Analog signal mode
The single-ended inputs 7 and 8 acquire signals in the range of 0 to 10 V.
The voltage is digitized with a resolution of 12 bits. LEDs are used to indicate the signal state.
Technical data | CX7293 |
|---|---|
Technology | single ended |
Number of inputs | 2 |
Signal voltage | 0…10 V |
Internal resistance | 500 kΩ |
Input filter cut-off frequency | 2 kHz |
Resolution | 12-bit (16-bit representation) |
Measuring error | < ±0.3 % (relative to full scale value) |
Connection cross-section | e*: 0.08…1.5 mm², |
Connection cross section AWG | e*: AWG 28…16, |
Strip length | 8 … 9 mm |
*e: single-wire, solid wire; f: stranded wire; a: with ferrule