ch.3), entry 0x07 (Error))

UINT32

RO

0x6020:07, 1

1A04:04

SubIndex 004

4. PDO Mapping entry (8 bits align)

UINT32

RO

0x0000:00, 8

1A04:05

SubIndex 005

5. PDO Mapping entry (object 0x6020 (PWM Inputs Ch.3), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x6020:10, 1

Index 1A05 PWM TxPDO-Map Ext. Inputs Ch. 3

Index (hex)

Name

Meaning

Data type

Flags

Default

1A05:0

PWM TxPDO-Map Ext. Inputs Ch. 3

PDO Mapping TxPDO 1

UINT8

RO

0x07 (7dec)

1A05:01

SubIndex 001

1. PDO Mapping entry (5 bits align)

UINT32

RO

0x0000:00, 5

1A05:02

SubIndex 002

2. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.3), entry 0x06 (Warning))

UINT32

RO

0x6020:06, 1

1A05:03

SubIndex 003

3. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.3), entry 0x07 (Error))

UINT32

RO

0x6020:07, 1

1A05:04

SubIndex 004

4. PDO Mapping entry (8 bits align)

UINT32

RO

0x0000:00, 8

1A05:05

SubIndex 005

5. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.3), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x6020:10, 1

1A05:06

SubIndex 006

6. PDO Mapping entry (32 bits align)

UINT32

RO

0x0000:00, 32

1A05:07

SubIndex 007

7. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.3), entry 0x13 (Output duty cycle))

UINT32

RO

0x6020:13, 16

Index 1A06 PWM TxPDO-Map Inputs Ch. 4

Index (hex)

Name

Meaning

Data type

Flags

Default

1A06:0

PWM TxPDO-Map Inputs Ch. 4

PDO Mapping TxPDO 4

UINT8

RO

0x05 (5dec)

1A06:01

SubIndex 001

1. PDO Mapping entry (5 bits align)

UINT32

RO

0x0000:00, 5

1A06:02

SubIndex 002

2. PDO Mapping entry (object 0x6030 (PWM Inputs Ch.4), entry 0x06 (Warning))

UINT32

RO

0x6030:06, 1

1A06:03

SubIndex 003

3. PDO Mapping entry (object 0x6030 (PWM Inputs Ch.4), entry 0x07 (Error))

UINT32

RO

0x6030:07, 1

1A06:04

SubIndex 004

4. PDO Mapping entry (8 bits align)

UINT32

RO

0x0000:00, 8

1A06:05

SubIndex 005

5. PDO Mapping entry (object 0x6030 (PWM Inputs Ch.4), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x6030:10, 1

Index 1A07 PWM TxPDO-Map Ext. Inputs Ch. 4

Index (hex)

Name

Meaning

Data type

Flags

Default

1A07:0

PWM TxPDO-Map Ext. Inputs Ch. 4

PDO Mapping TxPDO 1

UINT8

RO

0x07 (7dec)

1A07:01

SubIndex 001

1. PDO Mapping entry (5 bits align)

UINT32

RO

0x0000:00, 5

1A07:02

SubIndex 002

2. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.4), entry 0x06 (Warning))

UINT32

RO

0x6030:06, 1

1A07:03

SubIndex 003

3. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.4), entry 0x07 (Error))

UINT32

RO

0x6030:07, 1

1A07:04

SubIndex 004

4. PDO Mapping entry (8 bits align)

UINT32

RO

0x0000:00, 8

1A07:05

SubIndex 005

5. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.4), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x6030:10, 1

1A07:06

SubIndex 006

6. PDO Mapping entry (32 bits align)

UINT32

RO

0x0000:00, 32

1A07:07

SubIndex 007

7. PDO Mapping entry (object 0x6000 (PWM Inputs Ch.4), entry 0x13 (Output duty cycle))

UINT32

RO

0x6030:13, 16

Index 1C00 Sync manager type

Index (hex)

Name

Meaning

Data type

Flags

Default

1C00:0

Sync manager type

Using the Sync Managers

UINT8

RO

0x04 (4dec)

