Technical data
| CX8290 |
|---|---|
Dimensions (W x H x D) | 71 mm x 100 mm x 73 mm |
Weight | 220 g |
Technical data | CX8290 |
|---|---|
Processor | Arm® Cortex®-A53, 1.2 GHz |
Number of cores | 2 |
Flash memory | Slot for microSD card, card not included (requires at least a 16 GB microSD card) |
Main memory | 1 GB LPDDR4 RAM (not expandable) |
1-second UPS | integrated (1 MB on microSD card) |
Interfaces | 1 x RJ45 10/100/1000 Mbit/s, 1 x USB 3.0 |
Cooling | passive |
Bus interface | 2 x Ethernet RJ45 (switched, 10/100/1000 Mbit/s), optional PROFINET (TF627x), EtherNet/IP (TF628x), BACnet/IP (TF8020) |
Data transfer rates | 10/100/1000 Mbit/s |
Diagnostic LED | 1 x TC status, 1 x WD, 1 x Error |
Clock | internal, capacitor-buffered real-time clock for time and date (memory > 21 days) |
Operating system | Beckhoff RT Linux® |
Control software | TwinCAT 3 Runtime (XAR) from TwinCAT 3.1 Build 4026 |
Secure element | discrete TPM 2.0 chip |
Power supply | 24 VDC (-15%/+20%) |
Max. power consumption | 4 W |
Max. power consumption (with UPS charging) | 7.5 W |
Max. power consumption E-bus/K-bus | 10 W (5 V/max. 2 A) |
Approvals | CE, UL |
Technical data | CX8290 |
|---|---|
I/O connection | E-bus or K-bus, automatic recognition |
Power supply E-bus/K-bus | 2 A |
Power contacts current load | max. 10 A |
Process data on the K-bus | max. 2 kB In and 2 kB Out |
max. number of terminals (K-bus) | 64 (255 with K-bus extension) |
max. number of terminals (E-bus) | up to 65534 terminals. |
Technical data | CX8290 |
|---|---|
Ambient temperature during operation | -25 °C … +60 °C |
Ambient temperature during storage | -40 °C … +85 °C |
Relative humidity | 95% no condensation |
Vibration resistance | conforms to EN 60068-2-6 |
Shock resistance | conforms to EN 60068-2-27 |
EMC immunity | conforms to EN 61000-6-2 |
EMC emission | conforms to EN 61000-6-4 |
Protection rating | IP20 |
Technical data | Description |
|---|---|
Data transfer medium | 2 x Ethernet RJ45 (switched, 10/100/1000 Mbit/s) |
Cable length | 100 m from switch to CX8290 |
Data transfer rate | 10/100/1000 Mbit/s |
Topology | star wiring, line topology |
Protocols (real-time) | optional PROFINET (TF627x), EtherNet/IP (TF628x), BACnet/IP (TF8020) |
Protocols (non-real-time) | all non-real-time-capable protocols that are based on TCP or UDP and do not require a real-time extension |