RS422/RS485 (N031)

The optional N031 interface provides an RS422 or RS485 interface (X300). The interface is executed on a 9-pin D-sub socket.

RS422/RS485 (N031) 1:Fig.7: RS485 interface X300.

The maximum baud rate on both channels is 115 kbit. The interface parameters are set via the operating system or from the PLC program.

RS422/485 interface, pin assignment.

PIN

Signal

Type

Description

2

TxD+

Data-Out +

Transmit 422

3

RxD+

Data-In +

Receive 422

5

GND

Ground

Ground

6

VCC

VCC

+5 V

7

TxD-

Data-Out -

Transmit 422

8

RxD-

Data-In -

Receive 422

For RS 485 pins 2 and 3 (data +) must be connected, and pins 7 and 8 (data -).

By default the interface is parameterized as follows on delivery:

Default setting, RS485 without echo with end point (terminated).

Function

Status

Echo on

off

Echo off

on

Auto send on

on

Always send on

off

Auto receive on

on

Always receive on

off

Term on

on

Term on

On

Other configurations for the RS485 interface

Other configurations for the RS485 interface can be ordered ex factory. The following options are available:

An RS485 interface cannot be configured retrospectively and must always be ordered ex factory as required.