Technical properties

The ED5112 incremental encoder interface terminal enables connection of incremental encoders to the Bus Coupler or the PLC. In addition to the encoder inputs A, B, and the optional zero pulse C, up to two additional 24 V DC inputs are available (“latch” and “Gate”), which can be used for resetting, setting, locking and storing the counter value. If the incremental encoder has an alarm output, this can be connected to the “Digital input” Input (5 V DC).

Notice

Fast digital inputs – interference from interfering devices

Please note that the input wiring has very little filtering. It has been optimized for fast signal transmission from the input to the evaluation unit. In other words, rapid level changes/pulses in the µs range and/or high-frequency interference signals from devices (e.g. proportional valves, stepper motor or DC motor output stages) arrive at the evaluation unit almost unfiltered/unattenuated. These interferences can be incorrectly detected as a signal.

  • To suppress interference, an additional input filter can be parameterized.
  • Furthermore, EMC-compliant cabling and the use of separate power supply units for the terminal and the devices causing interference are recommended.