DIP switch

CAUTION

DIP switches as ignition source in potentially explosive atmospheres

Gases or dusts can be ignited by a spark discharge when DIP switches are used.

Switch off the power supply and wait until the 1-second UPS has discharged. Ensure that there is no explosive atmosphere before you use DIP switches.

10-pin DIP switch S101

The DIP switch has only one meaning for the EtherCAT interfaces X101 and X102.

DIP switch 1:

DIP switch S101

Meaning

9

Reserved

10

Reserved

1..8

Hot-Connect address (see EtherCAT slave interface)

2-pin DIP switch (under the flap between the battery and the SD card slot)

Requirements

DIP switch (red)

Meaning

1 OFF and 2 OFF

normal mode, TwinCAT is started

1 ON and 2 OFF

The CX starts in Config mode, the internal flash memory or the SC card of the CX80xx can be accessed via the USB interface (e.g. for an image update).

1 OFF and 2 ON

Restore the registry

1 ON and 2 ON

reserved