Standard objects
Index 1000 Device type
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1000:0 | Device type | Device type of the EtherCAT slave: The low word contains the CoE profile used (5001). The high word contains the module profile according to the modular device profile. | UINT32 | RO | 0x00001389 (5001dec)) |
Index 1008 Device name
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1008:0 | Device name | Device name of the EtherCAT slave | STRING | RO | ED7062-0000 |
Index 1009 Hardware version
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1009:0 | Hardware version | Hardware version des EtherCAT slaves | STRING | RO |
|
Index 100A Software version
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
100A:0 | Software version | Firmware version of the EtherCAT slave | STRING | RO | 01 |
Index 100B Bootloader version
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
100B:0 | Bootloader version |
| STRING | RO | n/a |
Index 1011 Restore default parameters
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1011:0 | Restore default parameters | Restore default settings | UINT8 | RO | 0x01 (1dec)) |
1011:01 | SubIndex 001 | If this object is set to “0x64616F6C” in the set value dialog, all backup objects are reset to their delivery state. | UINT32 | RW | 0x00000000 (0dec)) |
Index 1018 Identity
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1018:0 | Identity | Information for identifying the slave | UINT8 | RO | 0x04 (4dec)) |
1018:01 | Vendor ID | Vendor ID of the EtherCAT slave | UINT32 | RO | 0x00000002 (2dec)) |
1018:02 | Product code | Product code of the EtherCAT slave | UINT32 | RO | 0x1B961052 (462819410dec)) |
1018:03 | Revision | Revision number of the EtherCAT slave; the low word (bit 0–15) indicates the special terminal number, the high word (bit 16–31) refers to the device description | UINT32 | RO | 0x00000000 (0dec)) |
1018:04 | Serial number | Serial number of the EtherCAT slave; the low byte (bit 0–7) of the low word contains the year of production, the high byte (bit 8–15) of the low word contains the week of production, the high word (bit 16–31) is 0 | UINT32 | RO | 0x00000000 (0dec)) |
Index 10E2 Manufacturer-specific Identification Code
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
10E2:0 | Manufacturer-specific Identification Code |
| UINT8 | RO | 0x01 (1dec)) |
10E2:01 | SubIndex 001 |
| STRING | RO |
|
Index 10F0 Backup parameter handling
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
10F0:01 | Checksum | Checksum across all backup entries of the EtherCAT slave | UINT32 | RO | 0x00000000 (0dec)) |
Index 10F3 Diagnosis History
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
10F3:0 | Diagnosis History |
| UINT8 | RO | 0x37 (55dec)) |
10F3:01 | Maximum Messages |
| UINT8 | RO | 0x00 (0dec)) |
10F3:02 | Newest Message |
| UINT8 | RO | 0x00 (0dec)) |
10F3:03 | Newest Acknowledged Message |
| UINT8 | RW | 0x00 (0dec)) |
10F3:04 | New Messages Available |
| BOOLEAN | RO | 0x00 (0dec)) |
10F3:05 | Flags |
| UINT16 | RW | 0x0000 (0dec)) |
10F3:06 | Diagnosis Message 001 |
| OCTET-STRING[32] | RO | {0} |
10F3:07 | Diagnosis Message 002 |
| OCTET-STRING[32] | RO | {0} |
10F3:08 | Diagnosis Message 003 |
| OCTET-STRING[32] | RO | {0} |
… | … | … | … | … | … |
10F3:35 | Diagnosis Message 048 |
| OCTET-STRING[32] | RO | {0} |
10F3:36 | Diagnosis Message 049 |
| OCTET-STRING[32] | RO | {0} |
10F3:37 | Diagnosis Message 050 |
| OCTET-STRING[32] | RO | {0} |
Index 10F8 Timestamp Object
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
10F8:0 | Timestamp Object |
| UINT64 | RO |
|
Index 1460 DMC RxPDO-Par Outputs Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1460:0 |
DMC RxPDO-Par Outputs Ch.1 |
PDO Parameter RxPDO 97 |
UINT8 |
RO |
0x06 (6dec) |
|
1460:06 |
Exclude RxPDOs |
Specifies the RxPDOs (index of RxPDO mapping objects) that must not be transferred together with RxPDO 97 |
OCTET-STRING[2] |
RO |
61 16 |
Index 1461 DMC RxPDO-Par Outputs 32 Bit Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1461:0 |
DMC RxPDO-Par Outputs 32 Bit Ch.1 |
PDO Parameter RxPDO 98 |
UINT8 |
RO |
0x06 (6dec) |
|
1461:06 |
Exclude RxPDOs |
Specifies the RxPDOs (index of RxPDO mapping objects) that must not be transferred together with RxPDO 98 |
OCTET-STRING[2] |
RO |
60 16 |
Index 14E0 DMC RxPDO-Par Outputs Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
14E0:0 | DMC RxPDO-Par Outputs Ch.2 | PDO Parameter RxPDO 225 | UINT8 | RO | 0x06 (6dec)) |
14E0:06 | Exclude RxPDOs | Specifies the RxPDOs (index of RxPDO mapping objects) that must not be transferred together with RxPDO 225 | OCTET-STRING[2] | RO | E1 16 |
Index 14E1 DMC RxPDO-Par Outputs 32 Bit Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
14E1:0 | DMC RxPDO-Par Outputs 32 Bit Ch.2 | PDO Parameter RxPDO 226 | UINT8 | RO | 0x06 (6dec)) |
14E1:06 | Exclude RxPDOs | Specifies the RxPDOs (index of RxPDO mapping objects) that must not be transferred together with RxPDO 226 | OCTET-STRING[2] | RO | E0 16 |
Index 1600 DRV RxPDO-Map Controlword Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1600:0 |
DRV RxPDO-Map Controlword Ch.1 |
PDO Mapping RxPDO 1 |
UINT8 |
RO |
0x01 (1dec) |
|
1600:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x01 (Controlword)) |
UINT32 |
RO |
0x7010:01, 16 |
Index 1601 DRV RxPDO-Map Target velocity Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1601:0 |
DRV RxPDO-Map Target velocity Ch.1 |
PDO Mapping RxPDO 2 |
UINT8 |
RO |
0x01 (1dec) |
|
1601:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x06 (Target velocity)) |
UINT32 |
RO |
0x7010:06, 32 |
Index 1602 DRV RxPDO-Map Target torque Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1602:0 |
DRV RxPDO-Map Target torque Ch.1 |
PDO Mapping RxPDO 3 |
UINT8 |
RO |
0x01 (1dec) |
|
1602:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x09 (Target torque)) |
UINT32 |
RO |
0x7010:09, 16 |
Index 1603 DRV RxPDO-Map Commutation angle Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1603:0 |
DRV RxPDO-Map Commutation angle Ch.1 |
PDO Mapping RxPDO 4 |
UINT8 |
RO |
0x01 (1dec) |
|
1603:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x0E (Commutation angle)) |
UINT32 |
RO |
0x7010:0E, 16 |
Index 1604 DRV RxPDO-Map Torque limitation Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1604:0 |
DRV RxPDO-Map Torque limitation Ch.1 |
PDO Mapping RxPDO 5 |
UINT8 |
RO |
0x01 (1dec) |
|
1604:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x0B (Torque limitation)) |
UINT32 |
RO |
0x7010:0B, 16 |
Index 1605 DRV RxPDO-Map Torque offset Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1605:0 |
DRV RxPDO-Map Torque offset Ch.1 |
PDO Mapping RxPDO 6 |
UINT8 |
RO |
0x01 (1dec) |
|
1605:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x0A (Torque offset)) |
UINT32 |
RO |
0x7010:0A, 16 |
Index 1606 DRV RxPDO-Map Target position Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1606:0 |
DRV RxPDO-Map Target position Ch.1 |
PDO Mapping RxPDO 7 |
UINT8 |
RO |
0x01 (1dec) |
|
1606:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x05 (Target position)) |
UINT32 |
RO |
0x7010:05, 32 |
Index 1607 FB RxPDO-Map Touch probe control Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1607:0 |
FB RxPDO-Map Touch probe control Ch.1 |
PDO Mapping RxPDO 8 |
UINT8 |
RO |
0x0C (12dec) |
|
1607:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x01 (TP1 Enable)) |
UINT32 |
RO |
0x7001:01, 1 |
|
1607:02 |
SubIndex 002 |
2nd PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x02 (TP1 Continuous)) |
UINT32 |
RO |
0x7001:02, 1 |
|
1607:03 |
SubIndex 003 |
3rd PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x03 (TP1 Trigger mode)) |
UINT32 |
RO |
0x7001:03, 2 |
|
1607:04 |
SubIndex 004 |
4th PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x05 (TP1 Enable pos edge)) |
UINT32 |
RO |
0x7001:05, 1 |
|
1607:05 |
SubIndex 005 |
5th PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x06 (TP1 Enable neg edge)) |
UINT32 |
RO |
0x7001:06, 1 |
|
1607:06 |
SubIndex 006 |
6th PDO Mapping entry (2 bits align) |
UINT32 |
RO |
0x0000:00, 2 |
|
1607:07 |
SubIndex 007 |
7th PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x09 (TP2 Enable)) |
UINT32 |
RO |
0x7001:09, 1 |
|
1607:08 |
SubIndex 008 |
8th PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x0A (TP2 Continuous)) |
UINT32 |
RO |
0x7001:0A, 1 |
|
1607:09 |
SubIndex 009 |
9th PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x0B (TP2 Trigger mode)) |
UINT32 |
RO |
0x7001:0B, 2 |
|
1607:0A |
SubIndex 010 |
10th PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x0D (TP2 Enable pos edge)) |
UINT32 |
RO |
0x7001:0D, 1 |
|
1607:0B |
SubIndex 011 |
11th PDO Mapping entry (object 0x7001 (FB Touch probe outputs Ch.1), entry 0x0E (TP2 Enable neg edge)) |
UINT32 |
RO |
0x7001:0E, 1 |
|
1607:0C |
SubIndex 012 |
12th PDO Mapping entry (2 bits align) |
UINT32 |
RO |
0x0000:00, 2 |
Index 1608 DRV RxPDO-Map Modes of operation Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1608:0 |
DRV RxPDO-Map Modes of operation Ch.1 |
PDO Mapping RxPDO 9 |
UINT8 |
RO |
0x01 (1dec) |
|
1608:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x03 (Modes of operation)) |
UINT32 |
RO |
0x7010:03, 8 |
Index 1609 DRV RxPDO-Map Velocity offset Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1609:0 |
DRV RxPDO-Map Velocity offset Ch.1 |
PDO Mapping RxPDO 10 |
UINT8 |
RO |
0x01 (1dec) |
|
1609:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x0F (Velocity offset)) |
UINT32 |
RO |
0x7010:0F, 32 |
Index 160A DRV RxPDO-Map Positive torque limit value Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160A:0 |
DRV RxPDO-Map Positive torque limit value Ch.1 |
PDO Mapping RxPDO 11 |
UINT8 |
RO |
0x01 (1dec) |
|
160A:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x10 (Positive torque limit value)) |
UINT32 |
RO |
0x7010:10, 16 |
Index 160B DRV RxPDO-Map Negative torque limit value Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160B:0 |
DRV RxPDO-Map Negative torque limit value Ch.1 |
PDO Mapping RxPDO 12 |
UINT8 |
RO |
0x01 (1dec) |
|
160B:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x11 (Negative torque limit value)) |
UINT32 |
RO |
0x7010:11, 16 |
Index 160C DRV RxPDO-Map Low velocity limit value Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160C:0 |
DRV RxPDO-Map Low velocity limit value Ch.1 |
PDO Mapping RxPDO 13 |
UINT8 |
RO |
0x01 (1dec) |
|
160C:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x12 (Low velocity limit value)) |
UINT32 |
RO |
0x7010:12, 32 |
Index 160D DRV RxPDO-Map High velocity limit value Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160D:0 |
DRV RxPDO-Map High velocity limit value Ch.1 |
PDO Mapping RxPDO 14 |
UINT8 |
RO |
0x01 (1dec) |
|
160D:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x7010 (DRV Outputs Ch.1), entry 0x13 (High velocity limit value)) |
UINT32 |
RO |
0x7010:13, 32 |
Index 1660 DMC RxPDO-Map Outputs Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1660:0 |
DMC RxPDO-Map Outputs Ch.1 |
PDO Mapping RxPDO 97 |
UINT8 |
RO |
0x12 (18dec) |
