PROFIBUS (x310)
Pin 6 transfers 5 VDC, pin 5 transfers GND for the active termination resistor. These must never be used for other functions, as this can lead to destruction of the device.
Pins 3 and 8 transfer the PROFIBUS signals. These must never be swapped over, as this will prevent communication.
The Profibus bus line is connected via a 9-pin D-sub with the following pin assignment:
Pin  | Connection  | 
|---|---|
1  | Shielding  | 
2  | not used  | 
3  | RxD/TxD-P  | 
4  | not used  | 
5  | GND  | 
6  | +5 VDC  | 
7  | not used  | 
8  | RxD/TxD-N  | 
9  | not used  | 
PROFIBUS line  | D-sub  | 
|---|---|
B red  | Pin 3  | 
A green  | Pin 8  | 
For the PROFIBUS optional interface (x310), documentation with further information is available:
https://infosys.beckhoff.com/content/1033/m310_b310_profibus_optioninterface/index.html?id=2233561431434830097
Document name  | 
|---|
CXxxxx-M310/B310 | Profibus Optional Interface  |