1C00:01

SubIndex 001

Sync-Manager Type Channel 1: Mailbox Write

UINT8

RO

0x01 (1dec)

1C00:02

SubIndex 002

Sync-Manager Type Channel 2: Mailbox Read

UINT8

RO

0x02 (2dec)

1C00:03

SubIndex 003

Sync-Manager Type Channel 3: Process Data Write (Outputs)

UINT8

RO

0x03 (3dec)

1C00:04

SubIndex 004

Sync-Manager Type Channel 4: Process Data Read (Inputs)

UINT8

RO

0x04 (4dec)

Index 1C12 RxPDO assign

Index (hex)

Name

Meaning

Data type

Flags

Default

1C12:0

RxPDO assign

PDO Assign Outputs

UINT8

RW

0x05 (5dec)

1C12:01

Subindex 001

1. allocated RxPDO (contains the index of the associated RxPDO mapping object)

UINT16

RW

0x1600 (5632dec)

1C12:02

Subindex 002

2. allocated RxPDO (contains the index of the associated RxPDO mapping object)

UINT16

RW

0x1601 (5633dec)

1C12:03

Subindex 003

3. allocated RxPDO (contains the index of the associated RxPDO mapping object)

UINT16

RW

0x1602 (5634dec)

1C12:04

Subindex 004

4. allocated RxPDO (contains the index of the associated RxPDO mapping object)

UINT16

RW

0x1603 (5635dec)

1C12:05

Subindex 005

5. allocated RxPDO (contains the index of the associated RxPDO mapping object)

UINT16

RW

0x1604 (5636dec)

Index 1C13 TxPDO assign

Index (hex)

Name

Meaning

Data type

Flags

Default

1C13:0

TxPDO assign

PDO Assign Inputs

UINT8

RW

0x04 (4dec)

1C13:01

Subindex 001

1. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A00 (6656dec)

1C13:02

Subindex 002

2. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A02 (6658dec)

1C13:03

Subindex 003

3. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A04 (6600dec)

1C13:04

Subindex 004

4. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A06 (6662dec)

Index 1C32 SM output parameter

Index (hex)

Name

Meaning

Data type

Flags

Default

1C32:0

SM output parameter

Synchronization parameters for the outputs

UINT8

RO

0x20 (32dec)

1C32:01

Sync mode

Current synchronization mode:

  • 0: Free Run
  • 1: Synchron with SM 2 Event
  • 2: DC-Mode - Synchron with SYNC0 Event
  • 3: DC-Mode - Synchron with SYNC1 Event

UINT16

RW

0x0001 (1dec)

1C32:02

Cycle time

Cycle time (in ns):

  • Free Run: cycle time of the local timer
  • Synchronous with SM 2 Event: cycle time of the master
  • DC-Mode: SYNC0/SYNC1 Cycle Time

UINT32

RW

0x000F4240 (1000000dec)

1C32:03

Shift time

Time between SYNC0 event and output of the outputs (in ns, DC mode only)

UINT32

RO

0x00000000 (0dec)

1C32:04

Sync modes supported

Supported synchronization modes:

  • Bit 0 = 1: Free Run is supported
  • Bit 1 = 1: Synchron with SM 2 Event is supported
  • Bit 2-3 = 01: DC-Mode is supported
  • Bit 4-5 = 10: Output Shift with SYNC1 event (only DC mode)
  • Bit 14 = 1: dynamic times (measurement through writing of 1C32:08)

UINT16

RO

0x0003 (3dec)

1C32:05

Minimum cycle time

Minimum cycle time (in ns)

UINT32

RO

0x000186A0 (100000dec)

1C32:06

Calc and copy time

Minimum time between SYNC0 and SYNC1 event (in ns, DC mode only)

UINT32

RO

0x00000000 (0dec)

1C32:07

Minimum delay time

Minimum time between SYNC1 event and output of the outputs (in ns)

0, since EJ2564 does not support DC mode

UINT32

RO

0x00000000 (0dec)

1C32:08

Get Cycle Time

  • 0: Measurement of the local cycle time is stopped
  • 1: Measurement of the local cycle time is started

