Connection

WARNING

Risk of injury through electric shock and damage to the device!

Bring the bus terminal system into a safe, de-energized state before beginning to mount, disassemble, or wire the bus terminals!

Connection 1:
Fig.5: ED3362-0100

Notice

Cable lengths > 30 m

For cable lengths > 30 m, suitable overvoltage protection (surge protection) must be provided (e g. EL9540-0010) if corresponding interference could affect the signal cable.

ED3362-0100 connection

Terminal point

Description

Abbreviation

No.

n.c.

1

not connected

Ch1 UBridge+

2

Channel 1: Input bridge voltage+

Ch1 USense+

3

Channel 1: Input reference voltage+

Ch1 UExc+

4

Channel 1: Output sensor power supply+

Ch2 UExc+

5

Channel 2: Output sensor power supply+

Ch2 USense+

6

Channel 2: Input reference voltage+

Ch2 UBridge+

7

Channel 2: Input bridge voltage+

n.c

8

not connected

n.c.

9

not connected

Ch1 UBridge-

10

Channel 1: Input bridge voltage-

Ch1 USense-

11

Channel 1: Input reference voltage-

Ch1 UExc-

12

Channel 1: Output sensor power supply-

Ch2 UExc-

13

Channel 2: Output sensor power supply-

Ch2 USense-

14

Channel 2: Input reference voltage-

Ch2 UBridge-

15

Channel 2: Input bridge voltage-

n.c

16

not connected