“ENC input (frequency)” | ModuleIdent 0x1809C8

This module provides a frequency measurement. This information can also be used for speed or rotary speed measurement.

The following limit values apply to the determination of the measured values:

Measured value output

Lower measured value limit

Upper measured value limit

“Frequency Value“

1 Hz

1 kHz

The frequency module provides the following features:

“ENC input (frequency)” | ModuleIdent 0x1809C8 1:Fig.31: Settings for the digital input for frequency measurement

Parameterizable input characteristics

The digital input can be interpreted as having a positive or ground switching characteristic.
This is defined under:
0x80n1:1D “Counter Mode” (n = 1 for ENC 1, n = 3 for ENC 2, n = 5 for ENC 3, n = 7 for ENC 4):

Measurement of frequency/rotary speed | Positive switching

0x80n0:1D „Counter Mode“

Positive Switching (PNP)

Signal voltage “0”

-3…+1.5 V DC

Signal voltage “1”

2.7…28 V DC

Measurement of frequency/rotary speed | Ground switching

0x80n0:1D „Counter Mode“

Ground Switching (NPN)

Signal voltage “0”

2.5…28 V DC

Signal voltage “1”

-3…+1 V DC

In this operation mode, an additional pull-up resistor is connected to V+.

“ENC input (frequency)” | ModuleIdent 0x1809C8 2:

Sensors with open collector output circuits

A sensor with an open collector output circuit corresponds to the “Input Type”: “Ground Switching (NPN)”.

  • In this context, the switching thresholds defined by the manufacturer must be observed to determine whether the input signal should be interpreted as “normally open” or “normally closed”.

Parameterizable frequency output (“Frequency value”)