The entries 0x1C32:03, 0x1C32:05, 0x1C32:06, 0x1C32:09, 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values.
For a subsequent measurement the measured values are reset

UINT16

RW

0x0000 (0dec)

1C32:09

Maximum delay time

Time between SYNC1 event and output of the outputs (in ns, DC mode only)

UINT32

RO

0x00000000 (0dec)

1C32:0B

SM event missed counter

Number of missed SM events in OPERATIONAL (DC mode only)

UINT16

RO

0x0000 (0dec)

1C32:0C

Cycle exceeded counter

Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early)

UINT16

RO

0x0000 (0dec)

1C32:0D

Shift too short counter

Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only)

UINT16

RO

0x0000 (0dec)

1C32:20

Sync error

The synchronization was not correct in the last cycle (outputs were output too late; DC mode only)

BOOLEAN

RO

0x00 (0dec)

Index 1C33 SM input parameter

Index (hex)

Name

Meaning

Data type

Flags

Default

1C33:0

SM input parameter

Synchronization parameters for the inputs

UINT8

RO

0x20 (32dec)

1C33:01

Sync mode

Current synchronization mode:

  • 0: Free Run
  • 1: Synchron with SM 3 event (no outputs available)
  • 2: DC - Synchron with SYNC0 Event
  • 3: DC - Synchron with SYNC1 Event
  • 34: Synchron with SM 2 event (outputs available)

UINT16

RW

0x0022 (34dec)

1C33:02

Cycle time

Cycle time (in ns):

  • Free Run: cycle time of the local timer
  • Synchronous with SM 2 Event: cycle time of the master

DC-Mode: SYNC0/SYNC1 Cycle Time

UINT32

RW

0x000F4240 (1000000dec)

1C33:03

Shift time

Time between SYNC0 event and reading of the inputs (in ns, DC mode only)

UINT32

RO

0x00000000 (0dec)

1C33:04

Sync modes supported

Supported synchronization modes:

  • Bit 0: Free Run is supported
  • Bit 1: Synchron with SM 2 Event is supported (outputs available)
  • Bit 1: Synchron with SM 3 Event is supported (no outputs available)
  • Bit 2-3 = 01: DC-Mode is supported
  • Bit 4-5 = 01: Input Shift through local event (outputs available)
  • Bit 4-5 = 10: Input Shift with SYNC1 event (no outputs available)
  • Bit 14 = 1: dynamic times (measurement through writing of 0x1C32:08 or 0x1C33:08)

UINT16

RO

0x0003 (3dec)

1C33:05

Minimum cycle time

Minimum cycle time (in ns)

UINT32

RO

0x000186A0 (100000dec)

1C33:06

Calc and copy time

Time between reading of the inputs and availability of the inputs for the master (in ns, only DC mode)

UINT32

RO

0x00000000 (0dec)

1C33:07

Minimum delay time

Min. time between SYNC1 event and the reading of the inputs (in ns, DC mode only)

0, since EJ2564 does not support DC mode

UINT32

RO

0x00000000 (0dec)

1C33:08

Command

  • 0: Measurement of the local cycle time is stopped
  • 1: Measurement of the local cycle time is started

The entries 0x1C32:03, 0x1C32:05 0x1C32:06, 0x1C32:09 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values.
For a subsequent measurement the measured values are reset

UINT16

RW

0x0000 (0dec)

1C33:09

Maximum delay time

Time between SYNC1 event and reading of the inputs (in ns, only DC mode)

UINT32

RO

0x00000000 (0dec)

1C33:0B

SM event missed counter

Number of missed SM events in OPERATIONAL (DC mode only)

UINT16

RO

0x0000 (0dec)

1C33:0C

Cycle exceeded counter

Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early)

UINT16

RO

0x0000 (0dec)

1C33:0D

Shift too short counter

Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only)

UINT16

RO

0x0000 (0dec)

1C33:20

Sync error

The synchronization was not correct in the last cycle (outputs were output too late; DC mode only)

BOOLEAN

RO

0x00 (0dec)