Technical data

General

ED6224

Number of channels | Total

4

Internal communication protocol

EtherCAT

Communication interface

ED6224

Number of ports

4

Interface

IO-Link

Protocol

IO-Link V1.1

Transmission type

serial

Device type

master

Transmission rate

4.8 kbaud, 38.4 kbaud, 230.4 kbaud

Number of devices

4

Device supply | Voltage

24 V DC

Device supply | Current

500 mA

Cable length | Point-to-point

max. 20 m

XFC

ED6224

Distributed clocks

yes

Distributed clocks | Accuracy

< 1 µs

Distributed clocks | Scope

64 bit

Timestamp

no

Oversampling

no

Supply and electrical isolation

ED6224

Electronics | Supply voltage

via E-bus, via power contacts

E-bus | Current consumption

typ. 120 mA

Power contacts | Input voltage

24 V DC (-15 %/+20 %)

Power contacts | Current carrying capacity

max. 10 A

Power contacts | Current consumption

load-dependent

Power contacts | Output voltage

corresponds to Power contacts | Input voltage

Electrical isolation | Channel/channel

no

Electrical isolation | Channel/bus

functional, 707 V DC (type test)

Environmental conditions

ED6224

Operating temperature

-25…+60°C

Storage temperature

-40…+85°C

Relative humidity

95%, no condensation

Installation position

variable

Standards and approvals

ED6224

Vibration resistance

conforms to EN 60068-2-6

Shock resistance

conforms to EN 60068-2-27

EMC immunity

conforms to EN 61000-6-2

EMC emission

conforms to EN 61000-6-4

Markings*)

CE

Approvals*)

-

*) Real applicable approvals/markings, see name plate on the side (product labeling)

Housing data

ED-12-16pin

Weight

approx. 60 g

Protection rating

IP20

Material

polycarbonate

Dimensions | Width (single)

15 mm

Dimensions | Width (stacked)

12 mm

Dimensions | Height

100 mm

Dimensions | Depth

65 mm

Installation | Terminal/back wall

DIN rail, 35 mm (EN 60715)

Installation | Terminal/terminal

double slot and key connection

Pluggable wiring level

no

Connection mechanism

push-in

Connection cross-section | Solid wire

0.08…1.5 mm²

Connection cross-section | Stranded wire

0.25…1.5 mm²

Connection cross-section | With ferrule

0.14…0.75 mm²

Connection cross-section AWG | Solid wire

AWG28…16

Connection cross-section AWG | Stranded wire

AWG22…16

Connection cross-section AWG | With ferrule

AWG26…19

Stripping length

8…9 mm

Power contact | "+" (left)

yes

Power contact | "+" (right)

yes

Power contact | "-" (left)

yes

Power contact | "-" (right)

yes

Power contact | "⏚" (left)

no

Power contact | "⏚" (right)

no

Insertion lock for power contact "⏚"

yes