|
1660:01 |
SubIndex 001 |
1st PDO Mapping entry (1 bit aligns) |
UINT32 |
RO |
0x0000:00, 1 |
|
1660:02 |
SubIndex 002 |
2nd PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x02 (DMC__FeedbackControl__Enable latch extern on positive edge)) |
UINT32 |
RO |
0x7060:02, 1 |
|
1660:03 |
SubIndex 003 |
3rd PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x03 (DMC__FeedbackControl__Set counter)) |
UINT32 |
RO |
0x7060:03, 1 |
|
1660:04 |
SubIndex 004 |
4th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x04 (DMC__FeedbackControl__Enable latch extern on negative edge)) |
UINT32 |
RO |
0x7060:04, 1 |
|
1660:05 |
SubIndex 005 |
5th PDO Mapping entry (12 bits align) |
UINT32 |
RO |
0x0000:00, 12 |
|
1660:06 |
SubIndex 006 |
6th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x11 (DMC__DriveControl__Enable)) |
UINT32 |
RO |
0x7060:11, 1 |
|
1660:07 |
SubIndex 007 |
7th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x12 (DMC__DriveControl__Reset)) |
UINT32 |
RO |
0x7060:12, 1 |
|
1660:08 |
SubIndex 008 |
8th PDO Mapping entry (14 bits align) |
UINT32 |
RO |
0x0000:00, 14 |
|
1660:09 |
SubIndex 009 |
9th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x21 (DMC__PositioningControl__Execute)) |
UINT32 |
RO |
0x7060:21, 1 |
|
1660:0A |
SubIndex 010 |
10th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x22 (DMC__PositioningControl__Emergency stop)) |
UINT32 |
RO |
0x7060:22, 1 |
|
1660:0B |
SubIndex 011 |
11th PDO Mapping entry (14 bits align) |
UINT32 |
RO |
0x0000:00, 14 |
|
1660:0C |
SubIndex 012 |
12th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x31 (DMC__Set counter value)) |
UINT32 |
RO |
0x7060:31, 64 |
|
1660:0D |
SubIndex 013 |
13th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x32 (DMC__Target position)) |
UINT32 |
RO |
0x7060:32, 64 |
|
1660:0E |
SubIndex 014 |
14th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x33 (DMC__Target velocity)) |
UINT32 |
RO |
0x7060:33, 16 |
|
1660:0F |
SubIndex 015 |
15th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x34 (DMC__Start type)) |
UINT32 |
RO |
0x7060:34, 16 |
|
1660:10 |
SubIndex 016 |
16th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x35 (DMC__Target acceleration)) |
UINT32 |
RO |
0x7060:35, 16 |
|
1660:11 |
SubIndex 017 |
17th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x36 (DMC__Target deceleration)) |
UINT32 |
RO |
0x7060:36, 16 |
|
1660:12 |
SubIndex 018 |
18th PDO Mapping entry (80 bits align) |
UINT32 |
RO |
0x0000:00, 80 |
Index 1661 DMC RxPDO-Map Outputs 32 Bit Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1661:0 |
DMC RxPDO-Map Outputs 32 Bit Ch.1 |
PDO Mapping RxPDO 98 |
UINT8 |
RO |
0x14 (20dec) |
|
1661:01 |
SubIndex 001 |
1st PDO Mapping entry (1 bit aligns) |
UINT32 |
RO |
0x0000:00, 1 |
|
1661:02 |
SubIndex 002 |
2nd PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x02 (DMC__FeedbackControl__Enable latch extern on positive edge)) |
UINT32 |
RO |
0x7060:02, 1 |
|
1661:03 |
SubIndex 003 |
3rd PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x03 (DMC__FeedbackControl__Set counter)) |
UINT32 |
RO |
0x7060:03, 1 |
|
1661:04 |
SubIndex 004 |
4th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x04 (DMC__FeedbackControl__Enable latch extern on negative edge)) |
UINT32 |
RO |
0x7060:04, 1 |
|
1661:05 |
SubIndex 005 |
5th PDO Mapping entry (12 bits align) |
UINT32 |
RO |
0x0000:00, 12 |
|
1661:06 |
SubIndex 006 |
6th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x11 (DMC__DriveControl__Enable)) |
UINT32 |
RO |
0x7060:11, 1 |
|
1661:07 |
SubIndex 007 |
7th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x12 (DMC__DriveControl__Reset)) |
UINT32 |
RO |
0x7060:12, 1 |
|
1661:08 |
SubIndex 008 |
8th PDO Mapping entry (14 bits align) |
UINT32 |
RO |
0x0000:00, 14 |
|
1661:09 |
SubIndex 009 |
9th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x21 (DMC__PositioningControl__Execute)) |
UINT32 |
RO |
0x7060:21, 1 |
|
1661:0A |
SubIndex 010 |
10th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x22 (DMC__PositioningControl__Emergency stop)) |
UINT32 |
RO |
0x7060:22, 1 |
|
1661:0B |
SubIndex 011 |
11th PDO Mapping entry (14 bits align) |
UINT32 |
RO |
0x0000:00, 14 |
|
1661:0C |
SubIndex 012 |
12th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x31 (DMC__Set counter value)) |
UINT32 |
RO |
0x7060:31, 32 |
|
1661:0D |
SubIndex 013 |
13th PDO Mapping entry (32 bits align) |
UINT32 |
RO |
0x0000:00, 32 |
|
1661:0E |
SubIndex 014 |
14th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x32 (DMC__Target position)) |
UINT32 |
RO |
0x7060:32, 32 |
|
1661:0F |
SubIndex 015 |
15th PDO Mapping entry (32 bits align) |
UINT32 |
RO |
0x0000:00, 32 |
|
1661:10 |
SubIndex 016 |
16th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x33 (DMC__Target velocity)) |
UINT32 |
RO |
0x7060:33, 16 |
|
1661:11 |
SubIndex 017 |
17th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x34 (DMC__Start type)) |
UINT32 |
RO |
0x7060:34, 16 |
|
1661:12 |
SubIndex 018 |
18th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x35 (DMC__Target acceleration)) |
UINT32 |
RO |
0x7060:35, 16 |
|
1661:13 |
SubIndex 019 |
19th PDO Mapping entry (object 0x7060 (DMC Outputs Ch.1), entry 0x36 (DMC__Target deceleration)) |
UINT32 |
RO |
0x7060:36, 16 |
|
1661:14 |
SubIndex 020 |
20th PDO Mapping entry (80 bits align) |
UINT32 |
RO |
0x0000:00, 80 |
Index 1680 DRV RxPDO-Map Controlword Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1680:0 | DRV RxPDO-Map Controlword Ch.2 | PDO Mapping RxPDO 129 | UINT8 | RO | 0x01 (1dec)) |
1680:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x01 (Controlword)) | UINT32 | RO | 0x7110:01, 16 |
Index 1681 DRV RxPDO-Map Target velocity Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1681:0 | DRV RxPDO-Map Target velocity Ch.2 | PDO Mapping RxPDO 130 | UINT8 | RO | 0x01 (1dec)) |
1681:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x06 (Target velocity)) | UINT32 | RO | 0x7110:06, 32 |
Index 1682 DRV RxPDO-Map Target torque Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1682:0 | DRV RxPDO-Map Target torque Ch.2 | PDO Mapping RxPDO 131 | UINT8 | RO | 0x01 (1dec)) |
1682:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x09 (Target torque)) | UINT32 | RO | 0x7110:09, 16 |
Index 1683 DRV RxPDO-Map Commutation angle Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1683:0 | DRV RxPDO-Map Commutation angle Ch.2 | PDO Mapping RxPDO 132 | UINT8 | RO | 0x01 (1dec)) |
1683:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x0E (Commutation angle)) | UINT32 | RO | 0x7110:0E, 16 |
Index 1684 DRV RxPDO-Map Torque limitation Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1684:0 | DRV RxPDO-Map Torque limitation Ch.2 | PDO Mapping RxPDO 133 | UINT8 | RO | 0x01 (1dec)) |
1684:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x0B (Torque limitation)) | UINT32 | RO | 0x7110:0B, 16 |
Index 1685 DRV RxPDO-Map Torque offset Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1685:0 | DRV RxPDO-Map Torque offset Ch.2 | PDO Mapping RxPDO 134 | UINT8 | RO | 0x01 (1dec)) |
1685:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x0A (Torque offset)) | UINT32 | RO | 0x7110:0A, 16 |
Index 1686 DRV RxPDO-Map Target position Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1686:0 | DRV RxPDO-Map Target position Ch.2 | PDO Mapping RxPDO 135 | UINT8 | RO | 0x01 (1dec)) |
1686:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x05 (Target position)) | UINT32 | RO | 0x7110:05, 32 |
Index 1687 FB RxPDO-Map Touch probe control Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1687:0 | FB RxPDO-Map Touch probe control Ch.2 | PDO Mapping RxPDO 136 | UINT8 | RO | 0x0C (12dec)) |
1687:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x01 (TP1 Enable)) | UINT32 | RO | 0x7101:01, 1 |
1687:02 | SubIndex 002 | PDO Mapping entry no. 2 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x02 (TP1 Continous)) | UINT32 | RO | 0x7101:02, 1 |
1687:03 | SubIndex 003 | PDO Mapping entry no. 3 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x03 (TP1 Trigger mode)) | UINT32 | RO | 0x7101:03, 2 |
1687:04 | SubIndex 004 | PDO Mapping entry no. 4 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x05 (TP1 Enable pos edge)) | UINT32 | RO | 0x7101:05, 1 |
1687:05 | SubIndex 005 | PDO Mapping entry no. 5 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x06 (TP1 Enable neg edge)) | UINT32 | RO | 0x7101:06, 1 |
1687:06 | SubIndex 006 | PDO Mapping entry no. 6 (2 bits align) | UINT32 | RO | 0x0000:00, 2 |
1687:07 | SubIndex 007 | PDO Mapping entry no. 7 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x09 (TP2 Enable)) | UINT32 | RO | 0x7101:09, 1 |
1687:08 | SubIndex 008 | PDO Mapping entry no. 8 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x0A (TP2 Continous)) | UINT32 | RO | 0x7101:0A, 1 |
1687:09 | SubIndex 009 | PDO Mapping entry no. 9 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x0B (TP2 Trigger mode)) | UINT32 | RO | 0x7101:0B, 2 |
1687:0A | SubIndex 010 | PDO Mapping entry no. 10 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x0D (TP2 Enable pos edge)) | UINT32 | RO | 0x7101:0D, 1 |
1687:0B | SubIndex 011 | PDO Mapping entry no. 11 (object 0x7101 (FB Touch probe outputs Ch.2), entry 0x0E (TP2 Enable neg edge)) | UINT32 | RO | 0x7101:0E, 1 |
1687:0C | SubIndex 012 | PDO Mapping entry no. 12 (2 bits align) | UINT32 | RO | 0x0000:00, 2 |
Index 1688 DRV RxPDO-Map Modes of operation Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1688:0 | DRV RxPDO-Map Modes of operation Ch.2 | PDO Mapping RxPDO 137 | UINT8 | RO | 0x01 (1dec)) |
1688:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x03 (Modes of operation)) | UINT32 | RO | 0x7110:03, 8 |
Index 1689 DRV RxPDO-Map Velocity offset Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1689:0 | DRV RxPDO-Map Velocity offset Ch.2 | PDO Mapping RxPDO 138 | UINT8 | RO | 0x01 (1dec)) |
1689:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x0F (Velocity offset)) | UINT32 | RO | 0x7110:0F, 32 |
Index 168A DRV RxPDO-Map Positive torque limit value Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
168A:0 | DRV RxPDO-Map Positive torque limit value Ch.2 | PDO Mapping RxPDO 139 | UINT8 | RO | 0x01 (1dec)) |
168A:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x10 (Positive torque limit value)) | UINT32 | RO | 0x7110:10, 16 |
Index 168B DRV RxPDO-Map Negative torque limit value Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
168B:0 | DRV RxPDO-Map Negative torque limit value Ch.2 | PDO Mapping RxPDO 140 | UINT8 | RO | 0x01 (1dec)) |
168B:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x11 (Negative torque limit value)) | UINT32 | RO | 0x7110:11, 16 |
Index 168C DRV RxPDO-Map Low velocity limit value Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
168C:0 | DRV RxPDO-Map Low velocity limit value Ch.2 | PDO Mapping RxPDO 141 | UINT8 | RO | 0x01 (1dec)) |
168C:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x12 (Low velocity limit value)) | UINT32 | RO | 0x7110:12, 32 |
