Incremental encoder mode

In incremental encoder mode, the CX7050 can be configured as an interface for direct connection of 24 V incremental encoders. A quadruple evaluation is used and both high level and low level are detected at input 1 and input 2.

Incremental encoder mode 1:Fig.34: Configurable inputs and outputs in incremental encoder mode.

The range of functions in encoder mode corresponds to the range of functions in counter mode. In addition, the counter value at input 3 can be latched, i.e. the value is entered in the process data on a high level at input 3. Alternatively, the counter can be reset on a high level at input 3.

In addition, output 1 can be switched depending on the counter value. Output 2 can be switched from the PLC. This allows fast control signals for field devices to be used and switched.

Incremental encoder mode 2:
Technical data, multi-function I/Os in encoder mode.

Technical data

CX7050

Technology

Incremental encoder interface

Nominal voltage

24 V DC (-15 %/+20 %)

Specification

EN 61131-2, type 3

Encoder connection

1 x A, B: 24 V, single-ended

Additional inputs

Latch input, 24 V DC

Cut-off frequency

250,000 increments/s (with 4-fold evaluation), corresponds to 62.5 kHz

Counter depth

32-bit

Quadrature decoder

4-fold evaluation

Max. output current

24 V/0.5 A (short-circuit proof)

Special features

Latch function, software gate, set counter, switch outputs, reset counters

Connection cross-section

e*: 0.08…1.5 mm²,
f*: 0.25…1.5 mm²,
a*: 0.14…0.75 mm²

Connection cross section AWG

e*: AWG 28…16,
f*: AWG 22…16,
a*: AWG 26…19

Strip length

8 … 9 mm

*e: single-wire, solid wire; f: stranded wire; a: with ferrule