Cycle time ≥1 ms
![Cycle time ≥1 ms 1:](Images/jpg/10805938827__Web.jpg)
Yellow and red: Mapping and update of the IOs.
Light grey: Time remaining until the task begins again (OS).
Dark grey: PLC cycle.
![Cycle time ≥1 ms 2:](Images/jpg/10805940747__Web.jpg)
Red: Output update.
Grey: CPU processing of the multifunction IOs.
Yellow: Input update (from a cycle time of 1 ms there is a waiting period of up to approx. 80% of the cycle time before the update of the input signals so that the inputs are read as late as possible, i.e. before the next cycle).
![Cycle time ≥1 ms 3:](Images/jpg/10805942667__Web.jpg)