BIOS settings
The 1-second UPS can be switched on or off via the BIOS. The parameters of the 1-second UPS are displayed in the following menu and can be adjusted if necessary:
Advanced > Power Controller Options
Advanced | ||
Bootloader version | 1.00-23 | Enables/disables the UPS |
Firmware version | 1.00-77 | |
Mainboard serial no | 120003414250178 | |
Mainboard Prod. Date (Week.Year) | 44.14 | |
Mainboard BootCount | 4711 | |
Mainboard operation time | 1224 min (20 h) | |
Voltage (Min/Max) | 5.00 V / 5.20 V | |
Temperature (Min/Max) | 15 °C / 63 °C | |
|
| |
USB-Port voltage | [Off in S3-5] | |
Watchdog timer mode | [Compatibility mode] | |
|
| |
1-second Uninterruptable Power Supply (SUPS) | → ←: Select Screen | |
SUPS Enable | [Enable] | |
Hold Usb | [Enable] | |
Delay | 0 | |
|
| |
SUPS Firmware version | 1.09 | |
Current Power source | On Line | |
Battery load level | 100% | |
Powerfail counter | 42 |
SUPS Enable
Options: Enable / Disable
Switches the 1-second UPS on or off.
Hold USB
Options: Enable / Disable
Switches off the power supply for the USB ports in UPS mode.
Delay
Options: 0…255 seconds
Start delay with which the 1-second UPS is charged.
SUPS Firmware version
Firmware version
Current Power source
Status of the power supply: On Line / Battery
Battery load level