RS422 - wire break and short-circuit detection (open circuit)

In the “RS422 (diff. input)” modes it is possible to detect a wire break or short circuit at the individual encoder inputs.

Activation of error detection for each channel

Index (hex)

Name

Description

80n0:0B *

Error detection A

TRUE

Broken wire and short circuit detection for encoder input A enabled

FALSE

Broken wire and short circuit detection for encoder input A disabled

80n0:0C *

Error detection B

TRUE

Broken wire and short circuit detection for encoder input B enabled

FALSE

Broken wire and short circuit detection for encoder input B disabled

80n0:0D *

Error detection C

TRUE

Broken wire and short circuit detection for encoder input C enabled

FALSE

Broken wire and short circuit detection for encoder input C disabled

*) depending on the number of channels (n = 0 for channel 1 and n = 1 for channel 2)

Error detection using the example of a wire break or short circuit between inputs A and A̅.

Error diagnosis

Display

Description

LED Ch. 1 A

Green

A TRUE level is present

Red

An error (open circuit) was detected

0x60n0:07 „Open circuit“

TRUE

Aggregate error message for “Open circuit”
A wire break or short circuit has occurred at one of the encoder inputs

FALSE

There is no “Open circuit” error.

0x60n0:0F „TxPDO State“

TRUE

The position data are invalid.

FALSE

The position data are valid.

0xA0n0:01 „Error A“

TRUE

An “Open circuit” error (wire break or short circuit) has occurred at encoder input A.

FALSE

There is no “Open circuit” error.

Diag Message

Text ID: 0x831B

Wire break or short circuit track A (channel n)

RS422 - wire break and short-circuit detection (open circuit) 1:

Error bits not permanently set in case of wire break at an encoder input

If a wire break is only present at one encoder input (e.g. only track A), it may happen in individual cases that the differential voltage (VID) is above the limit range (VIDLow) due to the applied common mode voltage (VCM).
This means that the error is not clearly identified.

The corresponding error bits (“Open circuit” and “Error A”) are not permanently present!