Index 168D DRV RxPDO-Map High velocity limit value Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
168D:0 | DRV RxPDO-Map High velocity limit value Ch.2 | PDO Mapping RxPDO 142 | UINT8 | RO | 0x01 (1dec)) |
168D:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x7110 (DRV Outputs Ch.2), entry 0x13 (High velocity limit value)) | UINT32 | RO | 0x7110:13, 32 |
Index 16E0 DMC RxPDO-Map Outputs Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
16E0:0 | DMC RxPDO-Map Outputs Ch.2 | PDO Mapping RxPDO 225 | UINT8 | RO | 0x12 (18dec)) |
16E0:01 | SubIndex 001 | PDO Mapping entry no. 1 (1 bits align) | UINT32 | RO | 0x0000:00, 1 |
16E0:02 | SubIndex 002 | PDO Mapping entry no. 2 (object 0x7160 (DMC Outputs Ch.2), entry 0x02 (DMC__FeedbackControl__Enable latch extern on positive edge)) | UINT32 | RO | 0x7160:02, 1 |
16E0:03 | SubIndex 003 | PDO Mapping entry no. 3 (object 0x7160 (DMC Outputs Ch.2), entry 0x03 (DMC__FeedbackControl__Set counter)) | UINT32 | RO | 0x7160:03, 1 |
16E0:04 | SubIndex 004 | PDO Mapping entry no. 4 (object 0x7160 (DMC Outputs Ch.2), entry 0x04 (DMC__FeedbackControl__Enable latch extern on negative edge)) | UINT32 | RO | 0x7160:04, 1 |
16E0:05 | SubIndex 005 | PDO Mapping entry no. 5 (12 bits align) | UINT32 | RO | 0x0000:00, 12 |
16E0:06 | SubIndex 006 | PDO Mapping entry no. 6 (object 0x7160 (DMC Outputs Ch.2), entry 0x11 (DMC__DriveControl__Enable)) | UINT32 | RO | 0x7160:11, 1 |
16E0:07 | SubIndex 007 | PDO Mapping entry no. 7 (object 0x7160 (DMC Outputs Ch.2), entry 0x12 (DMC__DriveControl__Reset)) | UINT32 | RO | 0x7160:12, 1 |
16E0:08 | SubIndex 008 | PDO Mapping entry no. 8 (14 bits align) | UINT32 | RO | 0x0000:00, 14 |
16E0:09 | SubIndex 009 | PDO Mapping entry no. 9 (object 0x7160 (DMC Outputs Ch.2), entry 0x21 (DMC__PositioningControl__Execute)) | UINT32 | RO | 0x7160:21, 1 |
16E0:0A | SubIndex 010 | PDO Mapping entry no. 10 (object 0x7160 (DMC Outputs Ch.2), entry 0x22 (DMC__PositioningControl__Emergency stop)) | UINT32 | RO | 0x7160:22, 1 |
16E0:0B | SubIndex 011 | PDO Mapping entry no. 11 (14 bits align) | UINT32 | RO | 0x0000:00, 14 |
16E0:0C | SubIndex 012 | PDO Mapping entry no. 12 (object 0x7160 (DMC Outputs Ch.2), entry 0x31 (DMC__Set counter value)) | UINT32 | RO | 0x7160:31, 64 |
16E0:0D | SubIndex 013 | PDO Mapping entry no. 13 (object 0x7160 (DMC Outputs Ch.2), entry 0x32 (DMC__Target position)) | UINT32 | RO | 0x7160:32, 64 |
16E0:0E | SubIndex 014 | PDO Mapping entry no. 14 (object 0x7160 (DMC Outputs Ch.2), entry 0x33 (DMC__Target velocity)) | UINT32 | RO | 0x7160:33, 16 |
16E0:0F | SubIndex 015 | PDO Mapping entry no. 15 (object 0x7160 (DMC Outputs Ch.2), entry 0x34 (DMC__Start type)) | UINT32 | RO | 0x7160:34, 16 |
16E0:10 | SubIndex 016 | PDO Mapping entry no. 16 (object 0x7160 (DMC Outputs Ch.2), entry 0x35 (DMC__Target acceleration)) | UINT32 | RO | 0x7160:35, 16 |
16E0:11 | SubIndex 017 | PDO Mapping entry no. 17 (object 0x7160 (DMC Outputs Ch.2), entry 0x36 (DMC__Target deceleration)) | UINT32 | RO | 0x7160:36, 16 |
16E0:12 | SubIndex 018 | PDO Mapping entry no. 18 (80 bits align) | UINT32 | RO | 0x0000:00, 80 |
Index 16E1 DMC RxPDO-Map Outputs 32 Bit Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
16E1:0 | DMC RxPDO-Map Outputs 32 Bit Ch.2 | PDO Mapping RxPDO 226 | UINT8 | RO | 0x14 (20dec)) |
16E1:01 | SubIndex 001 | PDO Mapping entry no. 1 (1 bits align) | UINT32 | RO | 0x0000:00, 1 |
16E1:02 | SubIndex 002 | PDO Mapping entry no. 2 (object 0x7160 (DMC Outputs Ch.2), entry 0x02 (DMC__FeedbackControl__Enable latch extern on positive edge)) | UINT32 | RO | 0x7160:02, 1 |
16E1:03 | SubIndex 003 | PDO Mapping entry no. 3 (object 0x7160 (DMC Outputs Ch.2), entry 0x03 (DMC__FeedbackControl__Set counter)) | UINT32 | RO | 0x7160:03, 1 |
16E1:04 | SubIndex 004 | PDO Mapping entry no. 4 (object 0x7160 (DMC Outputs Ch.2), entry 0x04 (DMC__FeedbackControl__Enable latch extern on negative edge)) | UINT32 | RO | 0x7160:04, 1 |
16E1:05 | SubIndex 005 | PDO Mapping entry no. 5 (12 bits align) | UINT32 | RO | 0x0000:00, 12 |
16E1:06 | SubIndex 006 | PDO Mapping entry no. 6 (object 0x7160 (DMC Outputs Ch.2), entry 0x11 (DMC__DriveControl__Enable)) | UINT32 | RO | 0x7160:11, 1 |
16E1:07 | SubIndex 007 | PDO Mapping entry no. 7 (object 0x7160 (DMC Outputs Ch.2), entry 0x12 (DMC__DriveControl__Reset)) | UINT32 | RO | 0x7160:12, 1 |
16E1:08 | SubIndex 008 | PDO Mapping entry no. 8 (14 bits align) | UINT32 | RO | 0x0000:00, 14 |
16E1:09 | SubIndex 009 | PDO Mapping entry no. 9 (object 0x7160 (DMC Outputs Ch.2), entry 0x21 (DMC__PositioningControl__Execute)) | UINT32 | RO | 0x7160:21, 1 |
16E1:0A | SubIndex 010 | PDO Mapping entry no. 10 (object 0x7160 (DMC Outputs Ch.2), entry 0x22 (DMC__PositioningControl__Emergency stop)) | UINT32 | RO | 0x7160:22, 1 |
16E1:0B | SubIndex 011 | PDO Mapping entry no. 11 (14 bits align) | UINT32 | RO | 0x0000:00, 14 |
16E1:0C | SubIndex 012 | PDO Mapping entry no. 12 (object 0x7160 (DMC Outputs Ch.2), entry 0x31 (DMC__Set counter value)) | UINT32 | RO | 0x7160:31, 32 |
16E1:0D | SubIndex 013 | PDO Mapping entry no. 13 (32 bits align) | UINT32 | RO | 0x0000:00, 32 |
16E1:0E | SubIndex 014 | PDO Mapping entry no. 14 (object 0x7160 (DMC Outputs Ch.2), entry 0x32 (DMC__Target position)) | UINT32 | RO | 0x7160:32, 32 |
16E1:0F | SubIndex 015 | PDO Mapping entry no. 15 (32 bits align) | UINT32 | RO | 0x0000:00, 32 |
16E1:10 | SubIndex 016 | PDO Mapping entry no. 16 (object 0x7160 (DMC Outputs Ch.2), entry 0x33 (DMC__Target velocity)) | UINT32 | RO | 0x7160:33, 16 |
16E1:11 | SubIndex 017 | PDO Mapping entry no. 17 (object 0x7160 (DMC Outputs Ch.2), entry 0x34 (DMC__Start type)) | UINT32 | RO | 0x7160:34, 16 |
16E1:12 | SubIndex 018 | PDO Mapping entry no. 18 (object 0x7160 (DMC Outputs Ch.2), entry 0x35 (DMC__Target acceleration)) | UINT32 | RO | 0x7160:35, 16 |
16E1:13 | SubIndex 019 | PDO Mapping entry no. 19 (object 0x7160 (DMC Outputs Ch.2), entry 0x36 (DMC__Target deceleration)) | UINT32 | RO | 0x7160:36, 16 |
16E1:14 | SubIndex 020 | PDO Mapping entry no. 20 (80 bits align) | UINT32 | RO | 0x0000:00, 80 |
Index 1860 DMC TxPDO-Par Inputs Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1860:0 |
DMC TxPDO-Par Inputs Ch.1 |
PDO Parameter TxPDO 97 |
UINT8 |
RO |
0x06 (6dec) |
|
1860:06 |
Exclude TxPDOs |
Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 97 |
OCTET-STRING[2] |
RO |
61 1A |
Index 1861 DMC TxPDO-Par Inputs 32 Bit Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1861:0 |
DMC TxPDO-Par Inputs 32 Bit Ch.1 |
PDO Parameter TxPDO 98 |
UINT8 |
RO |
0x06 (6dec) |
|
1861:06 |
Exclude TxPDOs |
Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 98 |
OCTET-STRING[2] |
RO |
60 1A |
Index 18E0 DMC TxPDO-Par Inputs Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
18E0:0 | DMC TxPDO-Par Inputs Ch.2 | PDO Parameter TxPDO 225 | UINT8 | RO | 0x06 (6dec)) |
18E0:06 | Exclude TxPDOs | Specifies the TxPDOs (index of TxPDO mapping objects) that may not be transferred with TxPDO 225 | OCTET-STRING[2] | RO | E1 1A |
Index 18E1 DMC TxPDO-Par Inputs 32 Bit Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
18E1:0 | DMC TxPDO-Par Inputs 32 Bit Ch.2 | PDO Parameter TxPDO 226 | UINT8 | RO | 0x06 (6dec)) |
18E1:06 | Exclude TxPDOs | Specifies the TxPDOs (index of TxPDO mapping objects) that may not be transferred with TxPDO 226 | OCTET-STRING[2] | RO | E0 1A |
Index 1A00 FB TxPDO-Map Position Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A00:0 |
FB TxPDO-Map Position Ch.1 |
PDO Mapping TxPDO 1 |
UINT8 |
RO |
0x01 (1dec) |
|
1A00:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6000 (FB Inputs Ch.1), entry 0x11 (Position)) |
UINT32 |
RO |
0x6000:11, 32 |
Index 1A01 DRV TxPDO-Map Statusword Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A01:0 |
DRV TxPDO-Map Statusword Ch.1 |
PDO Mapping TxPDO 2 |
UINT8 |
RO |
0x01 (1dec) |
|
1A01:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x01 (Statusword)) |
UINT32 |
RO |
0x6010:01, 16 |
Index 1A02 DRV TxPDO-Map Velocity actual value Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A02:0 |
DRV TxPDO-Map Velocity actual value Ch.1 |
PDO Mapping TxPDO 3 |
UINT8 |
RO |
0x01 (1dec) |
|
1A02:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x07 (Velocity actual value)) |
UINT32 |
RO |
0x6010:07, 32 |
Index 1A03 DRV TxPDO-Map Torque actual value Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A03:0 |
DRV TxPDO-Map Torque actual value Ch.1 |
PDO Mapping TxPDO 4 |
UINT8 |
RO |
0x01 (1dec) |
|
1A03:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x08 (Torque actual value)) |
UINT32 |
RO |
0x6010:08, 16 |
Index 1A04 DRV TxPDO-Map Info data 1 Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A04:0 |
DRV TxPDO-Map Info data 1 Ch.1 |
PDO Mapping TxPDO 5 |
UINT8 |
RW |
0x01 (1dec) |
|
1A04:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x12 (Info data 1)) |
UINT32 |
RW |
0x6010:12, 16 |
|
1A04:02 |
SubIndex 002 |
2nd PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:03 |
SubIndex 003 |
3rd PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:04 |
SubIndex 004 |
4th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:05 |
SubIndex 005 |
5th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:06 |
SubIndex 006 |
6th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:07 |
SubIndex 007 |
7th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:08 |
SubIndex 008 |
8th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:09 |
SubIndex 009 |
9th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:0A |
SubIndex 010 |
10th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:0B |
SubIndex 011 |
11th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:0C |
SubIndex 012 |
12th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:0D |
SubIndex 013 |
13th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:0E |
SubIndex 014 |
14th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:0F |
SubIndex 015 |
15th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A04:10 |
SubIndex 016 |
16th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
Index 1A05 DRV TxPDO-Map Info data 2 Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A05:0 |
DRV TxPDO-Map Info data 2 Ch.1 |
PDO Mapping TxPDO 6 |
UINT8 |
RW |
0x01 (1dec) |
|
1A05:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x13 (Info data 2)) |
UINT32 |
RW |
0x6010:13, 16 |
|
1A05:02 |
SubIndex 002 |
2nd PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:03 |
SubIndex 003 |
3rd PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:04 |
SubIndex 004 |
4th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:05 |
SubIndex 005 |
5th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:06 |
SubIndex 006 |
6th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:07 |
SubIndex 007 |
7th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:08 |
SubIndex 008 |
8th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:09 |
SubIndex 009 |
9th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:0A |
SubIndex 010 |
10th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:0B |
SubIndex 011 |
