CX5010 - Technical data

CX5010 - Technical data 1:

The basic configuration of the CX5010 includes a 128 MB Compact Flash card. The basic configuration includes two Ethernet RJ-45 interfaces, four USB-2.0 interfaces and a DVI-D interface.

Technical data

CX5010

Processor

Intel® Atom™ Z510 processor, 1.1 GHz clock frequency

Internal Flash memory

128 MB Compact Flash card (optionally extendable)

Internal main memory

512 MB RAM (interior, not expandable)

Interfaces

2 x RJ 45, 10/100/1000 Mbit/s, DVI-D, 4 x USB 2.0

Diagnostics LED

1 x power, 1 x TC status, 1 x flash access, 2 x bus status

Clock

Internal clock with battery backup for time and date (battery replaceable)

Operating system

Microsoft Windows CE or Microsoft Windows Embedded Standard

Control software

TwinCAT PLC runtime or TwinCAT NC PTP runtime

Power supply

24 V DC (-15 %/+20 %)

Current supply

I/O terminals 2 A

Max. power loss

12 W (including system interfaces)

Dielectric strength

500 Veff (supply/internal electronics)

Dimensions (H x W x D)

100 mm x 106 mm x 92 mm

Weight

approx. 575 g

Operating/storage temperature

-25 °C ... +60 °C/-40 °C ... +85 °C

Relative humidity

95 % no condensation

Vibration/shock resistant

conforms to EN 60068-2-6/EN 60068-2-27/ 29

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP 20

Further Information: www.beckhoff.de/CX5010