Peak hold
This functional unit is a drag indicator function. It continuously monitors the measured value and saves extremes, which can be used to diagnose sensor overloads.
Index | Designation |
|---|---|
90n0:0C | Actual Positive Peak Hold |
90n0:0D | Actual Negative Peak Hold |
The reset is carried out by
- an interface change
- or de-energizing [(Re-)Power-Cycle]
- or 0->1 in the PDO "AI Control.Peak Hold Reset"
- or the command x301n to index FB00:01 (channel 1: n=0, channel 2: n=1, ...).
During execution, "Status" 255 "busy" is displayed in index FB00:02, "0" means "successfully completed" - and the command x3001 "Reset all counters"
Fig.25: CoE Index FB00, DEV CommandDuring command execution, "Status" 255 "busy" is displayed in index FB00:02, "0" means "successfully completed".
The firmware responds to an unknown command with
Fig.26: General parameter incompatibility reason, 0x06040043