Range Warning
The Range Warning functional unit monitors the measured value according to 2 limit values (min. and max.), counts overrange/underrange, and reports this as a warning (Warning bit in the status). There is no limitation of measured values.
In the default setting, the Range Warning limit values are set to the negative and positive nominal full scale value, e.g. in the "±10 V" measuring range to LowRangeWarning = -10.7 V and HighRangeWarning = +10.7 V, when the limit is exceeded, it is then output as an error in the PDO status and LED.
Index | Name |
|---|---|
0x80nD:2D | Low Range Warning |
0x80nD:2E | High Range Warning |
Notice | ||
![]() | Changing the interface or IntegerScaler If you modify interface 0x80nD:11 or IntegerScaler 0x80nD:12 (Extended/Legacy Range), the limit values will be reset to the default settings specified in the interface! | |
Result | |
|---|---|
PDO AI Status | Error bit |
0x90n0:1D | Underrange Warning Counter |
0x90n0:1E | Overrange Warning Counter |
Resetting to the default setting according to the interface is done by
- an interface change
- or setting to de-energized [(re-)power cycle]
- or the command x302n to index 0xFB00:01 (channel 1: n=0, channel 2: n=1, ...).
During execution, "Status" 255 "busy" is displayed in index 0xFB00:02, "0" means "successfully completed", - and the command x3001 “Reset all counters”

During command execution, "Status" 255 "busy" is displayed in index 0xFB00:02, "0" means "successfully completed".
The firmware responds to an unknown command with