11th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:0C |
SubIndex 012 |
12th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:0D |
SubIndex 013 |
13th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:0E |
SubIndex 014 |
14th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:0F |
SubIndex 015 |
15th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A05:10 |
SubIndex 016 |
16th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
Index 1A06 DRV TxPDO-Map Following error actual value Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A06:0 |
DRV TxPDO-Map Following error actual value Ch.1 |
PDO Mapping TxPDO 7 |
UINT8 |
RO |
0x01 (1dec) |
|
1A06:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x06 (Following error actual value)) |
UINT32 |
RO |
0x6010:06, 32 |
Index 1A07 FB TxPDO-Map Touch probe status Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A07:0 |
FB TxPDO-Map Touch probe status Ch.1 |
PDO Mapping TxPDO 8 |
UINT8 |
RO |
0x0A (10dec) |
|
1A07:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x01 (TP1 Enable)) |
UINT32 |
RO |
0x6001:01, 1 |
|
1A07:02 |
SubIndex 002 |
2nd PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x02 (TP1 Pos value stored)) |
UINT32 |
RO |
0x6001:02, 1 |
|
1A07:03 |
SubIndex 003 |
3rd PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x03 (TP1 Neg value stored)) |
UINT32 |
RO |
0x6001:03, 1 |
|
1A07:04 |
SubIndex 004 |
4th PDO Mapping entry (4 bits align) |
UINT32 |
RO |
0x0000:00, 4 |
|
1A07:05 |
SubIndex 005 |
5th PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x08 (TP1 Input)) |
UINT32 |
RO |
0x6001:08, 1 |
|
1A07:06 |
SubIndex 006 |
6th PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x09 (TP2 Enable)) |
UINT32 |
RO |
0x6001:09, 1 |
|
1A07:07 |
SubIndex 007 |
7th PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x0A (TP2 Pos value stored)) |
UINT32 |
RO |
0x6001:0A, 1 |
|
1A07:08 |
SubIndex 008 |
8th PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x0B (TP2 Neg value stored)) |
UINT32 |
RO |
0x6001:0B, 1 |
|
1A07:09 |
SubIndex 009 |
9th PDO Mapping entry (4 bits align) |
UINT32 |
RO |
0x0000:00, 4 |
|
1A07:0A |
SubIndex 010 |
10th PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x10 (TP2 Input)) |
UINT32 |
RO |
0x6001:10, 1 |
Index 1A08 FB TxPDO-Map Touch probe 1 pos position Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A08:0 |
FB TxPDO-Map Touch probe 1 pos position Ch.1 |
PDO Mapping TxPDO 9 |
UINT8 |
RO |
0x01 (1dec) |
|
1A08:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x11 (TP1 Pos position)) |
UINT32 |
RO |
0x6001:11, 32 |
Index 1A09 FB TxPDO-Map Touch probe 1 neg position Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A09:0 |
FB TxPDO-Map Touch probe 1 neg position Ch.1 |
PDO Mapping TxPDO 10 |
UINT8 |
RO |
0x01 (1dec) |
|
1A09:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x12 (TP1 Neg position)) |
UINT32 |
RO |
0x6001:12, 32 |
Index 1A0A FB TxPDO-Map Touch probe 2 pos position Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0A:0 |
FB TxPDO-Map Touch probe 2 pos position Ch.1 |
PDO Mapping TxPDO 11 |
UINT8 |
RO |
0x01 (1dec) |
|
1A0A:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x13 (TP2 Pos position)) |
UINT32 |
RO |
0x6001:13, 32 |
Index 1A0B FB TxPDO-Map Touch probe 2 neg position Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0B:0 |
FB TxPDO-Map Touch probe 2 neg position Ch.1 |
PDO Mapping TxPDO 12 |
UINT8 |
RO |
0x01 (1dec) |
|
1A0B:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x14 (TP2 Neg position)) |
UINT32 |
RO |
0x6001:14, 32 |
Index 1A0D DRV TxPDO-Map Info data 3 Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0D:0 |
DRV TxPDO-Map Info data 3 Ch.1 |
PDO Mapping TxPDO 14 |
UINT8 |
RW |
0x01 (1dec) |
|
1A0D:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x14 (Info data 3)) |
UINT32 |
RW |
0x6010:14, 16 |
|
1A0D:02 |
SubIndex 002 |
2nd PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:03 |
SubIndex 003 |
3rd PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:04 |
SubIndex 004 |
4th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:05 |
SubIndex 005 |
5th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:06 |
SubIndex 006 |
6th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:07 |
SubIndex 007 |
7th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:08 |
SubIndex 008 |
8th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:09 |
SubIndex 009 |
9th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:0A |
SubIndex 010 |
10th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:0B |
SubIndex 011 |
11th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:0C |
SubIndex 012 |
12th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:0D |
SubIndex 013 |
13th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:0E |
SubIndex 014 |
14th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:0F |
SubIndex 015 |
15th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
|
1A0D:10 |
SubIndex 016 |
16th PDO Mapping entry (0 bits align) |
UINT32 |
RW |
0x0000:00, 0 |
Index 1A0E DRV TxPDO-Map Modes of operation display Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0E:0 |
DRV TxPDO-Map Modes of operation display Ch.1 |
PDO Mapping TxPDO 15 |
UINT8 |
RO |
0x01 (1dec) |
|
1A0E:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x03 (Modes of operation display)) |
UINT32 |
RO |
0x6010:03, 8 |
Index 1A0F DRV TxPDO-Map Torque limitation status Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0F:0 |
DRV TxPDO-Map Torque limitation status Ch.1 |
PDO Mapping TxPDO 16 |
UINT8 |
RO |
0x01 (1dec) |
|
1A0F:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6010 (DRV Inputs Ch.1), entry 0x15 (Torque limitation status)) |
UINT32 |
RO |
0x6010:15, 8 |
Index 1A10 DI TxPDO-Map Inputs Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A10:0 |
DI TxPDO-Map Inputs Ch.1 |
PDO Mapping TxPDO 17 |
UINT8 |
RO |
0x07 (7dec) |
|
1A10:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6020 (DI Inputs Ch.1), entry 0x01 (Input 1)) |
UINT32 |
RO |
0x6020:01, 1 |
|
1A10:02 |
SubIndex 002 |
2nd PDO Mapping entry (object 0x6020 (DI Inputs Ch.1), entry 0x02 (Input 2)) |
UINT32 |
RO |
0x6020:02, 1 |
|
1A10:03 |
SubIndex 003 |
3rd PDO Mapping entry (2 bits align) |
UINT32 |
RO |
0x0000:00, 2 |
|
1A10:04 |
SubIndex 004 |
4th PDO Mapping entry (object 0x6020 (DI Inputs Ch.1), entry 0x05 (Encoder A)) |
UINT32 |
RO |
0x6020:05, 1 |
|
1A10:05 |
SubIndex 005 |
5th PDO Mapping entry (object 0x6020 (DI Inputs Ch.1), entry 0x06 (Encoder B)) |
UINT32 |
RO |
0x6020:06, 1 |
|
1A10:06 |
SubIndex 006 |
6th PDO Mapping entry (object 0x6020 (DI Inputs Ch.1), entry 0x07 (Encoder C)) |
UINT32 |
RO |
0x6020:07, 1 |
|
1A10:07 |
SubIndex 007 |
7th PDO Mapping entry (9 bits align) |
UINT32 |
RO |
0x0000:00, 9 |
Index 1A11 FB TxPDO-Map Touch probe 1 pos timestamp Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A11:0 |
FB TxPDO-Map Touch probe 1 pos timestamp Ch.1 |
PDO Mapping TxPDO 18 |
UINT8 |
RO |
0x01 (1dec) |
|
1A11:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x15 (TP1 Pos timestamp)) |
UINT32 |
RO |
0x6001:15, 32 |
Index 1A12 FB TxPDO-Map Touch probe 1 neg timestamp Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A12:0 |
FB TxPDO-Map Touch probe 1 neg timestamp Ch.1 |
PDO Mapping TxPDO 19 |
UINT8 |
RO |
0x01 (1dec) |
|
1A12:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x16 (TP1 Neg timestamp)) |
UINT32 |
RO |
0x6001:16, 32 |
Index 1A13 FB TxPDO-Map Touch probe 2 pos timestamp Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A13:0 |
FB TxPDO-Map Touch probe 2 pos timestamp Ch.1 |
PDO Mapping TxPDO 20 |
UINT8 |
RO |
0x01 (1dec) |
|
1A13:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x17 (TP2 Pos timestamp)) |
UINT32 |
RO |
0x6001:17, 32 |
Index 1A14 FB TxPDO-Map Touch probe 2 neg timestamp Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A14:0 |
FB TxPDO-Map Touch probe 2 neg timestamp Ch.1 |
PDO Mapping TxPDO 21 |
UINT8 |
RO |
0x01 (1dec) |
|
1A14:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6001 (FB Touch probe inputs Ch.1), entry 0x18 (TP2 Neg timestamp)) |
UINT32 |
RO |
0x6001:18, 32 |
Index 1A15 FB TxPDO-Map Secondary Position Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A15:0 |
FB TxPDO-Map Secondary Position Ch.1 |
PDO Mapping TxPDO 22 |
UINT8 |
RO |
0x01 (1dec) |
|
1A15:01 |
SubIndex 001 |
1st PDO Mapping entry (object 0x6000 (FB Inputs Ch.1), entry 0x15 (Secondary position)) |
UINT32 |
RO |
0x6000:15, 32 |
Index 1A60 DMC TxPDO-Map Inputs Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A60:0 |
DMC TxPDO-Map Inputs Ch.1 |
PDO Mapping TxPDO 97 |
UINT8 |
RO |
0x26 (38dec) |
|
1A60:01 |
SubIndex 001 |
1st PDO Mapping entry (1 bit aligns) |
UINT32 |
RO |
0x0000:00, 1 |
|
1A60:02 |
SubIndex 002 |
2nd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x02 (DMC__FeedbackStatus__Latch extern valid)) |
UINT32 |
RO |
0x6060:02, 1 |
|
1A60:03 |
SubIndex 003 |
3rd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x03 (DMC__FeedbackStatus__Set counter done)) |
UINT32 |
RO |
0x6060:03, 1 |
|
1A60:04 |
SubIndex 004 |
4th PDO Mapping entry (9 bits align) |
UINT32 |
RO |
0x0000:00, 9 |
|
1A60:05 |
SubIndex 005 |
5th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x0D (DMC__FeedbackStatus__Status of extern latch)) |
UINT32 |
RO |
0x6060:0D, 1 |
|
1A60:06 |
SubIndex 006 |
6th PDO Mapping entry (3 bits align) |
UINT32 |
RO |
0x0000:00, 3 |
|
1A60:07 |
SubIndex 007 |
7th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x11 (DMC__DriveStatus__Ready to enable)) |
UINT32 |
RO |
0x6060:11, 1 |
|
1A60:08 |
SubIndex 008 |
8th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x12 (DMC__DriveStatus__Ready)) |
UINT32 |
RO |
0x6060:12, 1 |
|
1A60:09 |
SubIndex 009 |
9th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x13 (DMC__DriveStatus__Warning)) |
UINT32 |
RO |
0x6060:13, 1 |
|
1A60:0A |
SubIndex 010 |
10th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x14 (DMC__DriveStatus__Error)) |
UINT32 |
RO |
0x6060:14, 1 |
|
1A60:0B |
SubIndex 011 |
11th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x15 (DMC__DriveStatus__Moving positive)) |
UINT32 |
RO |
0x6060:15, 1 |
|
1A60:0C |
SubIndex 012 |
12th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x16 (DMC__DriveStatus__Moving negative)) |
UINT32 |
RO |
0x6060:16, 1 |
|
1A60:0D |
SubIndex 013 |
13th PDO Mapping entry (5 bits align) |
UINT32 |
RO |
0x0000:00, 5 |
|
1A60:0E |
SubIndex 014 |
14th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x1C (DMC__DriveStatus__Digital input 1)) |
UINT32 |
RO |
0x6060:1C, 1 |
|
1A60:0F |
SubIndex 015 |
15th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x1D (DMC__DriveStatus__Digital input 2)) |
UINT32 |
RO |
0x6060:1D, 1 |
|
1A60:10 |
SubIndex 016 |
16th PDO Mapping entry (3 bits align) |
UINT32 |
RO |
0x0000:00, 3 |
|
1A60:11 |
SubIndex 017 |
17th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x21 (DMC__PositioningStatus__Busy)) |
UINT32 |
RO |
0x6060:21, 1 |
|
1A60:12 |
SubIndex 018 |
18th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x22 (DMC__PositioningStatus__In-Target)) |
