General information on commissioning the ED407x/EL407x

The terminals support EtherCAT cycle times of up to 50 µs, but the following minimum cycle times are recommended for precise value output:
- ED4072/EL4072: >= 150 µs
- ED4074/EL4074: >= 250 µs
- ED4078/EL4078: >= 500 µs
If these values are not reached, it is not guaranteed that the analog value output will start in the corresponding output cycle. There may be a delay in output in the order of a few cycles. The fact that the internal analog value output can no longer follow the cycle can be seen from the incrementing of the local "SM Output" error counter CoE 0x1C32:0C.

Example EL4078:

General information on commissioning the ED407x/EL407x 2:Fig.27: EL4078 with 500 µs EtherCAT cycle time, output jitter according to theory ±0.5 cycle
General information on commissioning the ED407x/EL407x 3:Fig.28: EL4078 with 100 µs EtherCAT cycle time, output jitter > 1 ms

If such precise analog value output timing is required, the EL41xx or EL47xx series should be used.