Adapter RAM Hardware address overview

available memory addresses CX1020: D0000-DFFFF (hex)

Base Address (hex)

End Address (hex)

Size(Bytes)(hex)

Access Type

Description

D0000

D0FFF

1000

R/W

CX1100-0002/3 Dual Ported RAM

D1000

D100F

10

R/W

CX1100 Auxiliary Control Block( LCD Display, misc. registers)

D1010

D101F

10

R/W

CX1100-0900 UPS Control Block

D2000

D3FFF

2000

R/W

CX1100 Non Volatile RAM

D4000

D5FFF

2000

R/W

CX1500-M310 Profibus Master DPRAM

D6000

D7FFF

2000

R/W

CX1500-M510 CANopen Master DPRAM

D8000

D9FFF

2000

R/W

CX1500-M520 DeviceNet Master DPRAM

DA000

DBFFF

2000

R/W

CX1500-M200 Lightbus Master DPRAM

DC000

DDFFF

2000

R/W

CX1500-M750 Sercos Master DPRAM

 

For some fieldbus connections (all Slave modules) the base addresses are mapped in the memory region upper DFFFF(hex). So this modules must be ordered with other base addresses. The same situation takes place if more than two or  more master modules of same type are used (for more see note below).  The order numbers for the modules are:

order number

alternative ISA address

Master connection

CX1500-Mxxx-0001

D4000

CX1500-Mxxx-0002

D6000

CX1500-Mxxx-0003

D8000

CX1500-Mxxx-0004

DA000

CX1500-Mxxx-0005

DC000

Slave connection

CX1500-Bxxx-0001

D4000

CX1500-Bxxx-0002

D6000

CX1500-Bxxx-0003

D8000

CX1500-Bxxx-0004

DA000

CX1500-Bxxx-0005

DC000

 

Replace xxx with the following number for the requested fieldbus system:

 

NOTICE

Two connection modules (master or slave) can be used simultaneously. If more than two connections are needed call Beckhoff Automation GmbH for further information.