PROFIBUS (x310)
Pin 6 transfers 5 VDC, pin 5 transfers GND for the active termination resistor. These must never be used for other functions, as this can lead to destruction of the device.
Pins 3 and 8 transfer the PROFIBUS signals. These must never be swapped over, as this will prevent communication.
The Profibus bus line is connected via a 9-pin D-sub with the following pin assignment:
Pin | Connection |
|---|---|
1 | Shielding |
2 | not used |
3 | RxD/TxD-P |
4 | not used |
5 | GND |
6 | +5 VDC |
7 | not used |
8 | RxD/TxD-N |
9 | not used |
PROFIBUS line | D-sub |
|---|---|
B red | Pin 3 |
A green | Pin 8 |
For the PROFIBUS optional interface (x310), documentation with further information is available:
https://infosys.beckhoff.com/content/1033/m310_b310_profibus_optioninterface/index.html?id=2233561431434830097
Document name |
|---|
CXxxxx-M310/B310 | Profibus Optional Interface |