Connection

WARNING

Risk of electric shock and damage of device!

Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the bus terminals!

Connection 1:Fig.5: ED3362-0100

Notice

Cable lengths > 30 m

For cable lengths > 30 m, suitable overvoltage protection (Surge-Protection) must be provided (e g. EL9540-0010) if corresponding interference could affect the signal cable.

Connection ED3362-0100

Terminal point

Description

Abbreviation

No.

n.c.

1

not connected

Ch1 UBridge+

2

Channel 1 Input bridge voltage+

Ch1 USense+

3

Channel 1 Input reference voltage+

Ch1 UExc+

4

Channel 1 Output sensor power supply+

Ch2 UExc+

5

Channel 2 Output sensor power supply+

Ch2 USense+

6

Channel 2 Input reference voltage+

Ch2 UBridge+

7

Channel 2 Input bridge voltage+

n.c

8

not connected

n.c.

9

not connected

Ch1 UBridge-

10

Channel 1 Input bridge voltage-

Ch1 USense-

11

Channel 1 Input reference voltage-

Ch1 UExc-

12

Channel 1 Output sensor power supply-

Ch2 UExc-

13

Channel 2 Output sensor power supply-

Ch2 USense-

14

Channel 2 Input reference voltage-

Ch2 UBridge-

15

Channel 2 Input bridge voltage-

n.c

16

not connected