Technical data
| CX7050 |
---|---|
Dimensions (W x H x D) | 49 mm x 100 mm x 73 mm |
Weight | 142 g |
Technical data | CX7050 |
---|---|
Processor | ARM Cortex™ M7, 480 MHz |
Number of cores | 1 |
Flash memory | 512 MB microSD (optionally 1 GB, 2 GB, 4 GB or 8 GB) |
Main memory | 32 MB SDR (internal, non-extendable) |
Number of inputs | 8 multifunction inputs (24 V DC) |
Number of outputs | 4 multifunction outputs (24 V DC, 0.5 A, 1-wire technique) |
NOVRAM | 4 kB |
Interfaces | 1 x RJ45 10/100 Mbit/s, 1x USB (max 12 Mbit/s, max 100 mA) |
Bus interface | D-sub connector, 9-pin, 1 x CANopen commander (master), CAN 2.0A/2.0B |
Data transfer rate | 10, 20, 50, 100, 125, 250, 500, 800, 1000 kbaud |
Diagnostic LED | 1 x TC Status, 1 x WD LED, 1 x ERR LED |
Clock | internal, capacitor-buffered real-time clock for time and date (memory > 21 days) |
Operating system | TC/RTOS |
Control software | TwinCAT 3 Runtime (XAR) |
Power supply | 24 VDC (-15 %/+20 %) |
Max. power consumption | < 2 W (max. 12 W with E-bus/K-bus) |
TwinCAT 3 functions included | TC1000 TwinCAT 3 ADS, TC1100 TwinCAT 3 I/O, TC1200 TwinCAT 3 PLC, TF4100 TwinCAT 3 Controller Toolbox, TF4110 TwinCAT 3 Temperature Controller, TF6255 TwinCAT 3 Modbus RTU, TF6340 TwinCAT 3 Serial Communication, TF6701 TwinCAT 3 IoT Communication (MQTT), TF6730 TwinCAT 3 IoT Communicator |
Approvals | CE, UL |
Technical data | CX7050 |
---|---|
I/O connection | via power supply terminal (E-bus or K-bus, automatic recognition) |
Power supply for I/O terminals | max. 1.5 A (installation position any, temp. -25...45 °C) |
Power contacts current load | max. 10 A |
Process data on the K-bus | max. 512 bytes In and 512 bytes Out |
max. number of terminals (K-bus) | 64 (255 with K-bus extension) |
E-bus process data | max. 4 kB In and 4 kB Out |
max. number of terminals (E-bus) | up to 65534 terminals. |
Technical data | CX7050 |
---|---|
Ambient temperature during operation | -25° C ... +60° C |
Ambient temperature during storage | -40° C ... +85° C |
Relative humidity | 95 % no condensation |
Vibration resistance | conforms to EN 60068-2-6 |
Shock resistance | conforms to EN 60068-2-27 |
EMC immunity | conforms to EN 61000-6-2 |
EMC emission | conforms to EN 61000-6-4 |
Protection rating | IP20 |
Technical data | CX7050 |
---|---|
Data transfer medium | 4 x 2 twisted pair copper cables category 5 (100 Mbit/s) |
Cable length | 100 m from switch to CX7050 |
Data transfer rate | 10/100 Mbit/s |
Topology | star wiring |
Protocols | all non-real-time-capable protocols that are based on TCP or UDP and do not require a real-time extension |
Technical data | CX7050 |
---|---|
Fieldbus | CANopen |
Data transfer rate | 10, 20, 50, 100, 125, 250, 500, 800, 1,000 kbaud |
Bus interface | 1 x D sub-socket, 9-pin |
Bus devices | max. 64 |
max. process image | 512 Tx PDOs / 512 Rx PDOs |
Autobaud | - |
Electrical isolation | Yes |
Protocol |
|
CANopen slave | Yes |
CAN (virtual slave) | Yes |
ADS Interface | yes (only via Ethernet) |
Services |
|
CAN Layer 2 | Yes |
CAN 2.0A | Yes |
CAN 2.0B | Yes, can only be used via the CAN interface |
Technical data | CX7050 parameterized as slave |
---|---|
Fieldbus | CANopen |
Data transfer rate | 10, 20, 50, 100, 125, 250, 500, 800, 1,000 kbaud |
Bus interface | 1 x D sub-socket, 9-pin |
Extendable process image | Up to 3 virtual slaves in addition |
max. process image | 4 slaves x (16 Tx PDOs / 16 Rx PDOs (8 bytes per PDO)) |
Autobaud | Yes |
Electrical isolation | Yes |
Protocol |
|
CANopen slave | Yes |
CAN (virtual slave) | 4 (3 virtual CANopen nodes) |
ADS Interface | yes (only via Ethernet) |
Services |
|
CAN Layer 2 | No |
CAN 2.0A | acc. to CANopen |
CAN 2.0B | No |