UINT32 |
RO |
0x6060:22, 1 |
|
1A60:13 |
SubIndex 019 |
19th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x23 (DMC__PositioningStatus__Warning)) |
UINT32 |
RO |
0x6060:23, 1 |
|
1A60:14 |
SubIndex 020 |
20th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x24 (DMC__PositioningStatus__Error)) |
UINT32 |
RO |
0x6060:24, 1 |
|
1A60:15 |
SubIndex 021 |
21st PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x25 (DMC__PositioningStatus__Calibrated)) |
UINT32 |
RO |
0x6060:25, 1 |
|
1A60:16 |
SubIndex 022 |
22nd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x26 (DMC__PositioningStatus__Accelerate)) |
UINT32 |
RO |
0x6060:26, 1 |
|
1A60:17 |
SubIndex 023 |
23rd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x27 (DMC__PositioningStatus__Decelerate)) |
UINT32 |
RO |
0x6060:27, 1 |
|
1A60:18 |
SubIndex 024 |
24th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x28 (DMC__PositioningStatus__Ready to execute)) |
UINT32 |
RO |
0x6060:28, 1 |
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A60:19 |
SubIndex 025 |
25th PDO Mapping entry (8 bits align) |
UINT32 |
RO |
0x0000:00, 8 |
|
1A60:1A |
SubIndex 026 |
26th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x31 (DMC__Set position)) |
UINT32 |
RO |
0x6060:31, 64 |
|
1A60:1B |
SubIndex 027 |
27th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x32 (DMC__Set velocity)) |
UINT32 |
RO |
0x6060:32, 16 |
|
1A60:1C |
SubIndex 028 |
28th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x33 (DMC__Actual drive time)) |
UINT32 |
RO |
0x6060:33, 32 |
|
1A60:1D |
SubIndex 029 |
29th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x34 (DMC__Actual position lag)) |
UINT32 |
RO |
0x6060:34, 64 |
|
1A60:1E |
SubIndex 030 |
30th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x35 (DMC__Actual velocity)) |
UINT32 |
RO |
0x6060:35, 16 |
|
1A60:1F |
SubIndex 031 |
31st PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x36 (DMC__Actual position)) |
UINT32 |
RO |
0x6060:36, 64 |
|
1A60:20 |
SubIndex 032 |
32nd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x37 (DMC__Error id)) |
UINT32 |
RO |
0x6060:37, 32 |
|
1A60:21 |
SubIndex 033 |
33rd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x38 (DMC__Input cycle counter)) |
UINT32 |
RO |
0x6060:38, 8 |
|
1A60:22 |
SubIndex 034 |
34th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x39 (DMC__Channel id)) |
UINT32 |
RO |
0x6060:39, 8 |
|
1A60:23 |
SubIndex 035 |
35th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x3A (DMC__Latch value)) |
UINT32 |
RO |
0x6060:3A, 64 |
|
1A60:24 |
SubIndex 036 |
36th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x3B (DMC__Cyclic info data 1)) |
UINT32 |
RO |
0x6060:3B, 16 |
|
1A60:25 |
SubIndex 037 |
37th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x3C (DMC__Cyclic info data 2)) |
UINT32 |
RO |
0x6060:3C, 16 |
|
1A60:26 |
SubIndex 038 |
38th PDO Mapping entry (64 bits align) |
UINT32 |
RO |
0x0000:00, 64 |
Index 1A61 DMC TxPDO-Map Inputs 32 Bit Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A61:0 |
DMC TxPDO-Map Inputs 32 Bit Ch.1 |
PDO Mapping TxPDO 98 |
UINT8 |
RO |
0x2A (42dec) |
|
1A61:01 |
SubIndex 001 |
1st PDO Mapping entry (1 bit aligns) |
UINT32 |
RO |
0x0000:00, 1 |
|
1A61:02 |
SubIndex 002 |
2nd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x02 (DMC__FeedbackStatus__Latch extern valid)) |
UINT32 |
RO |
0x6060:02, 1 |
|
1A61:03 |
SubIndex 003 |
3rd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x03 (DMC__FeedbackStatus__Set counter done)) |
UINT32 |
RO |
0x6060:03, 1 |
|
1A61:04 |
SubIndex 004 |
4th PDO Mapping entry (9 bits align) |
UINT32 |
RO |
0x0000:00, 9 |
|
1A61:05 |
SubIndex 005 |
5th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x0D (DMC__FeedbackStatus__Status of extern latch)) |
UINT32 |
RO |
0x6060:0D, 1 |
|
1A61:06 |
SubIndex 006 |
6th PDO Mapping entry (3 bits align) |
UINT32 |
RO |
0x0000:00, 3 |
|
1A61:07 |
SubIndex 007 |
7th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x11 (DMC__DriveStatus__Ready to enable)) |
UINT32 |
RO |
0x6060:11, 1 |
|
1A61:08 |
SubIndex 008 |
8th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x12 (DMC__DriveStatus__Ready)) |
UINT32 |
RO |
0x6060:12, 1 |
|
1A61:09 |
SubIndex 009 |
9th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x13 (DMC__DriveStatus__Warning)) |
UINT32 |
RO |
0x6060:13, 1 |
|
1A61:0A |
SubIndex 010 |
10th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x14 (DMC__DriveStatus__Error)) |
UINT32 |
RO |
0x6060:14, 1 |
|
1A61:0B |
SubIndex 011 |
11th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x15 (DMC__DriveStatus__Moving positive)) |
UINT32 |
RO |
0x6060:15, 1 |
|
1A61:0C |
SubIndex 012 |
12th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x16 (DMC__DriveStatus__Moving negative)) |
UINT32 |
RO |
0x6060:16, 1 |
|
1A61:0D |
SubIndex 013 |
13th PDO Mapping entry (5 bits align) |
UINT32 |
RO |
0x0000:00, 5 |
|
1A61:0E |
SubIndex 014 |
14th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x1C (DMC__DriveStatus__Digital input 1)) |
UINT32 |
RO |
0x6060:1C, 1 |
|
1A61:0F |
SubIndex 015 |
15th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x1D (DMC__DriveStatus__Digital input 2)) |
UINT32 |
RO |
0x6060:1D, 1 |
|
1A61:10 |
SubIndex 016 |
16th PDO Mapping entry (3 bits align) |
UINT32 |
RO |
0x0000:00, 3 |
|
1A61:11 |
SubIndex 017 |
17th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x21 (DMC__PositioningStatus__Busy)) |
UINT32 |
RO |
0x6060:21, 1 |
|
1A61:12 |
SubIndex 018 |
18th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x22 (DMC__PositioningStatus__In-Target)) |
UINT32 |
RO |
0x6060:22, 1 |
|
1A61:13 |
SubIndex 019 |
19th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x23 (DMC__PositioningStatus__Warning)) |
UINT32 |
RO |
0x6060:23, 1 |
|
1A61:14 |
SubIndex 020 |
20th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x24 (DMC__PositioningStatus__Error)) |
UINT32 |
RO |
0x6060:24, 1 |
|
1A61:15 |
SubIndex 021 |
21st PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x25 (DMC__PositioningStatus__Calibrated)) |
UINT32 |
RO |
0x6060:25, 1 |
|
1A61:16 |
SubIndex 022 |
22nd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x26 (DMC__PositioningStatus__Accelerate)) |
UINT32 |
RO |
0x6060:26, 1 |
|
1A61:17 |
SubIndex 023 |
23rd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x27 (DMC__PositioningStatus__Decelerate)) |
UINT32 |
RO |
0x6060:27, 1 |
|
1A61:18 |
SubIndex 024 |
24th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x28 (DMC__PositioningStatus__Ready to execute)) |
UINT32 |
RO |
0x6060:28, 1 |
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A61:19 |
SubIndex 025 |
25th PDO Mapping entry (8 bits align) |
UINT32 |
RO |
0x0000:00, 8 |
|
1A61:1A |
SubIndex 026 |
26th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x31 (DMC__Set position)) |
UINT32 |
RO |
0x6060:31, 32 |
|
1A61:1B |
SubIndex 027 |
27th PDO Mapping entry (32 bits align) |
UINT32 |
RO |
0x0000:00, 32 |
|
1A61:1C |
SubIndex 028 |
28th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x32 (DMC__Set velocity)) |
UINT32 |
RO |
0x6060:32, 16 |
|
1A61:1D |
SubIndex 029 |
29th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x33 (DMC__Actual drive time)) |
UINT32 |
RO |
0x6060:33, 32 |
|
1A61:1E |
SubIndex 030 |
30th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x34 (DMC__Actual position lag)) |
UINT32 |
RO |
0x6060:34, 32 |
|
1A61:1F |
SubIndex 031 |
31st PDO Mapping entry (32 bits align) |
UINT32 |
RO |
0x0000:00, 32 |
|
1A61:20 |
SubIndex 032 |
32nd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x35 (DMC__Actual velocity)) |
UINT32 |
RO |
0x6060:35, 16 |
|
1A61:21 |
SubIndex 033 |
33rd PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x36 (DMC__Actual position)) |
UINT32 |
RO |
0x6060:36, 32 |
|
1A61:22 |
SubIndex 034 |
34th PDO Mapping entry (32 bits align) |
UINT32 |
RO |
0x0000:00, 32 |
|
1A61:23 |
SubIndex 035 |
35th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x37 (DMC__Error id)) |
UINT32 |
RO |
0x6060:37, 32 |
|
1A61:24 |
SubIndex 036 |
36th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x38 (DMC__Input cycle counter)) |
UINT32 |
RO |
0x6060:38, 8 |
|
1A61:25 |
SubIndex 037 |
37th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x39 (DMC__Channel id)) |
UINT32 |
RO |
0x6060:39, 8 |
|
1A61:26 |
SubIndex 038 |
38th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x3A (DMC__Latch value)) |
UINT32 |
RO |
0x6060:3A, 32 |
|
1A61:27 |
SubIndex 039 |
39th PDO Mapping entry (32 bits align) |
UINT32 |
RO |
0x0000:00, 32 |
|
1A61:28 |
SubIndex 040 |
40th PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x3B (DMC__Cyclic info data 1)) |
UINT32 |
RO |
0x6060:3B, 16 |
|
1A61:29 |
SubIndex 041 |
41st PDO Mapping entry (object 0x6060 (DMC Inputs Ch.1), entry 0x3C (DMC__Cyclic info data 2)) |
UINT32 |
RO |
0x6060:3C, 16 |
|
1A61:2A |
SubIndex 042 |
42nd PDO Mapping entry (64 bits align) |
UINT32 |
RO |
0x0000:00, 64 |
Index 1A80 FB TxPDO-Map Position Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A80:0 | FB TxPDO-Map Position Ch.2 | PDO Mapping TxPDO 129 | UINT8 | RO | 0x01 (1dec)) |
1A80:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6100 (FB Inputs Ch.2), entry 0x11 (Position)) | UINT32 | RO | 0x6100:11, 32 |
Index 1A81 DRV TxPDO-Map Statusword Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A81:0 | DRV TxPDO-Map Statusword Ch.2 | PDO Mapping TxPDO 130 | UINT8 | RO | 0x01 (1dec)) |
1A81:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x01 (Statusword)) | UINT32 | RO | 0x6110:01, 16 |
Index 1A82 DRV TxPDO-Map Velocity actual value Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A82:0 | DRV TxPDO-Map Velocity actual value Ch.2 | PDO Mapping TxPDO 131 | UINT8 | RO | 0x01 (1dec)) |
1A82:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x07 (Velocity actual value)) | UINT32 | RO | 0x6110:07, 32 |
Index 1A83 DRV TxPDO-Map Torque actual value Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A83:0 | DRV TxPDO-Map Torque actual value Ch.2 | PDO Mapping TxPDO 132 | UINT8 | RO | 0x01 (1dec)) |
1A83:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x08 (Torque actual value)) | UINT32 | RO | 0x6110:08, 16 |
Index 1A84 DRV TxPDO-Map Info data 1 Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A84:0 | DRV TxPDO-Map Info data 1 Ch.2 | PDO Mapping TxPDO 133 | UINT8 | RW | 0x01 (1dec)) |
1A84:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x12 (Info data 1)) | UINT32 | RW | 0x6110:12, 16 |
