Connection
| |
Risk of electric shock and damage of device! Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the bus terminals! |
Notice | |
Cable lengths > 30 m For cable lengths > 30 m, suitable overvoltage protection (Surge-Protection) must be provided (e g. EL9540-0010) if corresponding interference could affect the signal cable. |
Connection ED3362-0100
Terminal point | Description | |
|---|---|---|
Abbreviation | No. | |
n.c. | 1 | not connected |
Ch1 UBridge+ | 2 | Channel 1 Input bridge voltage+ |
Ch1 USense+ | 3 | Channel 1 Input reference voltage+ |
Ch1 UExc+ | 4 | Channel 1 Output sensor power supply+ |
Ch2 UExc+ | 5 | Channel 2 Output sensor power supply+ |
Ch2 USense+ | 6 | Channel 2 Input reference voltage+ |
Ch2 UBridge+ | 7 | Channel 2 Input bridge voltage+ |
n.c | 8 | not connected |
n.c. | 9 | not connected |
Ch1 UBridge- | 10 | Channel 1 Input bridge voltage- |
Ch1 USense- | 11 | Channel 1 Input reference voltage- |
Ch1 UExc- | 12 | Channel 1 Output sensor power supply- |
Ch2 UExc- | 13 | Channel 2 Output sensor power supply- |
Ch2 USense- | 14 | Channel 2 Input reference voltage- |
Ch2 UBridge- | 15 | Channel 2 Input bridge voltage- |
n.c | 16 | not connected |