Replace the battery
Notice | |
Fire and explosion hazard There is a risk of fire and explosion if the battery is short-circuited.
|
The battery must be replaced every 5 years. Replace the battery with a CR2032 battery (3 V, 225 mAh). The battery compartment is below the front flap.
The battery powers the built-in clock and thus buffers the time and date. The time and date are displayed incorrectly if the battery is empty or the battery is removed. Be aware of this behavior for your hardware and software configuration and reset the time and date in the BIOS after a battery change. If the operating system receives the time from an NTP server, the time and date can be set via the operating system.
Requirements:
- The embedded PC is switched off.
Replace the battery as follows:
- 1. Open the front flap with a spatula or screwdriver.
- 2. Push the side flap to the left.
- 3. Carefully lever the battery out of the bracket with a plastic spatula.
- 4. Push the new battery into the battery compartment. The positive pole points to the left towards the DVI interface.
- The battery change is complete. Close the side and front flaps and reset the date and time in the BIOS.
To dispose of the battery, remove it, stick insulating tape over the poles and take it to the local battery recycling.