1A84:02 | SubIndex 002 | PDO Mapping entry no. 2 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:03 | SubIndex 003 | PDO Mapping entry no. 3 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:04 | SubIndex 004 | PDO Mapping entry no. 4 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:05 | SubIndex 005 | PDO Mapping entry no. 5 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:06 | SubIndex 006 | PDO Mapping entry no. 6 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:07 | SubIndex 007 | PDO Mapping entry no. 7 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:08 | SubIndex 008 | PDO Mapping entry no. 8 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:09 | SubIndex 009 | PDO Mapping entry no. 9 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:0A | SubIndex 010 | PDO Mapping entry no. 10 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:0B | SubIndex 011 | PDO Mapping entry no. 11 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:0C | SubIndex 012 | PDO Mapping entry no. 12 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:0D | SubIndex 013 | PDO Mapping entry no. 13 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:0E | SubIndex 014 | PDO Mapping entry no. 14 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:0F | SubIndex 015 | PDO Mapping entry no. 15 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A84:10 | SubIndex 016 | PDO Mapping entry no. 16 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
Index 1A85 DRV TxPDO-Map Info data 2 Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A85:0 | DRV TxPDO-Map Info data 2 Ch.2 | PDO Mapping TxPDO 134 | UINT8 | RW | 0x01 (1dec)) |
1A85:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x13 (Info data 2)) | UINT32 | RW | 0x6110:13, 16 |
1A85:02 | SubIndex 002 | PDO Mapping entry no. 2 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:03 | SubIndex 003 | PDO Mapping entry no. 3 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:04 | SubIndex 004 | PDO Mapping entry no. 4 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:05 | SubIndex 005 | PDO Mapping entry no. 5 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:06 | SubIndex 006 | PDO Mapping entry no. 6 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:07 | SubIndex 007 | PDO Mapping entry no. 7 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:08 | SubIndex 008 | PDO Mapping entry no. 8 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:09 | SubIndex 009 | PDO Mapping entry no. 9 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:0A | SubIndex 010 | PDO Mapping entry no. 10 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:0B | SubIndex 011 | PDO Mapping entry no. 11 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:0C | SubIndex 012 | PDO Mapping entry no. 12 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:0D | SubIndex 013 | PDO Mapping entry no. 13 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:0E | SubIndex 014 | PDO Mapping entry no. 14 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:0F | SubIndex 015 | PDO Mapping entry no. 15 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A85:10 | SubIndex 016 | PDO Mapping entry no. 16 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
Index 1A86 DRV TxPDO-Map Following error actual value Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A86:0 | DRV TxPDO-Map Following error actual value Ch.2 | PDO Mapping TxPDO 135 | UINT8 | RO | 0x01 (1dec)) |
1A86:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x06 (Following error actual value)) | UINT32 | RO | 0x6110:06, 32 |
Index 1A87 FB TxPDO-Map Touch probe status Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A87:0 | FB TxPDO-Map Touch probe status Ch.2 | PDO Mapping TxPDO 136 | UINT8 | RO | 0x0A (10dec)) |
1A87:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x01 (TP1 Enable)) | UINT32 | RO | 0x6101:01, 1 |
1A87:02 | SubIndex 002 | PDO Mapping entry no. 2 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x02 (TP1 Pos value stored)) | UINT32 | RO | 0x6101:02, 1 |
1A87:03 | SubIndex 003 | PDO Mapping entry no. 3 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x03 (TP1 Neg value stored)) | UINT32 | RO | 0x6101:03, 1 |
1A87:04 | SubIndex 004 | PDO Mapping entry no. 4 (4 bits align) | UINT32 | RO | 0x0000:00, 4 |
1A87:05 | SubIndex 005 | PDO Mapping entry no. 5 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x08 (TP1 Input)) | UINT32 | RO | 0x6101:08, 1 |
1A87:06 | SubIndex 006 | PDO Mapping entry no. 6 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x09 (TP2 Enable)) | UINT32 | RO | 0x6101:09, 1 |
1A87:07 | SubIndex 007 | PDO Mapping entry no. 7 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x0A (TP2 Pos value stored)) | UINT32 | RO | 0x6101:0A, 1 |
1A87:08 | SubIndex 008 | PDO Mapping entry no. 8 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x0B (TP2 Neg value stored)) | UINT32 | RO | 0x6101:0B, 1 |
1A87:09 | SubIndex 009 | PDO Mapping entry no. 9 (4 bits align) | UINT32 | RO | 0x0000:00, 4 |
1A87:0A | SubIndex 010 | PDO Mapping entry no. 10 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x10 (TP2 Input)) | UINT32 | RO | 0x6101:10, 1 |
Index 1A88 FB TxPDO-Map Touch probe 1 pos position Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A88:0 | FB TxPDO-Map Touch probe 1 pos position Ch.2 | PDO Mapping TxPDO 137 | UINT8 | RO | 0x01 (1dec)) |
1A88:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x11 (TP1 Pos position)) | UINT32 | RO | 0x6101:11, 32 |
Index 1A89 FB TxPDO-Map Touch probe 1 neg position Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A89:0 | FB TxPDO-Map Touch probe 1 neg position Ch.2 | PDO Mapping TxPDO 138 | UINT8 | RO | 0x01 (1dec)) |
1A89:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x12 (TP1 Neg position)) | UINT32 | RO | 0x6101:12, 32 |
Index 1A8A FB TxPDO-Map Touch probe 2 pos position Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A8A:0 | FB TxPDO-Map Touch probe 2 pos position Ch.2 | PDO Mapping TxPDO 139 | UINT8 | RO | 0x01 (1dec)) |
1A8A:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x13 (TP2 Pos position)) | UINT32 | RO | 0x6101:13, 32 |
Index 1A8B FB TxPDO-Map Touch probe 2 neg position Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A8B:0 | FB TxPDO-Map Touch probe 2 neg position Ch.2 | PDO Mapping TxPDO 140 | UINT8 | RO | 0x01 (1dec)) |
1A8B:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x14 (TP2 Neg position)) | UINT32 | RO | 0x6101:14, 32 |
Index 1A8D DRV TxPDO-Map Info data 3 Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A8D:0 | DRV TxPDO-Map Info data 3 Ch.2 | PDO Mapping TxPDO 142 | UINT8 | RW | 0x01 (1dec)) |
1A8D:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x14 (Info data 3)) | UINT32 | RW | 0x6110:14, 16 |
1A8D:02 | SubIndex 002 | PDO Mapping entry no. 2 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:03 | SubIndex 003 | PDO Mapping entry no. 3 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:04 | SubIndex 004 | PDO Mapping entry no. 4 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:05 | SubIndex 005 | PDO Mapping entry no. 5 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:06 | SubIndex 006 | PDO Mapping entry no. 6 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:07 | SubIndex 007 | PDO Mapping entry no. 7 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:08 | SubIndex 008 | PDO Mapping entry no. 8 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:09 | SubIndex 009 | PDO Mapping entry no. 9 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:0A | SubIndex 010 | PDO Mapping entry no. 10 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:0B | SubIndex 011 | PDO Mapping entry no. 11 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:0C | SubIndex 012 | PDO Mapping entry no. 12 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:0D | SubIndex 013 | PDO Mapping entry no. 13 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:0E | SubIndex 014 | PDO Mapping entry no. 14 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:0F | SubIndex 015 | PDO Mapping entry no. 15 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
1A8D:10 | SubIndex 016 | PDO Mapping entry no. 16 (0 bits align) | UINT32 | RW | 0x0000:00, 0 |
Index 1A8E DRV TxPDO-Map Modes of operation display Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A8E:0 | DRV TxPDO-Map Modes of operation display Ch.2 | PDO Mapping TxPDO 143 | UINT8 | RO | 0x01 (1dec)) |
1A8E:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x03 (Modes of operation display)) | UINT32 | RO | 0x6110:03, 8 |
Index 1A8F DRV TxPDO-Map Torque limitation status Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A8F:0 | DRV TxPDO-Map Torque limitation status Ch.2 | PDO Mapping TxPDO 144 | UINT8 | RO | 0x01 (1dec)) |
1A8F:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6110 (DRV Inputs Ch.2), entry 0x15 (Torque limitation status)) | UINT32 | RO | 0x6110:15, 8 |
Index 1A90 DI TxPDO-Map Inputs Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A90:0 | DI TxPDO-Map Inputs Ch.2 | PDO Mapping TxPDO 145 | UINT8 | RO | 0x07 (7dec)) |
1A90:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6120 (DI Inputs Ch.2), entry 0x01 (Input 1)) | UINT32 | RO | 0x6120:01, 1 |
1A90:02 | SubIndex 002 | PDO Mapping entry no. 2 (object 0x6120 (DI Inputs Ch.2), entry 0x02 (Input 2)) | UINT32 | RO | 0x6120:02, 1 |
1A90:03 | SubIndex 003 | PDO Mapping entry no. 3 (2 bits align) | UINT32 | RO | 0x0000:00, 2 |
1A90:04 | SubIndex 004 | PDO Mapping entry no. 4 (object 0x6120 (DI Inputs Ch.2), entry 0x05 (Encoder A)) | UINT32 | RO | 0x6120:05, 1 |
1A90:05 | SubIndex 005 | PDO Mapping entry no. 5 (object 0x6120 (DI Inputs Ch.2), entry 0x06 (Encoder B)) | UINT32 | RO | 0x6120:06, 1 |
1A90:06 | SubIndex 006 | PDO Mapping entry no. 6 (object 0x6120 (DI Inputs Ch.2), entry 0x07 (Encoder C)) | UINT32 | RO | 0x6120:07, 1 |
1A90:07 | SubIndex 007 | PDO Mapping entry no. 7 (9 bits align) | UINT32 | RO | 0x0000:00, 9 |
Index 1A91 FB TxPDO-Map Touch probe 1 pos timestamp Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A91:0 | FB TxPDO-Map Touch probe 1 pos timestamp Ch.2 | PDO Mapping TxPDO 146 | UINT8 | RO | 0x01 (1dec)) |
1A91:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x15 (TP1 Pos timestamp)) | UINT32 | RO | 0x6101:15, 32 |
Index 1A92 FB TxPDO-Map Touch probe 1 neg timestamp Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A92:0 | FB TxPDO-Map Touch probe 1 neg timestamp Ch.2 | PDO Mapping TxPDO 147 | UINT8 | RO | 0x01 (1dec)) |
1A92:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x16 (TP1 Neg timestamp)) | UINT32 | RO | 0x6101:16, 32 |
Index 1A93 FB TxPDO-Map Touch probe 2 pos timestamp Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A93:0 | FB TxPDO-Map Touch probe 2 pos timestamp Ch.2 | PDO Mapping TxPDO 148 | UINT8 | RO | 0x01 (1dec)) |
1A93:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x17 (TP2 Pos timestamp)) | UINT32 | RO | 0x6101:17, 32 |
Index 1A94 FB TxPDO-Map Touch probe 2 neg timestamp Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A94:0 | FB TxPDO-Map Touch probe 2 neg timestamp Ch.2 | PDO Mapping TxPDO 149 | UINT8 | RO | 0x01 (1dec)) |
1A94:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6101 (FB Touch probe inputs Ch.2), entry 0x18 (TP2 Neg timestamp)) | UINT32 | RO | 0x6101:18, 32 |
Index 1A95 FB TxPDO-Map Secondary Position Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A95:0 | FB TxPDO-Map Secondary Position Ch.2 | PDO Mapping TxPDO 150 | UINT8 | RO | 0x01 (1dec)) |
1A95:01 | SubIndex 001 | PDO Mapping entry no. 1 (object 0x6100 (FB Inputs Ch.2), entry 0x15 (Secondary position)) | UINT32 | RO | 0x6100:15, 32 |
