DP State of the Slaves
|
Value |
Description |
|---|---|
|
0 |
No Error - station is exchanging data |
|
1 |
Station deactivated - slave has been deactivated, temporary state during StartUp |
|
2 |
Station not exists - slave does not reply on the bus -> check whether slave is switched on, whether PROFIBUS plug is in, correct station address or bus cables |
|
3 |
Master lock - slave is exchanging data with another master -> remove other master from bus or release slave again by other master |
|
4 |
Invalid slave response - incorrect answer from slave, occurs temporarily if slave has ceased data exchange as a result of a local event |
|
5 |
Parameter fault - check whether Bus Coupler / GSD file is correct, that station address is correct or that UserPrmData settings are correct |
|
6 |
Not supported - DP function is not supported -> check whether GSD file is correct or whether station address is correct |
|
7 |
Config fault – configuration fault -> check whether the added terminals / modules are correct |
|
8 |
Station not ready -> station starting up, temporarily displayed during StartUp |
|
9 |
Static diagnosis - slave signalling static diagnosis and cannot deliver valid data at present -> check operating state at the slave |
|
10 |
Diagnosis overflow - slave signalling a diagnosis overflow -> check diagnostic data (using ADS-Read, see below) and operating state at the slave |
|
11 |
Physical fault - physical fault interfering with slave response -> check cables |
|
13 |
Severe bus fault ->check cabling |
|
14 |
Telegram fault - slave responding with an invalid telegram -> must not occur |
|
15 |
Station has no resources -> slave has insufficient resources for the telegram -> check that GSD file is correct |
|
16 |
Service not activated -> temporary fault when slave ceases data exchange due to a local event, otherwise check whether DP functions are disabled at the slave |
|
17 |
Unexpected telegram -> can occur temporarily if two PROFIBUS networks are connected together or check whether bus times for the second master are set identically |
|
18 |
Station ready -> can occur temporarily during StartUp and until the task is started |
|
19 |
DPV1 StartUp -> occurs temporarily after the DP has started up if there is still data to be sent by DPV1 Write |
|
128 |
FC310x in slave mode, waiting for data transfer -> slave was parameterized and configured but has not yet received a Data_Exchange telegram |
|
129 |
FC310x in slave mode, waiting for configuration -> slave was parameterized, but has not yet received a Chk_Cfg telegram |
|
130 |
FC310x in slave mode, waiting for parameters -> slave was not yet parameterized, waiting for Set_Prm (Lock) telegram |