Sensor power supply

The sensor power supply can be set between OFF, 5 V and 10 V in CoE object 0xF800:01 Sensor Supply.

Even with multi-channel devices, the sensor power supply can only be set once, internally the same power supply is used for generation. However, the supply for each channel is filtered separately.

If a different supply voltage is required for the strain gauge used or different supplies for different channels, this can be specified externally in the specified range and measured back via the USense of the respective channel.

Even if the internal supply voltage UExc is used, this must be fed back to USense, as there is no internal connection between UExc and USense.