Index 1AE0 DMC TxPDO-Map Inputs Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1AE0:0 | DMC TxPDO-Map Inputs Ch.2 | PDO Mapping TxPDO 225 | UINT8 | RO | 0x26 (38dec)) |
1AE0:01 | SubIndex 001 | PDO Mapping entry no. 1 (1 bits align) | UINT32 | RO | 0x0000:00, 1 |
1AE0:02 | SubIndex 002 | PDO Mapping entry no. 2 (object 0x6160 (DMC Inputs Ch.2), entry 0x02 (DMC__FeedbackStatus__Latch extern valid)) | UINT32 | RO | 0x6160:02, 1 |
1AE0:03 | SubIndex 003 | PDO Mapping entry no. 3 (object 0x6160 (DMC Inputs Ch.2), entry 0x03 (DMC__FeedbackStatus__Set counter done)) | UINT32 | RO | 0x6160:03, 1 |
1AE0:04 | SubIndex 004 | PDO Mapping entry no. 4 (9 bits align) | UINT32 | RO | 0x0000:00, 9 |
1AE0:05 | SubIndex 005 | PDO Mapping entry no. 5 (object 0x6160 (DMC Inputs Ch.2), entry 0x0D (DMC__FeedbackStatus__Status of extern latch)) | UINT32 | RO | 0x6160:0D, 1 |
1AE0:06 | SubIndex 006 | PDO Mapping entry no. 6 (3 bits align) | UINT32 | RO | 0x0000:00, 3 |
1AE0:07 | SubIndex 007 | PDO Mapping entry no. 7 (object 0x6160 (DMC Inputs Ch.2), entry 0x11 (DMC__DriveStatus__Ready to enable)) | UINT32 | RO | 0x6160:11, 1 |
1AE0:08 | SubIndex 008 | PDO Mapping entry no. 8 (object 0x6160 (DMC Inputs Ch.2), entry 0x12 (DMC__DriveStatus__Ready)) | UINT32 | RO | 0x6160:12, 1 |
1AE0:09 | SubIndex 009 | PDO Mapping entry no. 9 (object 0x6160 (DMC Inputs Ch.2), entry 0x13 (DMC__DriveStatus__Warning)) | UINT32 | RO | 0x6160:13, 1 |
1AE0:0A | SubIndex 010 | PDO Mapping entry no. 10 (object 0x6160 (DMC Inputs Ch.2), entry 0x14 (DMC__DriveStatus__Error)) | UINT32 | RO | 0x6160:14, 1 |
1AE0:0B | SubIndex 011 | PDO Mapping entry no. 11 (object 0x6160 (DMC Inputs Ch.2), entry 0x15 (DMC__DriveStatus__Moving positive)) | UINT32 | RO | 0x6160:15, 1 |
1AE0:0C | SubIndex 012 | PDO Mapping entry no. 12 (object 0x6160 (DMC Inputs Ch.2), entry 0x16 (DMC__DriveStatus__Moving negative)) | UINT32 | RO | 0x6160:16, 1 |
1AE0:0D | SubIndex 013 | PDO Mapping entry no. 13 (5 bits align) | UINT32 | RO | 0x0000:00, 5 |
1AE0:0E | SubIndex 014 | PDO Mapping entry no. 14 (object 0x6160 (DMC Inputs Ch.2), entry 0x1C (DMC__DriveStatus__Digital input 1)) | UINT32 | RO | 0x6160:1C, 1 |
1AE0:0F | SubIndex 015 | PDO Mapping entry no. 15 (object 0x6160 (DMC Inputs Ch.2), entry 0x1D (DMC__DriveStatus__Digital input 2)) | UINT32 | RO | 0x6160:1D, 1 |
1AE0:10 | SubIndex 016 | PDO Mapping entry no. 16 (3 bits align) | UINT32 | RO | 0x0000:00, 3 |
1AE0:11 | SubIndex 017 | PDO Mapping entry no. 17 (object 0x6160 (DMC Inputs Ch.2), entry 0x21 (DMC__PositioningStatus__Busy)) | UINT32 | RO | 0x6160:21, 1 |
1AE0:12 | SubIndex 018 | PDO Mapping entry no. 18 (object 0x6160 (DMC Inputs Ch.2), entry 0x22 (DMC__PositioningStatus__In-Target)) | UINT32 | RO | 0x6160:22, 1 |
1AE0:13 | SubIndex 019 | PDO Mapping entry no. 19 (object 0x6160 (DMC Inputs Ch.2), entry 0x23 (DMC__PositioningStatus__Warning)) | UINT32 | RO | 0x6160:23, 1 |
1AE0:14 | SubIndex 020 | PDO Mapping entry no. 20 (object 0x6160 (DMC Inputs Ch.2), entry 0x24 (DMC__PositioningStatus__Error)) | UINT32 | RO | 0x6160:24, 1 |
1AE0:15 | SubIndex 021 | PDO Mapping entry no. 21 (object 0x6160 (DMC Inputs Ch.2), entry 0x25 (DMC__PositioningStatus__Calibrated)) | UINT32 | RO | 0x6160:25, 1 |
1AE0:16 | SubIndex 022 | PDO Mapping entry no. 22 (object 0x6160 (DMC Inputs Ch.2), entry 0x26 (DMC__PositioningStatus__Accelerate)) | UINT32 | RO | 0x6160:26, 1 |
1AE0:17 | SubIndex 023 | PDO Mapping entry no. 23 (object 0x6160 (DMC Inputs Ch.2), entry 0x27 (DMC__PositioningStatus__Decelerate)) | UINT32 | RO | 0x6160:27, 1 |
1AE0:18 | SubIndex 024 | PDO Mapping entry no. 24 (object 0x6160 (DMC Inputs Ch.2), entry 0x28 (DMC__PositioningStatus__Ready to execute)) | UINT32 | RO | 0x6160:28, 1 |
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1AE0:19 | SubIndex 025 | PDO Mapping entry no. 25 (8 bits align) | UINT32 | RO | 0x0000:00, 8 |
1AE0:1A | SubIndex 026 | PDO Mapping entry no. 26 (object 0x6160 (DMC Inputs Ch.2), entry 0x31 (DMC__Set position)) | UINT32 | RO | 0x6160:31, 64 |
1AE0:1B | SubIndex 027 | PDO Mapping entry no. 27 (object 0x6160 (DMC Inputs Ch.2), entry 0x32 (DMC__Set velocity)) | UINT32 | RO | 0x6160:32, 16 |
1AE0:1C | SubIndex 028 | PDO Mapping entry no. 28 (object 0x6160 (DMC Inputs Ch.2), entry 0x33 (DMC__Actual drive time)) | UINT32 | RO | 0x6160:33, 32 |
1AE0:1D | SubIndex 029 | PDO Mapping entry no. 29 (object 0x6160 (DMC Inputs Ch.2), entry 0x34 (DMC__Actual position lag)) | UINT32 | RO | 0x6160:34, 64 |
1AE0:1E | SubIndex 030 | PDO Mapping entry no. 30 (object 0x6160 (DMC Inputs Ch.2), entry 0x35 (DMC__Actual velocity)) | UINT32 | RO | 0x6160:35, 16 |
1AE0:1F | SubIndex 031 | PDO Mapping entry no. 31 (object 0x6160 (DMC Inputs Ch.2), entry 0x36 (DMC__Actual position)) | UINT32 | RO | 0x6160:36, 64 |
1AE0:20 | SubIndex 032 | PDO Mapping entry no. 32 (object 0x6160 (DMC Inputs Ch.2), entry 0x37 (DMC__Error id)) | UINT32 | RO | 0x6160:37, 32 |
1AE0:21 | SubIndex 033 | PDO Mapping entry no. 33 (object 0x6160 (DMC Inputs Ch.2), entry 0x38 (DMC__Input cycle counter)) | UINT32 | RO | 0x6160:38, 8 |
1AE0:22 | SubIndex 034 | PDO Mapping entry no. 34 (object 0x6160 (DMC Inputs Ch.2), entry 0x39 (DMC__Channel id)) | UINT32 | RO | 0x6160:39, 8 |
1AE0:23 | SubIndex 035 | PDO Mapping entry no. 35 (object 0x6160 (DMC Inputs Ch.2), entry 0x3A (DMC__Latch value)) | UINT32 | RO | 0x6160:3A, 64 |
1AE0:24 | SubIndex 036 | PDO Mapping entry no. 36 (object 0x6160 (DMC Inputs Ch.2), entry 0x3B (DMC__Cyclic info data 1)) | UINT32 | RO | 0x6160:3B, 16 |
1AE0:25 | SubIndex 037 | PDO Mapping entry no. 37 (object 0x6160 (DMC Inputs Ch.2), entry 0x3C (DMC__Cyclic info data 2)) | UINT32 | RO | 0x6160:3C, 16 |
1AE0:26 | SubIndex 038 | PDO Mapping entry no. 38 (64 bits align) | UINT32 | RO | 0x0000:00, 64 |
Index 1AE1 DMC TxPDO-Map Inputs 32 Bit Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1AE1:0 | DMC TxPDO-Map Inputs 32 Bit Ch.2 | PDO Mapping TxPDO 226 | UINT8 | RO | 0x2A (42dec)) |
1AE1:01 | SubIndex 001 | PDO Mapping entry no. 1 (1 bits align) | UINT32 | RO | 0x0000:00, 1 |
1AE1:02 | SubIndex 002 | PDO Mapping entry no. 2 (object 0x6160 (DMC Inputs Ch.2), entry 0x02 (DMC__FeedbackStatus__Latch extern valid)) | UINT32 | RO | 0x6160:02, 1 |
1AE1:03 | SubIndex 003 | PDO Mapping entry no. 3 (object 0x6160 (DMC Inputs Ch.2), entry 0x03 (DMC__FeedbackStatus__Set counter done)) | UINT32 | RO | 0x6160:03, 1 |
1AE1:04 | SubIndex 004 | PDO Mapping entry no. 4 (9 bits align) | UINT32 | RO | 0x0000:00, 9 |
1AE1:05 | SubIndex 005 | PDO Mapping entry no. 5 (object 0x6160 (DMC Inputs Ch.2), entry 0x0D (DMC__FeedbackStatus__Status of extern latch)) | UINT32 | RO | 0x6160:0D, 1 |
1AE1:06 | SubIndex 006 | PDO Mapping entry no. 6 (3 bits align) | UINT32 | RO | 0x0000:00, 3 |
1AE1:07 | SubIndex 007 | PDO Mapping entry no. 7 (object 0x6160 (DMC Inputs Ch.2), entry 0x11 (DMC__DriveStatus__Ready to enable)) | UINT32 | RO | 0x6160:11, 1 |
1AE1:08 | SubIndex 008 | PDO Mapping entry no. 8 (object 0x6160 (DMC Inputs Ch.2), entry 0x12 (DMC__DriveStatus__Ready)) | UINT32 | RO | 0x6160:12, 1 |
1AE1:09 | SubIndex 009 | PDO Mapping entry no. 9 (object 0x6160 (DMC Inputs Ch.2), entry 0x13 (DMC__DriveStatus__Warning)) | UINT32 | RO | 0x6160:13, 1 |
1AE1:0A | SubIndex 010 | PDO Mapping entry no. 10 (object 0x6160 (DMC Inputs Ch.2), entry 0x14 (DMC__DriveStatus__Error)) | UINT32 | RO | 0x6160:14, 1 |
1AE1:0B | SubIndex 011 | PDO Mapping entry no. 11 (object 0x6160 (DMC Inputs Ch.2), entry 0x15 (DMC__DriveStatus__Moving positive)) | UINT32 | RO | 0x6160:15, 1 |
1AE1:0C | SubIndex 012 | PDO Mapping entry no. 12 (object 0x6160 (DMC Inputs Ch.2), entry 0x16 (DMC__DriveStatus__Moving negative)) | UINT32 | RO | 0x6160:16, 1 |
1AE1:0D | SubIndex 013 | PDO Mapping entry no. 13 (5 bits align) | UINT32 | RO | 0x0000:00, 5 |
1AE1:0E | SubIndex 014 | PDO Mapping entry no. 14 (object 0x6160 (DMC Inputs Ch.2), entry 0x1C (DMC__DriveStatus__Digital input 1)) | UINT32 | RO | 0x6160:1C, 1 |
1AE1:0F | SubIndex 015 | PDO Mapping entry no. 15 (object 0x6160 (DMC Inputs Ch.2), entry 0x1D (DMC__DriveStatus__Digital input 2)) | UINT32 | RO | 0x6160:1D, 1 |
1AE1:10 | SubIndex 016 | PDO Mapping entry no. 16 (3 bits align) | UINT32 | RO | 0x0000:00, 3 |
1AE1:11 | SubIndex 017 | PDO Mapping entry no. 17 (object 0x6160 (DMC Inputs Ch.2), entry 0x21 (DMC__PositioningStatus__Busy)) | UINT32 | RO | 0x6160:21, 1 |
1AE1:12 | SubIndex 018 | PDO Mapping entry no. 18 (object 0x6160 (DMC Inputs Ch.2), entry 0x22 (DMC__PositioningStatus__In-Target)) | UINT32 | RO | 0x6160:22, 1 |
1AE1:13 | SubIndex 019 | PDO Mapping entry no. 19 (object 0x6160 (DMC Inputs Ch.2), entry 0x23 (DMC__PositioningStatus__Warning)) | UINT32 | RO | 0x6160:23, 1 |
1AE1:14 | SubIndex 020 | PDO Mapping entry no. 20 (object 0x6160 (DMC Inputs Ch.2), entry 0x24 (DMC__PositioningStatus__Error)) | UINT32 | RO | 0x6160:24, 1 |
1AE1:15 | SubIndex 021 | PDO Mapping entry no. 21 (object 0x6160 (DMC Inputs Ch.2), entry 0x25 (DMC__PositioningStatus__Calibrated)) | UINT32 | RO | 0x6160:25, 1 |
1AE1:16 | SubIndex 022 | PDO Mapping entry no. 22 (object 0x6160 (DMC Inputs Ch.2), entry 0x26 (DMC__PositioningStatus__Accelerate)) | UINT32 | RO | 0x6160:26, 1 |
1AE1:17 | SubIndex 023 | PDO Mapping entry no. 23 (object 0x6160 (DMC Inputs Ch.2), entry 0x27 (DMC__PositioningStatus__Decelerate)) | UINT32 | RO | 0x6160:27, 1 |
1AE1:18 | SubIndex 024 | PDO Mapping entry no. 24 (object 0x6160 (DMC Inputs Ch.2), entry 0x28 (DMC__PositioningStatus__Ready to execute)) | UINT32 | RO | 0x6160:28, 1 |
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1AE1:19 | SubIndex 025 | PDO Mapping entry no. 25 (8 bits align) | UINT32 | RO | 0x0000:00, 8 |
1AE1:1A | SubIndex 026 | PDO Mapping entry no. 26 (object 0x6160 (DMC Inputs Ch.2), entry 0x31 (DMC__Set position)) | UINT32 | RO | 0x6160:31, 32 |
1AE1:1B | SubIndex 027 | PDO Mapping entry no. 27 (32 bits align) | UINT32 | RO | 0x0000:00, 32 |
1AE1:1C | SubIndex 028 | PDO Mapping entry no. 28 (object 0x6160 (DMC Inputs Ch.2), entry 0x32 (DMC__Set velocity)) | UINT32 | RO | 0x6160:32, 16 |
1AE1:1D | SubIndex 029 | PDO Mapping entry no. 29 (object 0x6160 (DMC Inputs Ch.2), entry 0x33 (DMC__Actual drive time)) | UINT32 | RO | 0x6160:33, 32 |
1AE1:1E | SubIndex 030 | PDO Mapping entry no. 30 (object 0x6160 (DMC Inputs Ch.2), entry 0x34 (DMC__Actual position lag)) | UINT32 | RO | 0x6160:34, 32 |
1AE1:1F | SubIndex 031 | PDO Mapping entry no. 31 (32 bits align) | UINT32 | RO | 0x0000:00, 32 |
1AE1:20 | SubIndex 032 | PDO Mapping entry no. 32 (object 0x6160 (DMC Inputs Ch.2), entry 0x35 (DMC__Actual velocity)) | UINT32 | RO | 0x6160:35, 16 |
1AE1:21 | SubIndex 033 | PDO Mapping entry no. 33 (object 0x6160 (DMC Inputs Ch.2), entry 0x36 (DMC__Actual position)) | UINT32 | RO | 0x6160:36, 32 |
1AE1:22 | SubIndex 034 | PDO Mapping entry no. 34 (32 bits align) | UINT32 | RO | 0x0000:00, 32 |
1AE1:23 | SubIndex 035 | PDO Mapping entry no. 35 (object 0x6160 (DMC Inputs Ch.2), entry 0x37 (DMC__Error id)) | UINT32 | RO | 0x6160:37, 32 |
