Configuration data (0x80n0)

Index 80n0 IO Settings Ch. 1 - 4 (for 0 ≤ n ≤ 3)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

IO Settings

Max. Subindex

UINT8

RO

0x28 (40dec)

80n0:04

Device ID

The device ID is used for validating the IO-Link device.

UINT32

RW

0x00000000 (0dec)

80n0:05

VendorID

The Vendor ID is used for validating the vendor of the IO-Link device.

UINT32

RW

0x00000000 (0dec)

80n0:20

IO-Link Revision

ID of the specification version based on which the IO-Link device communicates.

Bit 0 - 3: MinorRev
Bit 4 - 7: MajorRev

UINT8

RW

0x00 (0dec)

80n0:21

Frame capability

The Frame Capability indicates certain functionalities of the IO-Link device (e.g. ISDU supported).

Bit 0: ISDU
Bit 1: Type1
Bit 7: PHY1

UINT8

RW

0x00 (0dec)

80n0:22

Min cycle time

The cycle time refers to the communication between the IO‑Link master and the IO‑Link device.

This value is transmitted in the IO‑Link format for Min Cycle Time.

Bit 6 and 7: time base
Bit 0 to 5: multiplier (see following table)

UINT8

RW

0x00 (0dec)

Time base

Time base meaning

Calculation

Min. Cycle Time

00bin

0.1 ms

multiplier x time base

0.0 - 6.3 ms

01bin

0.4 ms

6.4 ms + multiplier x time base

6.4 - 31.6 ms

10bin

1.6 ms

32.0 ms + multiplier x time base

32.0 - 132.8 ms

11bin

6.4 ms

134.4 ms + multiplier x time base

134.4 - 537.6 ms

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:23

Offset time

Reserved

UINT8

RW

0x00 (0dec)

80n0:24

Process data in length

These parameters are transmitted in the IO-Link format for “Process data in length”.

Bit 7: BYTE
indicates whether the value in LENGTH is interpreted

  • as bit length [bit not set] or
  • as byte length + 1 [bit set]

Bit 6: SIO
indicates whether the device supports the standard I/O mode [bit set]

Bit 0 to 4: LENGTH
Length of the process data

UINT8

RW

0x00 (0dec)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:25

Process data out length

These parameters are transmitted in the IO-Link format for “Process data out length”.

Bit 7: BYTE
indicates whether the value in LENGTH is interpreted

  • as bit length [bit not set] or
  • as byte length + 1 [bit set]

Bit 6: SIO
indicates whether the device supports the standard I/O mode [bit set]

Bit 0 to 4: LENGTH
Length of the process data

UINT8

RW

0x00 (0dec)

80n0:26

Compatible ID

reserved

UINT16

RW

0x0000 (0dec)

80n0:27

Reserved

reserved

UINT16

RW

0x0000 (0dec)

80n0:28

Master Control

Controls the IO-Link master port and defines the various operation modes of the IO-Link master.

Bits 0...3
0: IO-Link port inactive
1: IO-Link port as digital input port
2: IO-Link port as digital output port
3: IO-Link port in communication via the IO-Link protocol
4: IO-Link port in communication via the IO-Link protocol.
IO-Link state is ComStop (no cyclic communication, data is only exchanged when required).

Bits 4...15
2: DataStorage active
4: DataStorage upload inactive

UINT16

RW

0x0000 (0dec)

Index 80n8 IO Sync Settings Ch. 1 - 4 (for 0 ≤ n ≤ 3)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n8:0

IO Sync Settings

Max. Subindex

UINT8

RO

0x02 (2dec)

80n8:01

Ratio

UINT16

RW

0x0000 (0dec)

80n8:05

Offset

UINT16

RW

0x0000 (0dec)