Technical data  | CX8095  | 
|---|---|
Processor  | Arm9™, 400 MHz  | 
Internal main memory  | 64 MB RAM (internal, not expandable)  | 
Web-based Management  | yes  | 
Flash memory  | MicroSD card (ATP) 512 MB (optionally 1, 2, 4, 8 GB)  | 
Interfaces  | 1 x USB device (behind front flap)  | 
Protocols  | EtherNet/IP (Slave), ADS, ModbusTCP, TCP/IP, UDP/IP  | 
Interface for I/O terminals  | K-bus or E-bus, automatic recognition  | 
Process data on the K-bus  | max. 2 kB input data  | 
Diagnostic LED  | 1 x power, 1 x TC status, 2 x bus status  | 
Clock  | internal battery-backed clock (RTC) for time and date (battery exchangeable)  | 
Operating system  | Microsoft Windows CE 61)  | 
Control software  | TwinCAT PLC runtime (from version 2.11 R3)  | 
Programming  | TwinCAT PLC  | 
Programming languages  | IEC 61131-3  | 
Online Change  | Yes  | 
Up/download code  | yes/yes  | 
Power supply  | 24 VDC (-15%/+20%)  | 
1-second UPS  | integrated (1 MB on microSD card)  | 
Power supply for I/O terminals (K-bus or E-bus)  | max. 2 A  | 
Power contacts current load  | max. 10 A  | 
Max. power consumption  | 3 W  | 
Max. power consumption E-bus/K-bus  | 10 W (5 V/max. 2 A)  | 
Dielectric strength  | 500 V (supply / internal electronics)  | 
Dimensions (W x H x D)  | 64 mm x 100 mm x 73 mm  | 
Weight  | approx. 180 g  | 
Permissible ambient temperature during operation  | 0° C ... +55 °C  | 
Permissible ambient temperature during storage  | -25° C ... +85° C  | 
Installation position  | see chapter Installation positions  | 
Relative humidity  | 95% no condensation  | 
Vibration/shock resistance  | conforms to EN 60068-2-6 / EN 60068-2-27  | 
EMC immunity/emission  | conforms to EN 61000-6-2/EN 61000-6-4  | 
Protection rating  | IP20  | 
System data  | Ethernet (CX8095)  | 
Number of I/O modules  | control-dependent  | 
Number of I/O points  | control-dependent  | 
Data transfer medium  | 4 x 2 twisted pair copper cable; category 5 (100 Mbaud), shielded  | 
Cable length  | 100 m  | 
Data transfer rate  | 100 Mbaud  | 
Topology  | star wiring, line topology  | 