16n0, 1700, 1701 | Mapping RxPDO

The following applies to the objects below:
n = 0 for SlotGroup 1, n = 2 for SlotGroup 2, n = 4 for SlotGroup 3, n = 6 for SlotGroup 4

Index 16n0 PWM RxPDO-Map Outputs (INT16)

Index (hex)

Name

Meaning

Data type

Flags

Default

16n0:0

PWM RxPDO-Map Outputs

PDO parameter RxPDO (0xn0+1)

UINT8

RO

0x02 (2dec)

16n0:01

SubIndex 001

PDO mapping entry no. 1 (index 0x70n0 (SlotGroupx (Outputx, Inputx) “PWM Outputs”), entry 0x11 (PWM Output))

UINT32

RO

0x70n0:11, 16

16n0:02

SubIndex 002

PDO mapping entry no. 2 (index 0x70n0 (SlotGroupx (Outputx, Inputx) “PWM Outputs”), entry 0x12 (PWM Period))

UINT32

RO

0x70n0:12, 16

Index 16n0 PWM RxPDO-Map Outputs (INT32)

Index (hex)

Name

Meaning

Data type

Flags

Default

16n0:0

PWM RxPDO-Map Outputs

PDO parameter RxPDO (0xn0+1)

UINT8

RO

0x03 (3dec)

16n0:01

SubIndex 001

PDO mapping entry no. 1 (index 0x70n0 (SlotGroupx (Outputx, Inputx) “PWM Outputs”), entry 0x11 (PWM Output))

UINT32

RO

0x70n0:11, 16

16n0:02

SubIndex 002

PDO mapping entry no. 2 (16 bits align)

UINT32

RO

0x0000:00, 16

16n0:02

SubIndex 002

PDO mapping entry no. 1 (index 0x70n0 (SlotGroupx (Outputx, Inputx) “PWM Outputs”), entry 0x13 (PWM Period 1 Hz))

UINT32

RO

0x70n0:13, 32

Index 16n0 PWM RxPDO-Map Extended Outputs (REAL32)

Index (hex)

Name

Meaning

Data type

Flags

Default

16n0:0

PWM RxPDO-Map Extended Outputs

PDO parameter RxPDO (0xn0+1)

UINT8

RO

0x02 (2dec)

16n0:01

SubIndex 001

PDO mapping entry no. 1 (index 0x70n1 (SlotGroupx (Outputx, Inputx) “PWM Outputs”), entry 0x12 (PWM Duty Cycle))

UINT32

RO

0x70n1:12, 32

16n0:02

SubIndex 002

PDO mapping entry no. 1 (index 0x70n1 (SlotGroupx (Outputx, Inputx) “PWM Outputs”), entry 0x13 (PWM Frequency))

UINT32

RO

0x70n1:13, 32

Index 1700 PWM RxPDO-Map Outputs Device

Index (hex)

Name

Meaning

Data type

Flags

Default

1700:0

PWM RxPDO-Map Outputs Device

PDO parameter RxPDO (0xn0+1)

UINT8

RO

0x03 (3dec)

1700:01

SubIndex 001

PDO mapping entry no. 1 (6 bits align)

UINT32

RO

0x0000:00, 6

1700:02

SubIndex 002

PDO mapping entry no. 2 (index 0xF716 (“PWM Outputs”)), entry 0x13 (PWM Reset))

UINT32

RO

0xF716:07, 1

1700:03

SubIndex 003

PDO mapping entry no. 3 (9 bits align)

UINT32

RO

0x0000:00, 9

Index 1701 PWM RxPDO-Map Output Cycle Counter

Index (hex)

Name

Meaning

Data type

Flags

Default

1701:0

PWM RxPDO-Map Output Cycle Counter

PDO parameter RxPDO (0xn0+1)

UINT8

RO

0x01 (1dec)

1701:01

SubIndex 001

PDO mapping entry no. 2 (index 0xF716 (“PWM Outputs”)), entry 0x11 (PWM Output Cycle Counter))

UINT32

RO

0xF716:11, 16