1AE1:24 | SubIndex 036 | PDO Mapping entry no. 36 (object 0x6160 (DMC Inputs Ch.2), entry 0x38 (DMC__Input cycle counter)) | UINT32 | RO | 0x6160:38, 8 |
1AE1:25 | SubIndex 037 | PDO Mapping entry no. 37 (object 0x6160 (DMC Inputs Ch.2), entry 0x39 (DMC__Channel id)) | UINT32 | RO | 0x6160:39, 8 |
1AE1:26 | SubIndex 038 | PDO Mapping entry no. 38 (object 0x6160 (DMC Inputs Ch.2), entry 0x3A (DMC__Latch value)) | UINT32 | RO | 0x6160:3A, 32 |
1AE1:27 | SubIndex 039 | PDO Mapping entry no. 39 (32 bits align) | UINT32 | RO | 0x0000:00, 32 |
1AE1:28 | SubIndex 040 | PDO Mapping entry no. 40 (object 0x6160 (DMC Inputs Ch.2), entry 0x3B (DMC__Cyclic info data 1)) | UINT32 | RO | 0x6160:3B, 16 |
1AE1:29 | SubIndex 041 | PDO Mapping entry no. 41 (object 0x6160 (DMC Inputs Ch.2), entry 0x3C (DMC__Cyclic info data 2)) | UINT32 | RO | 0x6160:3C, 16 |
1AE1:2A | SubIndex 042 | PDO Mapping entry no. 42 (64 bits align) | UINT32 | RO | 0x0000:00, 64 |
Index 1C00 Sync manager type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C00:0 |
Sync manager type |
Using the Sync Managers |
UINT8 |
RO |
0x04 (4dec) |
|
1C00:01 |
SubIndex 001 |
Sync Manager Type Channel 1: Mailbox Write |
UINT8 |
RO |
0x01 (1dec) |
|
1C00:02 |
SubIndex 002 |
Sync Manager Type Channel 2: Mailbox Read |
UINT8 |
RO |
0x02 (2dec) |
|
1C00:03 |
SubIndex 003 |
Sync Manager Type Channel 3: Process Data Write (Outputs) |
UINT8 |
RO |
0x03 (3dec) |
|
1C00:04 |
SubIndex 004 |
Sync Manager Type Channel 4: Process Data Read (Inputs) |
UINT8 |
RO |
0x04 (4dec) |
Index 1C12 RxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C12:0 |
RxPDO assign |
PDO Assign Outputs |
UINT8 |
RW |
0x04 (4dec) |
|
1C12:01 |
SubIndex 001 |
1st assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x1600 (5632dec) |
|
1C12:02 |
SubIndex 002 |
2nd assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x1606 (5638dec) |
|
1C12:03 |
SubIndex 003 |
3rd assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x1680 (5760dec) |
|
1C12:04 |
SubIndex 004 |
4th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x1686 (5766dec) |
|
1C12:05 |
SubIndex 005 |
5th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:06 |
SubIndex 006 |
6th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:07 |
SubIndex 007 |
7th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:08 |
SubIndex 008 |
8th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:09 |
SubIndex 009 |
9th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0A |
SubIndex 010 |
10th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0B |
SubIndex 011 |
11th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0C |
SubIndex 012 |
12th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0D |
SubIndex 013 |
13th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0E |
SubIndex 014 |
14th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0F |
SubIndex 015 |
15th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:10 |
SubIndex 016 |
16th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:11 |
SubIndex 017 |
17th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:12 |
SubIndex 018 |
18th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:13 |
SubIndex 019 |
19th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:14 |
SubIndex 020 |
20th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:15 |
SubIndex 021 |
21st assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:16 |
SubIndex 022 |
22nd assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:17 |
SubIndex 023 |
23rd assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:18 |
SubIndex 024 |
24th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:19 |
SubIndex 025 |
25th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1A |
SubIndex 026 |
26th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1B |
SubIndex 027 |
27th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1C |
SubIndex 028 |
28th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1D |
SubIndex 029 |
29th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1E |
SubIndex 030 |
30th assigned RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
Index 1C13 TxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C13:0 |
TxPDO assign |
PDO Assign Inputs |
UINT8 |
RW |
0x06 (6dec) |
|
1C13:01 |
SubIndex 001 |
1st assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A00 (6656dec) |
|
1C13:02 |
SubIndex 002 |
2nd assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A01 (6657dec) |
|
1C13:03 |
SubIndex 003 |
3rd assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A06 (6662dec) |
|
1C13:04 |
SubIndex 004 |
4th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A80 (6784dec) |
|
1C13:05 |
SubIndex 005 |
5th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A81 (6785dec) |
|
1C13:06 |
SubIndex 006 |
6th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A86 (6790dec) |
|
1C13:07 |
SubIndex 007 |
7th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:08 |
SubIndex 008 |
8th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:09 |
SubIndex 009 |
9th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0A |
SubIndex 010 |
10th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0B |
SubIndex 011 |
11th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0C |
SubIndex 012 |
12th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0D |
SubIndex 013 |
13th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0E |
SubIndex 014 |
14th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0F |
SubIndex 015 |
15th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:10 |
SubIndex 016 |
16th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:11 |
SubIndex 017 |
17th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:12 |
SubIndex 018 |
18th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:13 |
SubIndex 019 |
19th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:14 |
SubIndex 020 |
20th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:15 |
SubIndex 021 |
21st assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:16 |
SubIndex 022 |
22nd assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:17 |
SubIndex 023 |
23rd assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:18 |
SubIndex 024 |
24th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:19 |
SubIndex 025 |
25th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1A |
SubIndex 026 |
26th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1B |
SubIndex 027 |
27th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1C |
SubIndex 028 |
28th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1D |
SubIndex 029 |
29th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C13:1E |
SubIndex 030 |
30th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1F |
SubIndex 031 |
31st assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:20 |
SubIndex 032 |
32nd assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:21 |
SubIndex 033 |
33rd assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:22 |
SubIndex 034 |
34th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:23 |
SubIndex 035 |
35th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:24 |
SubIndex 036 |
36th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:25 |
SubIndex 037 |
37th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:26 |
SubIndex 038 |
38th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:27 |
SubIndex 039 |
39th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:28 |
SubIndex 040 |
40th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:29 |
SubIndex 041 |
41st assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:2A |
SubIndex 042 |
42nd assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:2B |
SubIndex 043 |
43rd assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:2C |
SubIndex 044 |
44th assigned TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
Index 1C32 SM output parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C32:0 |
SM output parameter |
Synchronization parameters for the outputs |
UINT8 |
RO |
0x20 (32dec) |
|
1C32:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0003 (3dec) |
|
1C32:02 |
Cycle time |
Cycle time (in ns):
|
UINT32 |
RW |
0x000F4240 (1000000dec) |
|
1C32:03 |
Shift time |
Time between SYNC0 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C32:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RO |
0x0812 (2066dec) |
|
1C32:05 |
Minimum cycle time |
Minimum cycle time (in ns) |
UINT32 |
RO |
0x0001E848 (125000dec) |
|
1C32:06 |
Calc and copy time |
Minimum time between SYNC0 and SYNC1 event (in ns, DC mode only) |
UINT32 |
RO |
0x00007530 (30000dec) |
|
1C32:07 |
Minimum delay time |
|
UINT32 |
RO |
0x00007A12 (31250dec) |
|
1C32:08 |
Get Cycle Time |
|
UINT16 |
RW |
0x0000 (0dec) |
|
1C32:09 |
Maximum delay time |
Time between SYNC1 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RO |
0x00007A12 (31250dec) |
|
1C32:0A |
Sync0 Cycle Time |
|
UINT32 |
RO |
0x0000F424 (62500dec) |
|
1C32:0B |
SM event missed counter |
Number of missed SM events in OPERATIONAL (DC Mode only) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:0C |
Cycle exceeded counter |
Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:0D |
Shift too short counter |
Number of intervals between SYNC0 and SYNC1 events that are too short (DC Mode only) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:20 |
Sync error |
The synchronization was not correct in the last cycle (outputs were output too late; DC Mode only) |
BOOLEAN |
RO |
0x00 (0dec) |
Index 1C33 SM input parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C33:0 |
SM input parameter |
Synchronization parameters for the inputs |
UINT8 |
RO |
0x20 (32dec) |
|
1C33:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0003 (3dec) |
|
1C33:02 |
Cycle time |
as 1C32:02 |
UINT32 |
RW |
0x000F4240 (1000000dec) |
|
1C33:03 |
Shift time |
Time between SYNC0 event and reading of the inputs (in ns, DC Mode only) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C33:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RO |
0x0012 (18dec) |
|
1C33:05 |
Minimum cycle time |
as 1C32:05 |
UINT32 |
RO |
0x0001E848 (125000dec) |
|
1C33:06 |
Calc and copy time |
Time between reading of the inputs and the inputs being available for the master (in ns, DC Mode only) |
UINT32 |
RO |
0x00007530 (30000dec) |
|
1C33:07 |
Minimum delay time |
|
UINT32 |
RO |
0x00007A12 (31250dec) |
|
1C33:08 |
Get Cycle Time |
as 1C32:08 |
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:09 |
Maximum delay time |
Time between SYNC1 event and reading of the inputs (in ns, DC Mode only) |
UINT32 |
RO |
0x00007A12 (31250dec) |
|
1C33:0A |
Sync0 Cycle Time |
|
UINT32 |
RO |
0x0000F424 (62500dec) |
|
1C33:0B |
SM event missed counter |
as 1C32:11 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:0C |
Cycle exceeded counter |
as 1C32:12 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:0D |
Shift too short counter |
as 1C32:13 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:20 |
Sync error |
as 1C32:32 |
BOOLEAN |
RO |
0x00 (0dec) |