Technical data
  | CX5230  | CX5240  | 
|---|---|---|
Dimensions (W x H x D)  | 142 mm x 100 mm x 92 mm  | |
Weight  | approx. 1195 g  | |
Technical data  | CX5230  | CX5240  | 
|---|---|---|
Processor  | Intel Atom® x5-E3930, 1.3 GHz  | Intel Atom® x5-E3940, 1.6 GHz  | 
Number of cores  | 2  | 4  | 
Main memory  | 4 GB DDR4-RAM  | 8 GB DDR4-RAM  | 
Flash memory  | Slot for CFast card (card not included), slot for MicroSD card  | |
1-second UPS  | integrated (1 MB on CFast card)  | |
Power supply  | 24 V DC (-15 %/+20 %)  | |
Max. power consumption  | 16 W  | 18 W  | 
Max. power consumption (with UPS charging)  | 34 W  | 34 W  | 
Max. power consumption E-bus/K-bus  | 10 W (5 V/max. 2 A)  | |
Dielectric strength  | 500 V (supply / internal electronics)  | |
Operating system  | Microsoft Windows 10 IoT Enterprise LTSC, TwinCAT/BSD  | |
Control software  | TwinCAT 3  | |
Secure element  | fTPM 2.0 (UEFI BIOS and 64-bit Windows 10 version 1809 or higher required)  | |
Diagnostic LED  | 1 x power, 1 x TC status, 1 x flash access, 2 x bus status  | |
Clock  | Internal battery-backed clock for time and date (battery replaceable)  | |
Approvals  | CE, UL  | |
Technical data  | Description  | 
|---|---|
I/O connection  | via power supply terminal (E-bus or K-bus, automatic recognition)  | 
Power supply for I/O terminals  | max. 2 A  | 
Power contacts current load  | max. 10 A  | 
Process data on the K-bus  | max. 2048 bytes input and 2048 bytes output  | 
max. number of terminals (K-bus)  | 64 (255 with K-bus extension)  | 
max. number of terminals (E-bus)  | up to 65534 terminals.  | 
Technical data  | Description  | 
|---|---|
Ambient temperature during operation  | -25° C ... +60 °C  | 
Ambient temperature during storage  | -40° C ... +85° C  | 
Relative humidity  | 95 % no condensation  | 
Vibration resistance  | 10 frequency sweeps, in 3-axis  | 
Shock resistance  | 1000 shocks in each direction, in 3 axes  | 
EMC immunity  | conforms to EN 61000-6-2  | 
EMC emission  | conforms to EN 61000-6-4  | 
Protection rating  | IP20  | 
Technical data  | CX5230  | CX5240  | 
|---|---|---|
Processor graphics  | Intel® HD Graphics 500  | |
Shader model  | 6.4  | |
DirectX  | 12  | |
OpenGL  | 4.6  | |
Technical data  | Description  | 
|---|---|
LAN  | 2 x RJ 45, 10/100/1000 Mbit/s  | 
USB  | 4 x USB 3.0 each rated at 900 mA, type A  | 
DVI-D  | Resolution on the monitor in pixels:  | 
Technical data  | Description  | 
|---|---|
DVI-D  | Resolution on the monitor in pixels: 640 x 480 to 1920 x 1200  | 
DisplayPort  | Resolution on the monitor in pixels: max. 2560x1600  | 
RS232  | D-sub connector, 9-pin  | 
RS422/RS485  | D-sub connector, 9-pin  | 
EtherCAT slave  | 2 x RJ 45, EtherCAT IN and OUT  | 
PROFIBUS  | D-sub connector, 9-pin  | 
CANopen  | D-sub connector, 9-pin  | 
PROFINET RT  | 2 x RJ-45 switches  |