ADS Services
Local process image task 1 port 800 or port 801
Data can be read from and written to the local process image. If it is necessary for outputs to be written, it is important to ensure that they are not used by the local PLC, because the local controller will overwrite these values. The data is not associated with a watchdog, and therefore must not be used for outputs that would have to be switched off in the event of a fault.
ADS services
AdsServerAdsState
AdsServerDeviceState
AdsServerType
Register port 100
The ADS port number in the Bus Terminal Controller for register communication is fixed, being set at 100.