1An0 | Mapping TxPDO

The following applies to the objects below:
n = 1 for SlotGroup 1, n = 3 for SlotGroup 2, n = 5 for SlotGroup 3, n = 7 for SlotGroup 4

Index 1An0 DI TxPDO-Map Inputs

Index (hex)

Name

Meaning

Data type

Flags

Default

1An0:0

DI TxPDO-Map Inputs

PDO mapping TxPDO (0xn0+1)

UINT8

RO

0x02 (2dec)

1An0:01

SubIndex 001

PDO mapping entry no. 1 (index 0x60n0 (DI Inputs), entry 0x01 (Input))

UINT32

RO

0x60n0:01, 1

1An0:02

SubIndex 002

PDO mapping entry no. 2 (15 bits align)

UINT32

RO

0x0000:00, 15

Index 1An0 ENC TxPDO-Map Inputs

Index (hex)

Name

Meaning

Data type

Flags

Default

1An0:0

ENC TxPDO-Map Inputs

PDO mapping TxPDO (0xn0+1)

UINT8

RO

0x04 (4dec)

1An0:01

SubIndex 001

PDO mapping entry no. 1 (8 bits align)

UINT32

RO

0x0000:00, 8

1An0:02

SubIndex 002

PDO mapping entry no. 2 (index 0x60n0 (ENC Inputs), entry 0x09 (Status of Input A))

UINT32

RO

0x60n0:09, 1

1An0:03

SubIndex 003

PDO mapping entry no. 3 (87 bits align)

UINT32

RO

0x0000:00, 87

1An0:04

SubIndex 004

PDO mapping entry no. 4 (index 0x60n0 (ENC Inputs), entry 0x13 (Frequency Value))

UINT32

RO

0x60n0:13, 32

Index 1An0 HWE TxPDO-Map Inputs

Index (hex)

Name

Meaning

Data type

Flags

Default

1An0:0

HWE TxPDO-Map Inputs

PDO mapping TxPDO (0xn0+1)

UINT8

RO

0x02 (2dec)

1An0:01

SubIndex 001

PDO mapping entry no. 1 (index 0x60n0 (HWE Inputs), entry 0x01 (Input))

UINT32

RO

0x60n0:01, 1

1An0:02

SubIndex 002

PDO mapping entry no. 2 (15 bits align)

UINT32

RO

0x0000:00, 15