LEDs

LEDs 1:Fig.12: EJ1859 - LEDs

LED

Color

Display

State

Description

RUN

green

off

Init

State of the EtherCAT State Machine: INIT = initialization of the plug-in module

flashing

Pre-
Operational

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set

Single flash

Safe-
Operational

State of the EtherCAT State Machine: SAFEOP = verification of the Sync-Manager channels and the distributed clocks.
Outputs remain in safe state

on

Operational

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication are possible

flickering

Bootstrap

State of the EtherCAT State Machine: BOOTSTRAP = function for firmware updates of the plug-in module

Up

green

off

-

No 24 VDC power supply connected

on

-

24 VDC power supply connected

I1 ... I8

green

off

-

Signal voltage "0" (-3 V ... 5 V)

on

-

Signal voltage "1" (11 V ... 30 V)

O1 ... O8

green

off

-

no output voltage

 

on

-

+24 VDC output voltage