Connect Embedded PC
Notice | |
Damage to the Embedded PCs The Embedded PCs may be damaged during wiring.
|
An external voltage source providing a 24 V DC voltage (-15 % / +20 %) is required for the CX2100-0914 power supply unit.
The cabling of the Embedded PC in the control cabinet must be done in accordance with the standard EN 60204-1:2006 PELV = Protective Extra Low Voltage:
- The "PE" and "0 V" conductors of the voltage source for a basic CPU module must be on the same potential (connected in the control cabinet).
- Standard EN 60204-1:2006, section 6.4.1:b stipulates that one side of the circuit, or a point of the energy source for this circuit must be connected to the protective earth conductor system.
Connection example with CX2020 basic CPU module and CX2100-0914 power supply unit:
No. | Description |
|---|---|
1 | The upper spring-loaded terminals identified with "24 V" and "0 V" supply the basic CPU module and the terminal bus (data transfer via K- or E-bus). |
2 | The spring-loaded terminals identified as "+", "-" and "PE" supply the Bus Terminals via the power contacts and the sensors or actuators connected to the Bus Terminals. |
The cables of an external voltage source are connected to the power supply unit with spring-loaded terminals.
Conductor cross-section | 0,5 ... 2,5 mm2 | AWG 20 ... AWG 14 |
Strip length | 8 ... 9 mm | 0.33 inch |
Connect the embedded PC as follows:
- 1. Open a spring-loaded terminal by slightly pushing with a screwdriver or a rod into the square opening above the terminal.
- 2. The wire can now be inserted into the round terminal opening without any force.
- 3. The terminal closes automatically when the pressure is released, holding the wire safely and permanently.
The voltage source has been connected to the power supply unit successfully when the two upper power supply terminal LEDs light up in green. |
|
|
Notice | |
Interrupting / switching off the power supply To switch off the Embedded PC, do not disconnect the ground (0 V), because otherwise current may continue to flow via the shielding, depending on the device, and damage the Embedded PC or peripheral devices.
|