Configuring PWM outputs | ModuleIdent 0x1009C8

The following section describes the parameterization of the PWM outputs.

Changing the duty cycle | “PWM Duty Cycle” process data value

PWM Duty Cycle

Duty Cycle in %

0.1

10%

0.5

50%

1

100%

Changing the output frequency | “PWM Frequency” process data value

Notice

Specifying invalid duty cycle and frequency values

If the specified duty cycle or frequency value is outside the valid output range, then

  • the specification is rejected,
  • a diagnostic message is output:
    0x461B “Slot group n: Invalid duty cycle written”,
    0x461A “Slot Group n Invalid frequency/period written”,
  • the maximum permissible value is output.

Output signal range

The following table shows the valid range of values for the output signal.

Output signal range

Pulse duration | TON

typ. > 320 ns

Pulse duration | TOFF

typ. > 320 ns

Output frequency

1 Hz…64 kHz